Refrigeration inventory based on CO2 emissions and exergetic performance for supermarket applications

被引:12
|
作者
Sogut, M. Z. [1 ]
Yalcin, E. [2 ]
Karakoc, H. [3 ]
机构
[1] Mil Acad, Tech & Comp Applicat Ctr, Ankara, Turkey
[2] Balikesir Univ, Fac Engn, Dept Mech Engn, Balikesir, Turkey
[3] Anadolu Univ, Sch Civil Aviat, Eskisehir, Turkey
关键词
Cooling systems; Refrigerants; COP; Exergy efficiency; Carbon dioxide emissions;
D O I
10.1016/j.enbuild.2012.04.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, first energy and exergy analysis for supermarket cooling applications having high refrigerant capacity are examined and next, based on these analyses and different gases used. CO2 emission effect caused by these systems have been evaluated according to two parameters. The study investigated thermodynamic and environmental effects at medium (10/0 degrees C) and low (-35/0 degrees C) evaporation temperatures by reference to a supermarket cooling application with a 4000-5000 m(2) store size. The study revealed that, refrigerant R-404A is proved to have far worse results than R-22, and proposed alternatives for R-404A, the R-407C and R-152a refrigerants have better average exergetic efficiency ratio. 8.73% and 13.58% respectively. In addition, according to the TEWI and ICF parameters, emission potentials of these refrigerants were found to be lower being average 27.49% and 25.47 and 34.1% and 51.19 respectively. The study concluded with assessment of how the exegry and environmental effect analyses impact system preference. (C) 2012 Elsevier B.V. All rights reserved.
引用
收藏
页码:84 / 92
页数:9
相关论文
共 50 条
  • [1] Using CO2 in supermarket refrigeration
    Sawalha, S
    ASHRAE JOURNAL, 2005, 47 (08) : 26 - 30
  • [2] Transcritical CO2 Supermarket Refrigeration
    Weber, Collin
    Horning, Harrison
    ASHRAE JOURNAL, 2015, 57 (10) : 26 - +
  • [3] PERFORMANCE ANALYSIS OF TRANSCRITICAL CO2 REFRIGERATION SYSTEM FOR SUPERMARKET APPLICATION
    Santosa, IDewa M. C.
    Sudirman
    Ing, Suta Waisnawa
    INTERNATIONAL JOURNAL OF GEOMATE, 2018, 15 (50): : 70 - 75
  • [4] Experimental investigation of a new CO2 refrigeration system arrangement for supermarket applications
    Paez, Ana
    Ballot-Miguet, Benedicte
    Michel, Benoit
    Tobaly, Pascal
    Revellin, Remi
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 162 : 245 - 256
  • [5] Energy analysis and performance comparison of transcritical CO2 supermarket refrigeration cycles
    Caliskan, Oguz
    Ersoy, H. Kursad
    JOURNAL OF SUPERCRITICAL FLUIDS, 2022, 189
  • [6] Exergetic performance assessment of solar driven combined CO2 power and refrigeration system
    Kizilkan, Onder
    INTERNATIONAL JOURNAL OF EXERGY, 2018, 27 (02) : 147 - 164
  • [7] Thermodynamic performance evaluation of the CO2 parallel compression supermarket refrigeration system with a subcooler
    Wang Zheng
    Zhao Hongxia
    Wang Xinli
    Han Jitian
    Lai Yanhua
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2020, 44 (08) : 6709 - 6724
  • [8] Performance assessment of CO2 supermarket refrigeration system in different climate zones of China
    Sun, Zhili
    Li, Jiamei
    Liang, Youcai
    Sun, Huan
    Liu, Shengchun
    Yang, Lijie
    Wang, Caiyun
    Dai, Baomin
    ENERGY CONVERSION AND MANAGEMENT, 2020, 208 (208)
  • [9] Performance optimization of a transcritical CO2 supermarket refrigeration system equipped with an ice tank
    Khanlogh, Mehran
    Izadi-Zamanabadi, Roozbeh
    Ramezani, Hossein
    Gullo, Paride
    26TH IIR INTERNATIONAL CONGRESS OF REFRIGERATION, VOL 3, 2023, : 340 - 351
  • [10] Annual performance of a supermarket refrigeration system using different configurations with CO2 refrigerant
    Mitsopoulos, Georgios
    Syngounas, Evangelos
    Tsimpoukis, Dimitrios
    Bellos, Evangelos
    Tzivanidis, Christos
    Anagnostatos, Stavros
    ENERGY CONVERSION AND MANAGEMENT-X, 2019, 1