The energy absorption capability and time-to-failure of varistors used in station-class metal-oxide surge arresters

被引:45
|
作者
Ringler, KG
Kirkby, P
Erven, CC
Lat, MV
Malkiewicz, TA
机构
[1] Ontario Hydro Technologies, Toronto
关键词
metal-oxide surge arresters; varistors; energy absorption capability; current pulses; current density; current duration; testing; confidence limits; failure probability; failure modes; time-to-failure; standards;
D O I
10.1109/61.568242
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Varistors for use in station-class surge arresters were tested to destruction to determine their energy absorption capability at current levels ranging from 0.8 A(peak) to 35 kA(peak). Typical mean values increased from 400-600 J/cm(3) at the lower current end to 1,600-2,000 J/cm(3) at 35 kA(peak). The product of the mean time-to-failure and the mean current was found to be a constant over five orders of magnitude. The varistor failure mode was found to be a characteristic of the current magnitude. It is recommended that standard test methods be developed for the energy absorption capability of metal-oxide surge arresters, and be included in relevant standards.
引用
收藏
页码:203 / 212
页数:10
相关论文
共 14 条
  • [1] Failure study of metal-oxide surge arresters
    Akbar, M
    Ahmad, M
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1999, 50 (02) : 79 - 82
  • [2] DEVELOPMENT OF METAL-OXIDE VARISTORS FOR GAS-INSULATED SURGE ARRESTERS
    POTTER, ME
    SOKOLY, TO
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (07): : 2217 - 2220
  • [3] AN EXAMINATION OF THE POLLUTION PERFORMANCE OF GAPPED AND GAPLESS METAL-OXIDE STATION CLASS SURGE ARRESTERS
    LENK, DW
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (02): : 337 - 344
  • [4] Degradation Effects on Energy Absorption Capability and Time to Failure of Low Voltage Metal Oxide Varistors
    Khanmiri, Dawood Talebi
    Ball, Roy
    Lehman, Brad
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (05) : 2272 - 2280
  • [5] Recent Experimental Findings on the Single and Multi-Impulse Energy Handling Capability of Metal-Oxide Varistors for Use in High-Voltage Surge Arresters
    Tuczek, Maximilian Nikolaus
    Hinrichsen, Volker
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (05) : 2197 - 2205
  • [6] New Manufacturing Process for the Metal Oxide Varistors used on Low Voltage Surge-Arresters
    Paun, Adrian Constantin
    Vatau, Doru
    Frigura-Iliasa, Flaviu Mihai
    Andea, Petru
    Frigura-Iliasa, Mihaela
    Balcu, Florin Ionel
    [J]. PROCEEDINGS OF THE 2017 18TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE), 2017, : 351 - 354
  • [7] Comments on metal oxide surge arresters surges energy absorption capacity
    Martinez, MLB
    Zanetta, LC
    [J]. CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 498 - 501
  • [8] Failure mode tests for distribution type metal-oxide surge arresters with polymeric housing
    Colombo, E
    deNigris, M
    Sironi, A
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) : 240 - 252
  • [9] Comparisons of in-service and laboratory failure modes of metal-oxide distribution surge arresters
    Darveniza, M
    Saha, TK
    Wright, S
    [J]. 2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, 2000, : 2093 - 2100
  • [10] Reliability Analysis of Low-Voltage Metal-Oxide Surge Arresters Using Accelerated Failure Time Model
    Bokoro, Pitshou
    Doorsamy, Wesley
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 3139 - 3146