Static Parameter Detection and Identification of Power Grid Branch Based on PMU Measurement

被引:0
|
作者
Cui Yunfeng [1 ]
机构
[1] North China Elect Power Univ, Beijing 102206, Peoples R China
关键词
static parameter; detection and identification; partition; local identification; ERRORS;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
With the wide coverage of the WAMS in power system, it is possible to detect the static parameters of power grid branch with PMU measurement. The paper presents a method, that is, by the reformation of state space and linear static state estimation. To improve branch parameter computation redundancy, KCL equations are added to the measurement equation which is presented in parameter space. Through a combination of global detection and local identification, combined with much statistical analysis of measurement profiles, the adverse effects brought by the lack of precision of PMU measurement can be minimized. Finally, a New England 39 buses test system and a practical example are presented to verify the effectiveness of the proposed algorithm.
引用
收藏
页码:313 / 318
页数:6
相关论文
共 50 条
  • [1] A New Approach to Branch Parameter Estimation of Power Grid Based On PMU
    Zhou Suquan
    Zhang Liying
    Zhang Yanjun
    Xu Yan
    Lin Guihua
    Li Bijun
    Li Lei
    Gong Chengming
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [2] Detection of PMU spoofing in power grid based on phasor measurement analysis
    Yasinzadeh, Mohammad
    Akhbari, Mahdi
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (09) : 1980 - 1987
  • [3] Line Parameter Estimation Based on PMU Application in the Power Grid
    Oleinikova, Irina
    Mutule, Anna
    Grebesh, Ervin
    Lvovs, Aleksandrs
    2015 IEEE 5TH INTERNATIONAL CONFERENCE ON POWER ENGINEERING, ENERGY AND ELECTRICAL DRIVES (POWERENG), 2015, : 453 - 457
  • [4] Offline Detection, Identification, and Correction of Branch Parameter Errors Based on Several Measurement Snapshots
    Castillo, Madeleine R. M.
    London, Joao B. A., Jr.
    Bretas, Newton Geraldo
    Lefebvre, Serge
    Prevost, Jacques
    Lambert, Bertrand
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (02) : 870 - 877
  • [5] Grid equipment parameter error identification based on mean algebraic sum of branch measurement normalized residuals
    Yan, W. (cquyanwei@21cn.com), 1600, Electric Power Automation Equipment Press (33):
  • [6] Comparison of State Identification of VRE Power Grid based on PMU Big Data
    Lee K.-M.
    Park C.-W.
    Transactions of the Korean Institute of Electrical Engineers, 2023, 72 (01): : 46 - 51
  • [7] State estimation based branch parameter estimation method for power grid
    Ning, Liao-Yi
    Sun, Hong-Bin
    Wu, Wen-Chuan
    Zhang, Bo-Ming
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2009, 29 (01): : 7 - 13
  • [8] Corrigendum: Detection of PMU spoofing in power grid based on phasor measurement analysis (vol 12, pg 1980, 2018)
    Yasinzadeh, M.
    Akhbari, M.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (16) : 3910 - 3910
  • [9] Off-line Detection, Identification and Correction of Branch Parameter Errors Based on Several Measurement Snapshots
    Castillo, Madeleine
    Augusto London Junior, Joao Bosco
    Bretas, Newton Geraldo
    Lefebvre, Serge
    Prevost, Jacques
    Lambert, Bertrand
    2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2011,
  • [10] PMU Placement with Power Grid Partitioning for Line Outage Detection
    Alhalaseh, Rana
    Tokel, Halil Alper
    Chakraborty, Subhodeep
    Alirezaei, Gholamreza
    Mathar, Rudolf
    2019 4TH INTERNATIONAL CONFERENCE ON SMART AND SUSTAINABLE TECHNOLOGIES (SPLITECH), 2019, : 353 - 358