Research on Moisture Content Evaluation Algorithm of Transformer Oil-Paper Insulation System

被引:0
|
作者
Zhang, Mingze [1 ]
Liu, Ji [1 ]
Qi, Pengshuai [1 ]
Chen, Qingguo [1 ]
Lv, Jialu [1 ]
Sun, Yufei [1 ]
Chen, Xin [2 ]
机构
[1] Harbin Univ Sci & Technol, Harbin 150080, Heilongjiang, Peoples R China
[2] Heilongjiang Elect Power Res Inst, Harbin 150090, Heilongjiang, Peoples R China
基金
国家重点研发计划;
关键词
oil-paper insulation; moisture content; XY equivalent model; dielectric response; quantitative assessment;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
With the increase of the voltage level of the power grid, the role of the transformer in the power grid is becoming more and more important. Due to the transformer perennial outdoor operation condition, external moisture and internal insulation aging will cause the increase of moisture content in the transformer insulation pressboard. The increase in moisture content will greatly reduce the service life of the transformer. The aging degree of oil paper insulation is closely related to its moisture content. It has great significance to calculate the moisture content of the transformer. In order to use dielectric response technique for measuring the moisture content of transformer, the XY model of internal insulation and composite dielectric equivalent model are combined. Meanwhile, the basic data equation of the oil-immersed pressboard is obtained by using the frequency temperature translation method. The evaluation method of moisture content in oil-immersed pressboard based on dielectric loss factor curve can be obtained by continuous cyclic iterative calculation. In order to verify the accuracy of the moisture content assessment method in the oil-impregnated pressboard based on the equivalent model of the transformer, in this paper, a number of different proportional transformer equivalent models are designed in the laboratory. The accelerated aging test were performed at 130 degrees C of the equivalent model of different proportions, in different aging days, the algorithm proposed in this paper and the traditional titration method were used to analyze the different ratios moisture content of transformer equivalent model. The above experiment verifies the accuracy of the proposed algorithm.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] Time domain dielectric characteristics for quantitative assessment of moisture content in transformer oil-paper insulation
    Liu, Jiefeng
    Liao, Ruijin
    Lü, Yandong
    Yang, Lijun
    Gao, Jun
    Zhang, Yiyi
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (02): : 196 - 203
  • [2] Model moisture transport in oil-paper insulation of transformer: Theory and experiment
    Zhou, Junjie
    Wu, Zhicheng
    Guo, Yiran
    Zhang, Rui
    Zhu, Wenbing
    Zhang, Qiaogen
    [J]. HIGH VOLTAGE, 2024, 9 (04) : 879 - 887
  • [3] Quantitative Assessment of moisture content in Transformer Oil-paper Insulation Based on Extended Debye model and PDC
    Xia Guoqiang
    Wu Guangning
    [J]. 2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [4] Effect of Moisture Content on the Production and Partitioning of Furfural in Oil-Paper Insulation
    Feng, Dawei
    Yang, Lijun
    Liao, Ruijin
    Zhou, Luowei
    Lin, Yuandi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (06) : 2389 - 2397
  • [5] Diffusion Mechanism of Furfural in Transformer Oil-Paper Insulation Under Moisture Effect
    Geng, Chuhan
    Liu, Jiefeng
    Zhang, Heng
    Liu, Chuying
    Luo, Yiwen
    Zhang, Yiyi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (02) : 485 - 492
  • [6] Evaluation Method for Moisture Content and Aging Degree of Transformer Oil-paper Insulation Based on Frequency Dielectric Spectroscopy and Compensation Factor
    Wu G.
    Xia G.
    Su M.
    Zhu H.
    Yang F.
    Gao B.
    [J]. Gaodianya Jishu/High Voltage Engineering, 2019, 45 (03): : 691 - 700
  • [7] A Comparative Study of Conductivity and Moisture for Condition Assessment of Oil-Paper Insulation of a Transformer
    Ojha, S. K.
    Purkait, P.
    Chakravorti, S.
    [J]. 2015 INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2015, : 99 - 104
  • [8] Influence of Moisture Dispersion in Oil-paper Insulation on Dielectric Spectrum of Power Transformer
    Li, Jiajun
    Lv, Xiaolu
    Wang, Ke
    Li, Jinzhong
    Xia, Yuan
    Yang, Lijun
    Yang, Hao
    [J]. 2023 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, CEIDP, 2023,
  • [9] Research Progress on Influence of Water Content of Oil-paper Insulation on Partial Discharge of Converter Transformer
    Du B.
    Jiang J.
    [J]. Gaodianya Jishu/High Voltage Engineering, 2021, 47 (08): : 2932 - 2945
  • [10] Equilibrium moisture distribution in oil-paper insulation
    School of Electric Engineering, Southwest Jiaotong University, Chengdu 610031, China
    [J]. Gaodianya Jishu, 2007, 8 (27-30):