Experimental study on the testing environment improvement of fire smoke detectors

被引:0
|
作者
Chen Nan [1 ]
Ma Xianmeng [1 ]
Dong Wenhui [2 ]
机构
[1] Chinese People Armed Police Force Acad, Fire Engn Dept, Langfang 065000, Hebei, Peoples R China
[2] Shenyang Fire Res Inst, Fire Alarm Lab, Shenyang 117000, Liaoning, Peoples R China
关键词
fire smoke detector; aerosol generator; aerosol flow; testing tube; particle size distribution;
D O I
10.1016/j.proeng.2012.08.211
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
To simulate the test smoke for fire smoke detectors, the bypass setting of aerosol generator is currently adjusted to the particle size of 0.75 mu m according to the standard of EN 54-7 of China. It leads to the single test environment of fire smoke detectors. In this paper, the improvement of aerosol generator is presented. It makes the aerosol flow which has different particle size characteristics can be generated by aerosol generator and be installed several bypass flows according to the principle of aerosol generator. By the way, the particle size distribution and particle size characteristics of aerosol flow can be obtained after measuring the quality of aerosol flow which is collected under different bypass flows by Berner Impactor. So the different type of test smoke for fire smoke detectors can be obtained by aerosol generator. And then, the distribution characteristics of aerosol flow can be obtained in testing tubes (EN54-5/7c) of fire smoke detectors. Finally, the improved test environment of fire smoke detectors has realized the diversification of test environment. And the reliability of the test results has improved through this study. (C) 2012 The Authors. Published by Elsevier Ltd. Selection and/or peer-review under responsibility of the Beijing Institute of Technology.
引用
收藏
页码:610 / 616
页数:7
相关论文
共 50 条
  • [1] Experimental study on interference source of smoke fire detector in religious building environment
    Zhong, Chen
    Li, Xiaobai
    Liu, Xiaopeng
    Ding, Hongjun
    2020 6TH INTERNATIONAL CONFERENCE ON ENERGY, ENVIRONMENT AND MATERIALS SCIENCE, 2020, 585
  • [2] An experimental study of smoke flow in tunnel fire
    Tongji University, Shanghai 200092, China
    不详
    Tumu Gongcheng Xuebao, 2006, 4 (95-99):
  • [3] Experimental study on the sensitivity and nuisance immunity of smoke detectors
    Xie, Qiyuan
    Yuan, Hongyong
    Su, Guofeng
    Zhang, Yongming
    2002, Baywood Publishing Co. Inc. (11): : 323 - 334
  • [4] Experimental study on cabin fire smoke controlling with mechanical smoke exhaust
    You, Yu-Hang
    Li, Yuan-Zhou
    Wang, Hao-Bo
    Huo, Ran
    Ranshao Kexue Yu Jishu/Journal of Combustion Science and Technology, 2007, 13 (03): : 259 - 264
  • [5] Environment - No smoke without fire
    不详
    CHEMISTRY & INDUSTRY, 2005, (24) : 4 - 4
  • [6] TESTING THE SMOKE AND FIRE HAZARD
    FLISI, U
    POLYMER DEGRADATION AND STABILITY, 1990, 30 (01) : 153 - 168
  • [7] Experimental study on smoke characteristics of bifurcated tunnel fire
    Chen, Longfei
    Mao, Pengfei
    Zhang, Yuchun
    Xing, Shaoshuai
    Li, Tao
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2020, 98
  • [8] Ventilation improvement in fire smoke control
    Santarpia, L
    Gugliermetti, F
    Zori, G
    Environmental Health Risk III, 2005, 9 : 241 - 250
  • [9] Testing of fire dampers and motorized fire/smoke dampers
    Mohammed, Tony
    TAB Journal, 2004, (SPRING): : 5 - 6
  • [10] Investigation of the performance and improvement of optical smoke detectors
    To, Hingman
    Fong, Naikong
    9TH ASIA-OCEANIA SYMPOSIUM ON FIRE SCIENCE AND TECHNOLOGY, 2013, 62 : 985 - 993