Thermal Sizing and Electric Shock Calculations for Equipment Grounding Conductors

被引:9
|
作者
Liu, Haijun [1 ]
Mitolo, Massimo [1 ]
Shokooh, Farrokh [1 ]
机构
[1] Operat Technol Inc, Irvine, CA 92618 USA
关键词
Electric shock; equipment grounding conductors (EGCs); grounding; protective conductors (PEs); residual current devices (RCDs); safety; thermal sizing; SYSTEMS;
D O I
10.1109/TIA.2013.2258133
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper presents the thermal sizing procedure of equipment grounding (protective) conductors and the electric shock calculations as per the standard 60364 of the International Electrotechnical Committee (IEC) that is used worldwide. The application of IEC standards in the design of low-voltage systems (i.e., not exceeding 1 kV) governed by the National Electrical Code (NEC) and the American National Standards Institute (ANSI), which are adopted in the U. S., is discussed and proposed in this paper. The authors propose an interpretation of the NEC installations in light of the earthing definitions included in the IEC realm. On this premises, IEC sizing criteria are applied to typical North American installations to prove their general applicability and their legitimacy to NEC/ANSI-based electrical systems. Examples are also presented for both thermal sizing and electric shock calculation of equipment grounding conductors.
引用
收藏
页码:1720 / 1725
页数:6
相关论文
共 50 条
  • [1] Thermal Sizing and Electric Shock Calculations for Equipment Grounding Conductors
    Liu, Haijun
    Shokooh, Farrokh
    Mitolo, Massimo
    [J]. 2012 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING (IAS), 2012,
  • [2] Sizing equipment grounding conductors based on thermal damage curves
    Hughes, CD
    Strycula, EC
    [J]. IEEE INDUSTRY APPLICATIONS MAGAZINE, 2000, 6 (03) : 42 - 44
  • [3] Sizing of equipment grounding conductors based on thermal damage curves.
    Hughes, CD
    Strycula, EC
    [J]. 1998 IEEE INDUSTRIAL & COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE - CONFERENCE RECORD, 1998, : 140 - 142
  • [4] SIZING GROUNDING-ELECTRODE CONDUCTORS
    STALLCUP, JG
    [J]. EC&M-ELECTRICAL CONSTRUCTION AND MAINTENANCE, 1985, 84 (05): : 120 - 120
  • [5] EQUIPMENT GROUNDING CONDUCTORS AND BONDING A VITAL LINK IN ELECTRICAL SYSTEM PROTECTION
    OCKULY, GJ
    [J]. CONFERENCE RECORD OF THE 1989 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, PTS 1-2, 1989, : 1651 - 1655
  • [6] Thermal agitation of electric charge in conductors
    Nyquist, H
    [J]. PHYSICAL REVIEW, 1928, 32 (01): : 110 - 113
  • [7] ELECTRIC-SHOCK HAZARDS FOR OPERATORS OF ECT EQUIPMENT
    FISHER, J
    RAILTON, R
    [J]. BRITISH JOURNAL OF PSYCHIATRY, 1983, 142 (JAN) : 105 - 105
  • [8] ELECTRIC-SHOCK TREATMENT WITH NEW AC EQUIPMENT
    ASRICAN, E
    [J]. DISEASES OF THE NERVOUS SYSTEM, 1956, 17 (07): : 232 - 233
  • [9] ARE YOU PROTECTING AGAINST ELECTRIC SHOCK OR EQUIPMENT FAILURE?
    Gilbert, David
    [J]. Vector (Electrical Engineering), 1984, : 6 - 9
  • [10] Analysis of the thermal field of electric power equipment
    Medved, Dusan
    Conka, Zsolt
    Kolcun, Michal
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE AND WORKSHOP IN OBUDA ON ELECTRICAL AND POWER ENGINEERING (CANDO-EPE), 2018, : 173 - 177