Analysis of Very Fast Transient Overvoltages (VFTO) from Onsite Measurements on 800 kV GIS

被引:35
|
作者
Li, Yunge [1 ]
Shang, Yong [2 ]
Zhang, Lin [2 ]
Shi, Rong [2 ]
Shi, Wei [3 ]
机构
[1] Shaanxi Elect Power Res Inst, Xian 710054, Shaanxi, Peoples R China
[2] Shaanxi Elect Power Corp, Xian 710048, Shaanxi, Peoples R China
[3] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Shaanxi, Peoples R China
关键词
Digital measurements; disconnector switching; EHV substations; gas insulated switchgear; switching transients; very fast transient overvoltages; IMPULSE WAVE-FORMS; GAS-INSULATED SWITCHGEARS; BREAKDOWN CHARACTERISTICS; SUPPRESSION; SIMULATION;
D O I
10.1109/TDEI.2012.6396970
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In IEC 60071-1 and 62271-102, there is neither standard voltage shape nor standard peak value for very fast transient overvoltages (VFTO). Previous work by other researchers had classified VFTO into two types. A new type was identified in this paper based on an onsite test on a commercially-operated 800 kV GIS. Disconnectors were opened/closed under real operation conditions. Characteristics of the new VFTO type were analyzed, including times of the arc restrikes between the contacts of the disconnectors, trapped charge, damping time constant, magnitude, rise rate, and oscillating frequency. The results of this paper are expected to be of help for the completion of standards on VFTO.
引用
收藏
页码:2102 / 2110
页数:9
相关论文
共 50 条
  • [1] Computation of Very Fast Transient Overvoltages (VFTO) in a 1000 kV Gas Insulated Substation
    Haseeb, M. A.
    Thomas, M. Joy
    [J]. 2017 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2017,
  • [2] Very fast transient overvoltages in GIS
    Zhang, WY
    Shi, BZ
    Qiu, YC
    [J]. POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2, 1998, : 212 - 214
  • [3] Measurement of very fast transient overvoltages in GIS
    Shi, Baozhuang
    Zhang, Wenyuan
    Qiu, Yuchang
    Wang, Yun
    Dai, Youfu
    [J]. Gaodianya Jishu/High Voltage Engineering, 24 (01): : 17 - 18
  • [4] Comparison and Analysis on Very Fast Transient Overvoltage Based on 550kV GIS and 800kV GIS
    Tian Chi
    Lin Xin
    Xu Jianyuan
    Geng Zhen-xin
    [J]. ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 288 - 291
  • [5] Application of Multiple Modelling Techniques for Analysis of Very Fast Transient Overvoltages in GIS
    James, J.
    Albano, M.
    Haddad, A.
    Guo, D.
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [6] Study on transformer protection from VFTO in 800 kV GIS
    Liu, Qing
    Zhang, Yu-Feng
    Shi, Wei
    [J]. Gaoya Dianqi/High Voltage Apparatus, 2007, 43 (02): : 122 - 124
  • [7] Analysis of Influential Factors in Determining Very Fast Transient Overvoltages of GIS Substations
    Babaei, Maziar
    Babaei, Mehdi
    Nourirad, Ghasem
    [J]. 2014 IEEE 8TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO), 2014, : 79 - 84
  • [8] ACCURATE MODELLING OF VERY FAST TRANSIENT OVERVOLTAGES IN A 245kV GIS AND RESEARCH ON PROTECTION MEASURES
    Rao, J. V. G. Rama
    Amarnath, J.
    Kamakshaiah, S.
    [J]. 2010 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTIC PHENOMENA, 2010,
  • [9] Study of the behavior of low voltage ZnO varistors against very fast transient overvoltages (VFTO)
    Rojo Ceballos, Clara
    Chejne, Farid
    Perez, Ernesto
    Osorio, Andres
    Correa, Alexander
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2023, 214
  • [10] CAPACITIVE VOLTAGE SENSOR FOR MEASURING VERY FAST TRANSIENT OVERVOLTAGES IN GIS
    YASHIMA, M
    FUJINAMI, H
    TAKUMA, T
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 1995, 115 (01) : 64 - 74