Experience with Partial Discharge Measurements on Instrument Transformers in High Voltage Laboratory Acceptance Tests

被引:0
|
作者
Jacob, N. D. [1 ]
McDermid, W. M. [1 ]
机构
[1] Manitoba Hydro, Insulat Engn & Testing Dept, Winnipeg, MB, Canada
关键词
Instrument transformers; partial discharge; high-voltage techniques; oil insulation;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper highlights high-voltage laboratory acceptance tests performed by Manitoba Hydro on new 230kV current transformers (CTs). In performing these tests it was revealed that a number of CTs failed to meet requirements for partial discharge (PD). For the performance of PD tests, a modern digital PD measurement instrument was used. This instrumentation proved valuable in its ability to produce phase-resolved PD pattern plots which could be analyzed for identification of the defects causing discharge. From this work, much has been learned about the nature of PD in oil-paper insulated instrument transformers. Evidence from phase-resolved PD measurements suggested the presence of gas-filled voids within the insulation producing PD. It has been observed that PD in oil-paper insulation has some peculiar qualities; PDs can incept, then extinguish, and then re-incept, all while voltage stress may be held constant. Additional evidence suggests that the discharge activity may be influenced by exposure to extended periods of overvoltage prior to test. Findings show that extended exposure to overvoltage prior to PD measurement may cause instrument transformers to falsely pass PD tests.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] Partial Discharge Location in High Voltage Transformers
    Mohamed, R.
    Lewin, P. L.
    [J]. 2009 IEEE ELECTRICAL INSULATION CONFERENCE, 2009, : 200 - 204
  • [2] Voltage Dependence of Dissipation Factor Measurements on High Voltage Instrument Transformers
    Wallace, D. A.
    Kluss, J. V.
    Ahmed, Z.
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [3] PARTIAL DISCHARGE MEASUREMENTS ON TRANSFORMERS
    NICOLET, A
    [J]. BROWN BOVERI REVIEW, 1979, 66 (07): : 456 - 460
  • [4] Alternative methods of partial discharge measurements in power transformers - factory tests and diagnostics
    Szczechowski, Janusz
    Siodla, Krzysztof
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (10): : 89 - 94
  • [5] Partial Discharge Measurement to Predict the Lifetime of High Frequency High Voltage Transformers
    Guastavino, F.
    Della Giovanna, L.
    Galbiati, S.
    Massa, B.
    Torello, E.
    [J]. 2023 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, CEIDP, 2023,
  • [6] An Ultrawideband Partial Discharge Sensor for High-Voltage Power Transformers
    Dhara, Sourav
    Koley, Chiranjib
    Chakravorti, Sivaji
    [J]. IEEE SENSORS JOURNAL, 2024, 24 (10) : 16261 - 16269
  • [7] PARTIAL-DISCHARGE MEASUREMENT ON HIGH-VOLTAGE POWER TRANSFORMERS
    KAWAGUCHI, Y
    YANABU, S
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1969, PA88 (08): : 1187 - +
  • [8] Denoising Autoencoder for Partial Discharge Identification in Instrument Transformers
    Crivelaro, Matheus Goes
    Rodrigues, Douglas
    Gifalli, Andre
    Papa, Joao Paulo
    Gonzales, Carlos Guilherme
    de Souza, Andre Nunes
    da Silva, Gustavo Vinicius
    Silveira Neto, Erasmo
    [J]. 2024 31ST INTERNATIONAL CONFERENCE ON SYSTEMS, SIGNALS AND IMAGE PROCESSING, IWSSIP 2024, 2024,
  • [9] On-line partial discharge measurement on instrument transformers
    Blackburn, TR
    Phung, BT
    Liu, Z
    James, RE
    [J]. 1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, : 497 - 500
  • [10] Experience with partial discharge monitoring of high voltage motors
    Leung, YC
    MacAlpine, JMK
    [J]. APSCOM - 2000: 5TH INTERNATIONAL CONFERENCE ON ADVANCES IN POWER SYSTEM CONTROL, OPERATION & MANAGEMENT, VOLS 1 AND 2, 2000, : 306 - 310