A Study of the Propagation Behavior of Partial Discharge Pulses in the High-Voltage Winding of Hydro Generators

被引:0
|
作者
Oettl, Fabian [1 ]
Engelen, Christoph [1 ]
Binder, Erich
Kessler, Thomas [2 ]
机构
[1] OMICRON Elect GmbH, Engn Serv Primary Testing, Klaus, Austria
[2] Vorarlberger Illwerke AG, Operat Management, Vandans, Austria
关键词
stator winding; propagation behavior of partial discharges; measurement of apparent charge; analysis of PD pulses in time and frequency domains; frequency-selective measurement; frequency analysis of propagation paths of PD pulses;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Rotating electrical machines are one of the key assets for a reliable power supply. An unplanned outage of such components can lead to high follow-up costs. To prevent such unexpected occurrences the partial discharge (PD) diagnosis can be a reliable instrument for detecting failures in the insulation system before larger damages or a breakdown occurs. However, there have been repeated instances where the measurable apparent charge on the terminals does not correlate with damages found during inspection or repair. One important reason is the fact that PD-measuring systems with high bandwidth can only accurately measure PD-sources, which are located close to the terminals. The investigation described in this contribution intend to enhance the understanding of the propagation behavior of PD pulses in a stator winding. The goal of these tests is to contribute to a reliable identification of hidden PD symptoms in the stator winding insulation. To reach this goal, artificial PD impulses are injected at different parts of the winding of two different hydro generators. They are different in their physical size and electrical parameters. Measurements at the terminals of the stator windings are performed using both, the frequency selective PD system and a wide band digital oscilloscope. The result of the frequency selective measurement is a so-called "attenuation matrix", where the dependence of the location of injection and the corresponding measurement of the apparent charge recorded at the terminals is presented. The analysis of recorded signals at the terminals of the stator winding shows strong damping phenomena for the high frequency content of the pulse and demonstrates the benefits of the frequency selective measurement.
引用
收藏
页数:5
相关论文
共 50 条