Simplified Analytic Approach of Pole-to-Pole Faults in MMC-HVDC for AC System Backup Protection Setting Calculation

被引:6
|
作者
Lan, Tongkun [1 ]
Li, Yinhong [1 ]
Duan, Xianzhong [1 ]
Zhu, Jia [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Hubei Elect Power Secur & High Efficiency Key Lab, Wuhan 430074, Hubei, Peoples R China
关键词
AC (alternating current) system backup protection; setting calculation; MMC-HVDC (multi-modular converter based high voltage direct current); pole-to-pole faults; fault analysis; DISTANCE PROTECTION; POWER;
D O I
10.3390/en11020264
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
AC (alternating current) system backup protection setting calculation is an important basis for ensuring the safe operation of power grids. With the increasing integration of modular multilevel converter based high voltage direct current (MMC-HVDC) into power grids, it has been a big challenge for the AC system backup protection setting calculation, as the MMC-HVDC lacks the fault self-clearance capability under pole-to-pole faults. This paper focused on the pole-to-pole faults analysis for the AC system backup protection setting calculation. The principles of pole-to-pole faults analysis were discussed first according to the standard of the AC system protection setting calculation. Then, the influence of fault resistance on the fault process was investigated. A simplified analytic approach of pole-to-pole faults in MMC-HVDC for the AC system backup protection setting calculation was proposed. In the proposed approach, the derived expressions of fundamental frequency current are applicable under arbitrary fault resistance. The accuracy of the proposed approach was demonstrated by PSCAD/EMTDC (Power Systems Computer-Aided Design/Electromagnetic Transients including DC) simulations.
引用
收藏
页数:16
相关论文
共 27 条
  • [1] Arm Overcurrent Analysis and Calculation of MMC-HVDC System with DC-link Pole-to-Pole Fault
    Jiang, Bin
    Gong, Yanfeng
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2018, 46 (02) : 177 - 186
  • [2] Improved Fault Current Calculation Method for Pole-to-Pole Faults in MMC Multi-Terminal HVDC Grids Considering Control Dynamics
    Langwasser, Marius
    De Carne, Giovanni
    Liserre, Marco
    Biskoping, Matthias
    2018 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2018, : 5529 - 5535
  • [3] Enhanced Independent Pole Control of Hybrid MMC-HVdc System
    Xiang, Wang
    Lin, Weixing
    Xu, Lie
    Wen, Jinyu
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) : 861 - 872
  • [4] Transient Operation Characteristics of Offshore Wind Power Generation Integration System With MMC-HVDC Under Pole-to-pole Short-circuit Fault
    Wang J.
    Yao J.
    Liu K.
    Huang S.
    Gou S.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (10): : 3755 - 3765
  • [5] Analytic Calculation of Pole-to-Pole Faults in Twelve-phase Synchronous Generator-rectifier systems
    Ma F.
    Fu L.
    Guo Y.
    Yi X.
    Ji F.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (20): : 7117 - 7125
  • [6] Analysis and Protection Scheme of Station Internal AC Grounding Faults in a Bipolar MMC-HVDC System
    Xue, Shimin
    Gu, Cheng
    Liu, Baibing
    Fan, Boyang
    IEEE ACCESS, 2020, 8 : 26536 - 26548
  • [7] An Approximated Analytical Model for Pole-to-Ground Faults in Symmetrical Monopole MMC-HVDC Systems
    Lacerda, Vinicius Albernaz
    Monaro, Renato Machado
    Campos-Gaona, David
    Pena-Alzola, Rafael
    Coury, Denis Vinicius
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2021, 9 (06) : 7009 - 7017
  • [8] Equivalent Model of MMC-HVDC for AC Protection Setting with Access Bus Fault
    Liu R.
    Tu Q.
    Li Y.
    Luo Q.
    Lei Q.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (18): : 145 - 153
  • [9] Operating state evaluation for MMC-HVDC system under AC transient faults
    Chen, Jikai
    Dou, Yanhui
    Li, Guoqing
    Xin, Yechun
    Wang, Zhenhao
    Yi Qi Yi Biao Xue Bao/Chinese Journal of Scientific Instrument, 2017, 38 (12): : 3129 - 3136
  • [10] Research on a current calculation method and characteristics of pole-to-ground faults in true bipolar MMC-HVDC grids considering line coupling
    Li, Botong
    Wang, Wenxin
    Li, Bin
    Liu, Yichao
    Wen, Weijie
    Chen, Xiaolong
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 192