Improved DC-link Voltage Control of PMSG WECS based on Feedback Linearization under Grid Faults

被引:0
|
作者
Zhou Sizhan [1 ,2 ]
Liu Jinjun [1 ,2 ]
Zhou Linyuan [1 ,2 ]
Zhu Yangque [1 ,2 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian 710049, Peoples R China
[2] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
关键词
WIND TURBINE; CONVERTER;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a DC-link voltage control method for the permanent magnet synchronous generator (PMSG) wind power system with a full-rated back-to-back converter, to improve the dc-link voltage dynamic response under normal operation and grid faults conditions. The dc-link voltage is controlled by the motor-side converter, while the grid-side converter is responsible for the maximum power point tracking. Considering the system nonlinear characteristic, a dc-link voltage controller is designed based on the feedback linearization theory. With this control scheme, the dc-link voltage responses much faster than other control structures. It can suppress the dc-link voltage fluctuation with the wind speed varying and prevent the voltage from rising too high under grid faults. The validity of the control algorithm has been verified by simulation with Matlab/Simulink, and the results show a better dc-link dynamic response with the proposed control scheme.
引用
收藏
页码:2895 / 2899
页数:5
相关论文
共 50 条
  • [1] Nonlinear Control Strategy for DC-Link Voltage Control in a DFIG of WECS During 3φ Grid Faults
    Shanmugam, Ramanathan
    Sakthivel, Dinesh Kumar
    Ramaiah, Ananda Natarajan
    Ramalingam, Sundaramurthy
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2024, 71 (10) : 1 - 8
  • [2] An improved fuzzy logic based DC-link voltage control strategy for smoothing output power of the PMSG-WECS
    Zhu, Ying
    Ma, Zhengzhou
    Wang, Zhicong
    [J]. ENERGY REPORTS, 2022, 8 : 8413 - 8425
  • [3] Robust Backstepping Control Strategy of Limiting DC-link Voltage Fluctuation for DFIG-based WECS Under Harmonically Distorted Grid Voltage
    Kim, Hyoungwoo
    Choi, Joon Young
    [J]. 2015 15TH INTERNATIONAL CONFERENCE ON CONTROL, AUTOMATION AND SYSTEMS (ICCAS), 2015, : 730 - 734
  • [4] A Method to Reduce DC-link Overvoltage of PMSG Based WECS during LVRT
    Dey, Papan
    Datta, Manoj
    Fernando, Nuwantha
    Senjyu, Tomonohu
    [J]. PROCEEDINGS OF THE 2016 IEEE REGION 10 CONFERENCE (TENCON), 2016, : 1894 - 1899
  • [5] Active Damping for PMSG-Based WECS With DC-Link Current Estimation
    Geng, Hua
    Xu, Dewei
    Wu, Bin
    Yang, Geng
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (04) : 1110 - 1119
  • [6] An Improved DC-Link Voltage Control Strategy for Grid Connected Converters
    Merai, Meriem
    Naouar, Mohamed Wissem
    Slama-Belkhodja, Ilhem
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2018, 33 (04) : 3575 - 3582
  • [7] Enhanced DC-link voltage control of PMSG-based wind turbine generators by machine-side converter during asymmetrical grid faults
    Wang, Zhihao
    Gao, Xuesong
    Liu, Lu
    Ren, Ziyu
    Zhang, Desheng
    Zhu, Guofang
    Jia, Chunjiang
    Terzija, Vladimir
    Ding, Lei
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 155
  • [8] LVRT Capability and Improved Control Scheme of PMSG-based WECS during Asymmetrical Grid Faults
    Guo, Yunlu
    Geng, Hua
    Yang, Geng
    [J]. 39TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2013), 2013, : 5294 - 5299
  • [9] Fuzzy-based Coordinated Control to Reduce DC-link Overvoltage of a PMSG based Wind Energy Systems during Grid Faults
    Dey, Papan
    Datta, Manoj
    Fernando, Nuwantha
    Senjyu, Tomonobu
    [J]. 2018 5TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER AND ENERGY CONVERSION SYSTEMS (EPECS), 2018,
  • [10] Impact of DC-Link Voltage Control on Torsional Vibrations in Grid-Forming PMSG Wind Turbines
    Liu, Shiyi
    Wu, Heng
    Bosma, Theo
    Wang, Xiongfei
    [J]. IEEE Transactions on Energy Conversion, 2024, 39 (04) : 2631 - 2642