An Attempt to Investigate the Transformer Failure by using DGA and SFRA Analysis

被引:0
|
作者
Patil, Shubhangi S. [1 ]
Chaudhari, Sushil E. [1 ]
机构
[1] Crompton Greaves Ltd, High Voltage Prod Technol Ctr, Global R&D Ctr, Bombay, Maharashtra, India
关键词
Power transformer; Insulation Deterioration; Overheating; DGA; SFRA; Resonance shift and Failure Analysis;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A sudden increasing power demand leads to manufacture of large number of oil immersed power transformers and other electrical power equipments. Power transformers are the most vital equipment in power system. Any failure in transformer leads to malfunction of whole power system. Unfortunately, the failure rate of these transformers is very high in India, 25% per annum, which is not favorable as compared to international units of 1-2 %. Failures happen due to internal reasons or operational hazardless. Transformer insulation deteriorates as the function of temperature, moisture and time. The core and winding losses, stray losses in tank and metal support structures are the principle sources of heat which cause oil and winding temperature rise. There are multiple reasons for overheating such as improper cooling, excessive eddy currents, bad joints, blocked radiators, overloading, improper earthing and harmonic contents in power supply. This leads to accelerated aging of oil and cellulosic solid insulation, which generate the gases within transformer and further leads to permanent failure. To prevent such failures, effective analysis and diagnosis needs to be investigated. The type of gases generated and amount of gas concentrations in oil efficiently evaluated using Dissolved Gas analysis (DGA). Various other electrical diagnostic tests like winding resistance test, short circuit impedance, oil analysis and sweep frequency response analysis (SFRA) are also helpful for identification of abnormalities and probable fault area. SFRA technique is widely accepted and used for transformer mechanical condition assessment. Based on the type and concentration of gases generated in oil along with application of SFRA test on transformer can help to identify the abnormal areas prior to catastrophic failure. An attempt has made for the investigation on relation of DGA with SFRA response. Case studies are presented here for the transformers which have higher fault gas concentrations (DGA). Additional diagnostic tests and analysis, inspection and history data has found supportive in investigation.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] Condition Assessment of Power Transformer Bushing Using SFRA and DGA as Auxiliary Tools
    Mohseni, Bahar
    Hashemnia, Naser
    Islam, Syed
    2016 IEEE INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2016,
  • [2] Evaluating transformer condition using DGA oil analysis
    Ward, SA
    2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, : 463 - 468
  • [3] Location of Faults in Transformer Winding using SFRA
    Usha, K.
    Joseph, Jineeth
    Usa, S.
    2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, : 196 - 201
  • [4] Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)
    Gite, Priti
    Sindekar, A. S.
    2017 IEEE INTERNATIONAL CONFERENCE ON ELECTRICAL, INSTRUMENTATION AND COMMUNICATION ENGINEERING (ICEICE), 2017,
  • [5] Proposals for an improvement in transformer diagnosis using dissolved gas analysis (DGA)
    Optec Dai-Ichi Denko Co, Ltd, Tokyo, Japan
    IEEE Electr Insul Mag, 6 (15-21):
  • [6] Inter Disc Fault Location in Transformer Windings Using SFRA
    Usha, K.
    Usa, S.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) : 3567 - 3573
  • [7] PROPOSALS FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS USING DISSOLVED-GAS ANALYSIS (DGA)
    KAN, H
    MIYAMOTO, T
    IEEE ELECTRICAL INSULATION MAGAZINE, 1995, 11 (06) : 15 - 21
  • [8] Power Transformer Condition Assessment Using DGA and FRA
    Gonzales, J. C.
    Mombello, E. E.
    IEEE LATIN AMERICA TRANSACTIONS, 2016, 14 (11) : 4527 - 4533
  • [9] Improvement in Transformer Diagnosis by DGA using Fuzzy Logic
    Dhote, Nitin K.
    Helonde, J. B.
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2014, 9 (02) : 615 - 621
  • [10] Using cross-correlation coefficients to analyze transformer Sweep Frequency Response Analysis (SFRA) traces
    Kennedy, G. M.
    McGrail, A. J.
    Lapworth, J. A.
    2007 IEEE POWER ENGINEERING SOCIETY CONFERENCE AND EXPOSITION IN AFRICA, VOLS 1 AND 2, 2007, : 553 - +