Temperature Segment Compensation Method of Dissipation Factor for Insulation Diagnosis in Converter Transformer Bushing

被引:6
|
作者
Dai, Quanmin [1 ]
Liu, Yanxia [1 ]
Yu, Xin [1 ]
Zhang, Yinoon [1 ]
Chen, Huidong [1 ]
Huang, Zhiming [2 ]
机构
[1] Beijing Union Univ, Coll Urban Rail Transit & Logist, Beijing 100101, Peoples R China
[2] CSG Elect Power Res Inst Co Ltd, Guangzhou 510080, Peoples R China
来源
IEEE ACCESS | 2022年 / 10卷
关键词
Converter transformer; resin-impregnated paper insulation; frequency domain spectroscopy (FDS); temperature; dissipation factor; fault diagnosis; DIELECTRIC RESPONSE; MULTILAYER; DESIGN;
D O I
10.1109/ACCESS.2022.3144077
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Temperature compensation occupies a significant function in the insulation condition evaluation of converter transformer bushings based on the Frequency Domain Spectroscopy (FDS), which could influence the accuracy of its insulation diagnosis. In order to accurately obtain the variation law of FDS at different temperature, a Resin Impregnated Paper (RIP) insulation bushing for converter transformer was designed by the equivalence of maximum electric field, coaxial cylinder structure and RIP materials. The increment law of dielectric parameters both dissipation factor and capacitance at wideband frequency (1mHz similar to 10kHz) was measured for a quality RIP insulation samples at the temperature from 30 degrees C to 100 degrees C. 1) Under the uniform temperature, it was found that the value of dissipation factor was rising with the frequency from 10 Hz to 0.001Hz, while the tendency was reversed at the frequency from 100Hz to10kHz. 2) The minimum value of tan delta from 0.001Hz to 10kHz could be driven to higher frequency moving (10Hz to 10kHz) by the action of temperature rising 30 degrees C to 100 degrees C.3) The effect of temperature on the lower frequency 0.001Hz similar to 1Hz tan delta of RIP insulation closely conformed to the index law of Arrhenius equation, while it was in accordance with the linear decrease at higher frequency 1kHz similar to 10kHz. The effect of temperature on dissipation factor could be eliminated by curve segment shifting based the experiment equation, which it at 0.001Hz dissipation factor could be eliminated by curve shifting based the index equation originated Arrhenius equation. The method is beneficial to eliminate the influence of temperature on the dielectric spectroscopy test results, and then to eliminate the influence of temperature on the dielectric spectroscopy diagnosis of RIP bushings.
引用
收藏
页码:10310 / 10316
页数:7
相关论文
共 50 条
  • [1] Study on Electrical Insulation Structure Optimization Design of Converter Transformer Bushing
    Zhang Shiling
    Ji Yongliang
    [J]. 2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1292 - 1299
  • [2] Insulation structure design of valve side bushing of ± 400 kV converter transformer
    Zhang S.
    Peng Z.
    Ning X.
    Tian H.
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (06): : 199 - 206
  • [3] Design and Analysis of Insulation Structure of ±800 kV Valve Side Converter Transformer Bushing
    Zhang S.
    Peng Z.
    [J]. Gaodianya Jishu/High Voltage Engineering, 2019, 45 (07): : 2257 - 2266
  • [4] Research Status of Oil-Paper Insulation for Valve Side Bushing of Converter Transformer
    Du B.
    Zhu W.
    Li J.
    Jiang J.
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (06): : 1300 - 1309
  • [5] Temperature-dependent electric field distribution in ±800 kV valve-side bushing insulation for a converter transformer
    Du, Boxue
    Sun, Hanlei
    Jiang, Jinpeng
    Kong, Xiaoxiao
    Yang, Wei
    [J]. HIGH VOLTAGE, 2021, 6 (01) : 106 - 115
  • [6] Research of on-line monitoring method for insulation condition of power transformer bushing
    Xia Jiuyun
    Qian Zheng
    Yu Hao
    Yao Junda
    [J]. SEVENTH INTERNATIONAL SYMPOSIUM ON PRECISION MECHANICAL MEASUREMENTS, 2016, 9903
  • [7] Design and Optimization Analysis of Water Cooling Heat Dissipation for the Valve-side Bushing of Converter Transformer
    Shi S.
    Liu S.
    Xie G.
    Wang Q.
    Wang Q.
    Liu P.
    Peng Z.
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (12): : 4861 - 4870
  • [8] Partial Discharge Detection and Diagnosis of Transformer Bushing Based on UHF Method
    Jiang, Jun
    Chen, Judong
    Li, Jiansheng
    Yang, Xiaoping
    Bie, Yifan
    Ranjan, Prem
    Zhang, Chaohai
    Schwarz, Harald
    [J]. IEEE SENSORS JOURNAL, 2021, 21 (15) : 16798 - 16806
  • [9] Study on the Transformer Solid Insulation Aging Diagnosis Method
    Mu Xueyun
    Yang Qiping
    Wang Jun
    Xu Danfeng
    [J]. 2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [10] Effects of Converter Harmonic Voltages on Transformer Insulation Ageing and an Online Monitoring Method for Interlayer Insulation
    Lu, Geye
    Zheng, Dayong
    Zhang, Qinghao
    Zhang, Pinjia
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (03) : 3504 - 3514