Exergetic Evaluation of an Ethylene Refrigeration Cycle

被引:2
|
作者
Amaral, Francisco [1 ]
Santos, Alex [2 ]
Calixto, Ewerton [2 ]
Pessoa, Fernando [2 ]
Santana, Delano [3 ]
机构
[1] Braskem, Rua Eteno, BR-42816200 Camacari, BA, Brazil
[2] Univ Ctr SENAI CIMATEC, Computat Modeling Dept, BR-41650010 Salvador, BA, Brazil
[3] Univ Fed Bahia, Dept Chem Engn, BR-40210630 Salvador, BA, Brazil
关键词
exergy; refrigeration cycles; process monitoring; CENTRIFUGAL COMPRESSORS; ENERGY; SYSTEM; OPTIMIZATION;
D O I
10.3390/en13143753
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The production of light olefins by selective steam cracking is an energy-intensive process, and ethylene and propylene refrigeration cycles are key parts of it. The objective of this study was to identify opportunities for energy savings in an ethylene refrigeration cycle through an exergetic analysis. Two main causes of lower operational efficiency were identified: (1) Lower polytropic efficiency of the refrigerant compressor and (2) operating with the compressor mini-flow valve open to ensure reliability. The evaluation showed that the amount of irreversibilities generated by the cycle in operation is 22% higher than that predicted by the original design, which represents a 14% lower exergy efficiency. There is a potential savings of 0.20 MW in the cycle's energy consumption with the implementation of the following improvements: recover refrigerant compressor efficiency by performing maintenance on the equipment and optimize the flow distribution between the recycle valve, the level control valve, and the temperature control valve.
引用
收藏
页数:21
相关论文
共 50 条
  • [1] Performance evaluation of Ammonia Absorption Refrigeration cycle based on Exergetic Coefficient of Performance
    Hasabnis, Y. C.
    Bhagwat, S. S.
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2007, 4 (01) : 19 - 37
  • [2] Exergetic optimization of a refrigeration cycle for natural gas liquefaction
    Cipolato, Liza
    Lirani, Maria C. A.
    Costa, Thiago V.
    Fabrega, Francine M.
    d'Angelo, Jose V. H.
    [J]. 11TH INTERNATIONAL SYMPOSIUM ON PROCESS SYSTEMS ENGINEERING, PTS A AND B, 2012, 31 : 440 - 444
  • [3] Exergetic efficiency optimization for an irreversible Brayton refrigeration cycle
    Chen, CK
    Su, YF
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (03) : 303 - 310
  • [4] Exergetic analysis of the refrigeration system in ethylene and propylene production process
    Fabrega, F. M.
    Rossi, J. S.
    d'Angelo, J. V. H.
    [J]. ENERGY, 2010, 35 (03) : 1224 - 1231
  • [5] Exergetic optimisation of a multi-stage compression transcritical refrigeration cycle
    Rashidi, M. M.
    Parsa, A. Basiri
    Shamekhi, L.
    Nazari, F.
    Ali, M.
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2016, 20 (01) : 22 - 47
  • [6] Exergetic analysis of the vapour compression refrigeration cycle using ejector as an expander
    Yari, Mortaza
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2008, 5 (03) : 326 - 340
  • [7] Energetic and exergetic investigation on a solar powered integrated system of ejector refrigeration cycle and Kalina cycle
    Alazazmeh, Ayman J.
    Khaliq, Abdul
    Shivlal
    [J]. INTERNATIONAL JOURNAL OF EXERGY, 2022, 39 (04) : 361 - 376
  • [8] EXERGETIC ANALYSIS OF A REFRIGERATION SYSTEM
    Belman-Flores, J. M.
    Gallegos-Munoz, A.
    Riesco-Avila, J. M.
    Zaleta-Aguilar, A.
    Mendoza-Miranda, J. M.
    [J]. REVISTA MEXICANA DE INGENIERIA QUIMICA, 2014, 13 (03): : 957 - 968
  • [9] Advanced exergetic evaluation of refrigeration machines using different working fluids
    Morosuk, T.
    Tsatsaronis, G.
    [J]. ENERGY, 2009, 34 (12) : 2248 - 2258
  • [10] An exergetic analysis of membrane unit operations integrated in the ethylene production cycle
    Bernardo, P.
    Barbieri, G.
    Drioli, E.
    [J]. CHEMICAL ENGINEERING RESEARCH & DESIGN, 2006, 84 (A5): : 405 - 411