Optimal PMU placement for power system state estimation with random component outages

被引:47
|
作者
Tai, Xin [1 ]
Marelli, Damian [1 ]
Rohr, Eduardo [1 ]
Fu, Minyue [1 ]
机构
[1] Univ Newcastle, Sch Elect Engn & Comp Sci, Callaghan, NSW 2308, Australia
基金
奥地利科学基金会;
关键词
Optimal PMU placement; State estimation; MAP estimation; Kalman filter; OBSERVABILITY; FORMULATION;
D O I
10.1016/j.ijepes.2013.02.007
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Phasor measurement units (PMUs) provide globally synchronized measurements of voltage and current phasors in real-time and at a high sampling rate. Hence, they permit improving the state estimation performance in power systems. In this paper we propose a novel method for optimal PMU placement in a power system suffering from random component outages (RCOs). In the proposed method, for a given RCO model, the optimal PMU locations are chosen to minimize the state estimation error covariance. We consider both static and dynamic state estimation. To reduce the complexity, the search for the optimal PMU locations is constrained to the set of locations guaranteeing topological observability. We present numerical results showing the application and scalability of our method using the IEEE 9-bus, 14-bus, 39-bus and 118-bus systems. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:35 / 42
页数:8
相关论文
共 50 条
  • [1] Observability enhancement by optimal PMU placement considering random power system outages
    Aminifar F.
    Fotuhi-Firuzabad M.
    Shahidehpour M.
    Khodaei A.
    [J]. Energy Systems, 2011, 2 (1) : 45 - 65
  • [2] Optimal PMU Placement Evaluation for Power System Dynamic State Estimation
    Zhang, Jinghe
    Welch, Greg
    Bishop, Gary
    Huang, Zhenyu
    [J]. 2010 IEEE PES CONFERENCE ON INNOVATIVE SMART GRID TECHNOLOGIES EUROPE (ISGT EUROPE), 2010,
  • [3] Power System State Estimation Accuracy and Observability Evaluation with Optimal PMU Placement
    Almehizia, Abdullah. A.
    Alismail, Fahad. S.
    [J]. 2017 IEEE TEXAS POWER AND ENERGY CONFERENCE (TPEC), 2017,
  • [4] Heuristic Placement of PMU in Power System State Estimation
    Habiballah, I. O.
    Sahito, M.
    [J]. 2017 9TH IEEE-GCC CONFERENCE AND EXHIBITION (GCCCE), 2018, : 500 - 504
  • [5] Optimum PMU Placement for Power System State Estimation
    Akingeneye, Israel
    Wu, Jingxian
    Yang, Jing
    [J]. 2017 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2017,
  • [6] Optimal PMU Placement for State Estimation Robustness
    Gol, Murat
    Abur, Ali
    [J]. 2014 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE EUROPE (ISGT EUROPE), 2014,
  • [7] Optimal PMU Placement for Power System Dynamic State Estimation by Using Empirical Observability Gramian
    Qi, Junjian
    Sun, Kai
    Kang, Wei
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (04) : 2041 - 2054
  • [8] Optimal PMU Placement for Power System Dynamic State Estimation by Using Empirical Observability Gramian
    Qi, Junjian
    Sun, Kai
    Kang, Wei
    [J]. 2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [9] Optimal Probabilistic PMU Placement in Electric Distribution System State Estimation
    Arefi, Ali
    Haghifam, Mahmood-Reza
    Fathi, Seyed-Hamid
    Behi, Behnaz
    Razavi, S. Ehsan
    Jennings, Philip
    [J]. 2019 IEEE 10TH INTERNATIONAL WORKSHOP ON APPLIED MEASUREMENTS FOR POWER SYSTEMS (AMPS 2019), 2019,
  • [10] Optimal PMU Placement for Identification of Multiple Power Line Outages in Smart Grids
    Wu, Jie
    Xiong, Jinjun
    Shil, Prasenjit
    Shi, Yiyu
    [J]. 2014 IEEE 57TH INTERNATIONAL MIDWEST SYMPOSIUM ON CIRCUITS AND SYSTEMS (MWSCAS), 2014, : 354 - 357