Current Limiting Characteristics of Transformer Type HTS Superconducting Fault Current Limiter with Rewound Structure

被引:7
|
作者
Shirai, Y. [1 ]
Nii, T. [1 ]
Oda, S. [1 ]
Shiotsu, M. [1 ]
机构
[1] Kyoto Univ, Sakyo Ku, Kyoto 6068501, Japan
关键词
D O I
10.1088/1742-6596/234/3/032053
中图分类号
O4 [物理学];
学科分类号
0702 ;
摘要
A transformer type SCFCL of HTS wire with rewound structure has a primary coil of BSCCO wire connected to a power system and has a secondary coil of also BSCCO wire short-circuited. Both HTS coils were wound co-axially with rewound structure to get longer wire, that is, larger resistance at the normal state. The rewound structure offers greater flexibility in the design of the inductance and resistance of the SCFCL. It was experimentally confirmed that the SCFCL gives an inductive limiting impedance for smaller fault current while the only secondary wire transits to normal state and for larger fault current, it can give a resistive component additively by the normal transition of the primary wire. The current limiting characteristics of the proposed SCFCL were discussed by experimental results. Excellent recovery characteristics, that is, the recovery under load operation and repetitive limiting operation were confirmed experimentally.
引用
收藏
页数:8
相关论文
共 50 条
  • [1] Current limiting characteristics of transformer type superconducting fault current limiter
    Yamaguchi, H
    Yoshikawa, K
    Nakamura, M
    Kataoka, T
    Kaiho, K
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2005, 15 (02) : 2106 - 2109
  • [2] Current limiting characteristics of transformer type superconducting fault current limiter with shunt impedance
    Yamaguchi, H.
    Kataoka, T.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2007, 17 (02) : 1919 - 1922
  • [3] Current Limiting Experiment of Transformer Type Superconducting Fault Current Limiter With Rewound Structure Using BSCCO Wire in Small Model Power System
    Oda, Sayaka
    Noda, Sho
    Nishioka, Hideyoshi
    Mori, Masato
    Baba, Jumpei
    Shirai, Yasuyuki
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2011, 21 (03) : 1307 - 1310
  • [4] Effect of magnetic saturation on the current limiting characteristics of transformer type superconducting fault current limiter
    Yamaguchi, H.
    Kataoka, T.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2006, 16 (02) : 691 - 694
  • [5] Current limiting characteristics of transformer type superconducting fault current limiter with shunt impedance and inductive load
    Yamaguchi, H.
    Kataoka, T.
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2008, 18 (02) : 668 - 671
  • [6] Characteristics analysis of transformer type superconducting fault current limiter
    Yamaguchi, H
    Kataoka, T
    Yaguchi, K
    Fujita, S
    Yoshikawa, K
    Kaiho, K
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2004, 14 (02) : 815 - 818
  • [7] Analysis of the DC Fault Current Limiting Characteristics of a DC Superconducting Fault Current Limiter Using a Transformer
    Cho, Kang-Cheol
    Park, Min-Ki
    Lim, Sung-Hun
    ENERGIES, 2020, 13 (16)
  • [8] Fault Current Limiting Characteristics of Transformer-Type Superconducting Fault Current Limiter Due to Winding Direction of Additional Circuit
    Han, Tae-Hee
    Ko, Seck-Cheol
    Lim, Sung-Hun
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2018, 28 (03)
  • [9] Resistive current limiting characteristics in magnetic shield type superconducting fault current limiter
    Onishi, T
    Matsui, A
    Nii, A
    INTERNATIONAL CRYOGENIC ENGINEERING CONFERENCE 1998, 1998, : 395 - 398
  • [10] Current limiting characteristics of a resistance-inductance type superconducting fault current limiter
    Zhang, Jing
    Dai, Shaotao
    Ma, Tao
    Li, Yan
    He, Darui
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2022, 601