Fouling mitigation in a heat exchanger: High cycles of concentration for a cooling-tower application

被引:7
|
作者
Cho, YI
Kim, WT
Cho, D
机构
[1] Drexel Univ, Dept Mech Engn & Mech, Philadelphia, PA 19104 USA
[2] PWT Ctr, Phoenixville, PA USA
关键词
fouling mitigation; physical water treatment; cooling tower water; high cycle of concentration;
D O I
10.1080/08916150500479372
中图分类号
O414.1 [热力学];
学科分类号
摘要
The purpose of the present study is to investigate the effect of a physical water treatment (PWT) technology on fouling mitigation in a simulated cooling tower operating at high cycles of concentration. Hard water was produced by evaporating pure water in a circulating open cooling tower, where dissolved calcium carbonate ions became concentrated with time. Heat transfer tests were conducted in a rectangular channel by varying the cycle of concentration (COC) from 5 to 10, and fouling resistances were measured over 270 hrs for each case with and without the PWT treatment. Another test was conducted with no blowdown case with and without the PWT treatment. The fouling resistance at 5 cycles with the PWT treatment was about 70% less than that in the case without the PWT treatment at the end of 270-hr tests. Even at 10 cycles, the PWT treatment reduced the fouling resistance by 60% from the value for the no treatment case. Thus, one can conclude that the PWT technology can help circulating cooling-tower water at relatively high COC for significant freshwater conservation, while keeping fouling resistances below industry standards.
引用
收藏
页码:113 / 128
页数:16
相关论文
共 50 条
  • [1] Effect of electronic anti-fouling treatment on fouling mitigation with circulating cooling-tower water
    Kim, WT
    Cho, YI
    Bai, C
    [J]. INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2001, 28 (05) : 671 - 680
  • [2] DRY COOLING-TOWER - CHANGE OF WATER-FLOW IN CLOSED COOLING CYCLES INCLUDING A DRY COOLING-TOWER
    BUXMANN, J
    HOFFMANN, T
    [J]. BRENNSTOFF-WARME-KRAFT, 1985, 37 (06): : 259 - 262
  • [3] Mitigation of heat exchanger fouling
    Bott, TR
    [J]. Advances in Heat Transfer Engineering, Proceedings, 2003, : 15 - 27
  • [4] COOLING WATER TREATMENT IN MITIGATION OF HEAT EXCHANGER FOULING AND CORROSION.
    Yang, John Y.
    Soong, Tsu T.
    [J]. Industrial water engineering, 1984, 21 (03): : 9 - 17
  • [5] EFFECT OF SURFACE TEMPERATURE ON FOULING OF COOLING-TOWER WATER.
    Epstein, Norman
    [J]. Heat Transfer Engineering, 1987, 8 (01) : 60 - 62
  • [6] MANAGING WASTE HEAT WITH THE WATER COOLING-TOWER
    DICKEY, JB
    [J]. COMBUSTION, 1979, 50 (11): : 12 - 19
  • [7] Effect of Fouling Mitigation for Ceramic Ball in Cooling Water System of Heat Exchanger
    Sung, Sun-Kyung
    Suh, Sang-Ho
    [J]. TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2007, 31 (04) : 330 - 334
  • [8] Crossflow microsand filtration in cooling tower systems to control fouling in heat exchanger devices
    Ashok, Vaishali
    Absalan, Faezeh
    Silverwood, Alain
    Robert, Etienne
    Claveau-Mallet, Dominique
    Bedard, Emilie
    [J]. JOURNAL OF BUILDING ENGINEERING, 2024, 95
  • [9] APPLICATION OF PULSED SPARK DISCHARGE FOR MITIGATION OF MINERAL FOULING IN A HEAT EXCHANGER
    Yang, Yong
    Kim, Hyoungsup
    Jung, Jin M.
    Fridman, Alexander
    Cho, Young I.
    [J]. PROCEEDINGS OF THE ASME INTERNATIONAL HEAT TRANSFER CONFERENCE - 2010, VOL 4: HEAT TRANSFER MEASUREMENT TECHNIQUES, HEAT TRANSFER EQUIPMENT, THERMOELECTRICS, 2010, : 385 - 393
  • [10] Mitigation of heat exchanger fouling in the oil industry
    Al-Bagawi, JJ
    Said, SAM
    [J]. PROCEEDINGS OF AN INTERNATIONAL CONFERENCE ON MITIGATION OF HEAT EXCHANGER FOULING AND ITS ECONOMIC AND ENVIRONMENTAL IMPLICATIONS, 2001, : 193 - 197