Sensitive Equipment Failure Assessment Caused by Voltage Sags Using Interval Probability

被引:0
|
作者
Li, Hao [1 ]
Xiao, Xianyong [1 ]
Wang, Ying [1 ]
机构
[1] Sichuan Univ, Coll Elect Engn & Informat, Chengdu 610065, Peoples R China
关键词
Voltage Sags; Interval Probability; Maximum Entropy; Failure Probability; INTERRUPTIONS;
D O I
10.4028/www.scientific.net/AMR.605-607.806
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
It is difficult to assess the impact of voltage sags on sensitive equipment because of the complex uncertainties involved in voltage tolerance capability. Determining the distribution regularity of voltage tolerance capability is an important step in voltage sag sensitivity assessment. Computers' voltage tolerance capability are obtained through laboratory tests. The point-value distribution function of voltage tolerance capability is calculated by Maximum Entropy Principle and then the interval probability distribution function is derived based on confidence interval, so as to derive an interval probability of equipment failure probability. The proposed model is finally verified in the IEEE-30 bus system. The results are compared with that of stochastic estimation method, showing that the proposed method can reflect actual conditions better and obtain accurate result.
引用
收藏
页码:806 / 810
页数:5
相关论文
共 50 条
  • [1] Uncertainty Assessment of Sensitive Equipment Failure Probability Caused by Voltage Sags
    Yuan Zhijian
    Wang Hong
    Huang Yong
    Chen Wu
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [2] Interval failure probability assessment of sensitive load due to voltage sags
    Li, Zheng-Guang
    Gui, Xian-Ming
    Xiao, Xian-Yong
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (17): : 37 - 42
  • [3] Maximum Hybrid Entropy Assessment of Equipment Failure Probability Caused by Voltage Sags
    Zeng, Zhuolin
    Xiao, Xianyong
    Wang, Ying
    SUSTAINABLE DEVELOPMENT OF NATURAL RESOURCES, PTS 1-3, 2013, 616-618 : 574 - 579
  • [4] Maximum Hybrid Entropy Interval Probability Assessment of Equipment Failure Due to Voltage Sags
    Zeng Zhuo-Lin
    Xu Pei-Dong
    Ma Jing
    Xiao Xian-Yong
    Wang Ying
    Xu mei
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [5] Failure Probability Analysis of Sensitive Equipment Due to Voltage Sags Using Fuzzy-Random Assessment Method
    Xiao, Xian-Yong
    Ma, Chao
    Yang, Hong-Geng
    Chen, Wu
    Li, Hua-Qiang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) : 2970 - 2975
  • [6] Nonadditive Measure and Assessment Method of the Failure Possibility of Sensitive Equipment Due to Voltage Sags
    Li Yuan-Bo
    Li Wan
    Xiao Xian-Yong
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [7] Fault Sample Augmentation and Maximum Entropy Modeling for Probability Assessment of Sensitive Equipment Due to Voltage Sags
    Zheng M.
    Xiao X.
    Chen Y.
    Zheng Z.
    Wang Y.
    Gongcheng Kexue Yu Jishu/Advanced Engineering Sciences, 2024, 56 (02): : 68 - 79
  • [8] Study on Failure Frequency of Sensitive Equipment Caused by Voltage
    Cai, Wei
    He, Huimin
    Wang, Jianwei
    Suo, Juan
    Wu, Chuanlai
    POWER AND ENERGY SYSTEMS III, 2014, 492 : 195 - +
  • [9] Estimation of sensitive equipment disruptions due to voltage sags
    Lu, Chan-Nan
    Shen, Cheng-Chieh
    IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) : 1132 - 1137
  • [10] Estimation of sensitive equipment disruptions due to voltage sags
    Lu, Chan-Nan
    Shen, Cheng-Chieh
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 268 - 268