Fault ride-through control of grid-connected photovoltaic power plants: A review

被引:63
|
作者
Al-Shetwi, Ali Q. [1 ,2 ]
Sujod, Muhamad Zahim [1 ]
Blaabjerg, Frede [3 ]
Yang, Yongheng [3 ]
机构
[1] Univ Malaysia Pahang, Fac Elect & Elect Engn, Pekan 26600, Pahang, Malaysia
[2] Univ Sci & Technol, Dept Elect Engn & Automat Control, Sanaa, Yemen
[3] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
关键词
Fault ride-through (FRT) requirements; Grid codes; low voltage ride through (LVRT); Photovoltaic (PV) system; Solar energy; LOW-VOLTAGE-RIDE; CONTROL STRATEGY; INVERTER TOPOLOGIES; WIND TURBINES; SYSTEM; CAPABILITY; ENHANCEMENT; INTEGRATION; CHALLENGES; GENERATION;
D O I
10.1016/j.solener.2019.01.032
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Over the recent years, the photovoltaic (PV) system generation and integration with utility grid became the most widely used energy resource among other renewable energies worldwide. Thereon, the integration of PV power plants (PVPPs) to the power grid and their dynamics during grid faults had become a critical issue in the new grid codes requirements. In line with this, the fault ride through (FRT) capability control of grid-connected PV power plants (GCPPPs) became the most important issue related to grid codes. In order to fulfill the FRT requirements imposed by grid codes, various approaches have been proposed in the last years. This paper presents an overview and comparison of several FRT capability enhancement approaches during grid fault conditions. A novel feature of this paper is to categorize FRT capability enhancement methods into two main groups depending on the control type and connection configuration including external devices based methods and modified controller based methods and then discuss their advantages and limitations in detail. A comparison between these methods in terms of grid code compliance, controller complexity and economic feasibility are also analyzed in this paper. According to the literature study, the FRT strategies based on external devices can be more effective. However, some of these methods come with significant increased cost. On the other hand, the modified controller-based FRT methods can achieve the FRT requirements at a minimal price. Among various types of control approaches, the modified inverter controller (MIC) is the highly efficient FRT capability approach.
引用
收藏
页码:340 / 350
页数:11
相关论文
共 50 条
  • [1] Modeling and Control of Grid-Connected Photovoltaic Power Plant With Fault Ride-Through Capability
    Al-Shetwi, Ali Q.
    Sujod, Muhamad Zahim
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2018, 140 (02):
  • [2] Fault Ride-through of a Grid-connected Photovoltaic System with Quasi Z Source Inverter
    Al-Durra, Ahmed
    Fayyad, Yara
    Muyeen, S. M.
    Blaabjerg, Frede
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2016, 44 (16) : 1786 - 1800
  • [3] Control Strategy of Low Voltage Ride-Through for Grid-Connected Photovoltaic Inverter
    Zhang, Peng
    Zhang, Guorong
    Wang, Haining
    [J]. 2015 IEEE 6TH INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS FOR DISTRIBUTED GENERATION SYSTEMS (PEDG), 2015, : 639 - 644
  • [4] Voltage Sag Detection in Grid-connected Photovoltaic Power Plant for Low Voltage Ride-through Control
    Al-Shetwi, Ali Qasem
    Sujod, Muhamad Zahim
    [J]. RECENT ADVANCES IN ELECTRICAL & ELECTRONIC ENGINEERING, 2019, 12 (04) : 384 - 392
  • [5] Research on the Control Technique of Low Voltage Ride-through for Grid-connected Photovoltaic Inverter
    Zhang, Ying
    Cao, Dufeng
    Yang, Zilong
    Wang, Yibo
    Xu, Honghua
    [J]. 2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [6] Enhancing low voltage ride-through capability of grid-connected photovoltaic plants using superconducting fault current limiters
    Li, Chao
    Wu, Qi
    Xin, Ying
    Li, Bin
    [J]. RENEWABLE ENERGY, 2024, 231
  • [7] Application of Dynamic Voltage Restorer in Fault Ride-Through of Grid-Connected Photovoltaic Storage System
    ZENG Guohui
    ZHANG Jie
    HUANG Bo
    [J]. Wuhan University Journal of Natural Sciences, 2020, 25 (04) : 343 - 351
  • [8] A review on current injection techniques for low-voltage ride-through and grid fault conditions in grid-connected photovoltaic system
    Hassan, Z.
    Amir, A.
    Selvaraj, J.
    Rahim, N. A.
    [J]. SOLAR ENERGY, 2020, 207 : 851 - 873
  • [9] Increase of fault ride-through capability for the grid-connected wind farms
    Ko, H. S.
    Jatskevich, J.
    Dumont, G. A.
    Moshref, A.
    [J]. 2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 718 - +
  • [10] Control Strategy of Low Voltage Ride-Through for Grid-Connected Photovoltaic Power System Based on Predictive Current
    Zhang, Mingguang
    Chen, Xiaojing
    [J]. MECHATRONICS ENGINEERING, COMPUTING AND INFORMATION TECHNOLOGY, 2014, 556-562 : 1753 - 1756