Impact of Arc Flash Hazards on Medium-Voltage Switchgear

被引:8
|
作者
Shah, Kanu R. [1 ]
Cinsavich, Alan L. [1 ]
De Silva, Priyan [1 ]
机构
[1] Shah & Associates Inc, Gaithersburg, MD 20877 USA
关键词
Arc flash hazard analysis; flash protection; hazard/risk category (HRC); incident energy level; personal protective equipment (PPE); protective devices;
D O I
10.1109/TIA.2008.2006299
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper discusses the arc flash ramifications associated with the design and selection of medium-voltage switchgear. Three case studies are presented to demonstrate the impact of performing arc flash hazard analysis on the proposed and/or existing medium-voltage installation at the design stage. This paper proposes the following: 1) changes in the National Electrical Code, Article 110.16, to provide mandatory requirements for a) performing arc flash analysis at the design stage and b) placement of warning labels on switchgear to warn qualified persons of potential are flash hazards and 2) a need to promulgate regulations requiring a utility company to notify its customers of changes in a) the available fault duty at the point of common coupling with a customer's facility and b) utility upstream protective device settings.
引用
收藏
页码:1859 / 1863
页数:5
相关论文
共 50 条
  • [1] Impact of Arc Flash Hazards on Medium Voltage Switchgear
    Shah, K. R.
    Cinsavich, A.
    De Silva, P.
    CONFERENCE RECORD OF THE 2007 IEEE INDUSTRY APPLICATIONS CONFERENCE FORTY-SECOND IAS ANNUAL MEETING, VOLS. 1-5, 2007, : 2128 - 2132
  • [2] MANAGING ARC FLASH Collaborative solutions in medium-voltage switchgear
    Krause, Kenneth
    Burns, David
    Hutchinson, Scott
    Arvola, Juha
    IEEE INDUSTRY APPLICATIONS MAGAZINE, 2014, 20 (01) : 70 - 78
  • [3] Medium-Voltage Arc Flash in Switchgear and Live-Front Transformers
    Eblen, Marcia L.
    Short, Tom A.
    Lee, Wei-Jen
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2016, 52 (06) : 5280 - 5288
  • [4] Medium-Voltage Arc Flash in Switchgear and Live-Front Transformers
    Eblen, M. L.
    Short, T. A.
    Lee, W. -J.
    2016 IEEE IAS ELECTRICAL SAFETY WORKSHOP (ESW), 2016, : 100 - 109
  • [5] How to mitigate arc flash hazards in medium-voltage electrical systems
    Karki, Bibek
    Plant Engineering, 2023, 77 (06) : 20 - 25
  • [6] Sulphur hexafluoride in modern medium-voltage switchgear: Advantages, hazards and environmental impact
    Boskovic, Aleksandar
    Sremacki, Maja
    Vjestica, Suncica
    Cavic, Aleksandra
    Markovic, Nada
    Borovac, Branislav
    JOURNAL OF THE SERBIAN CHEMICAL SOCIETY, 2024, 89 (05) : 693 - 704
  • [7] MEDIUM-VOLTAGE SWITCHGEAR CUBICLES
    POOLE, D
    MUNZINGER, K
    BROWN BOVERI REVIEW, 1984, 71 (1-2): : 54 - 61
  • [8] Arc Flash Analysis Approaches for Medium-Voltage Distribution
    Short, T. A.
    2009 RURAL ELECTRIC POWER CONFERENCE, 2009,
  • [9] Safety benefits of arc-resistant metalclad medium-voltage switchgear
    Kalkstein, EW
    Doughty, RL
    Paullin, AE
    Jackson, JM
    Ryner, JL
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1995, 31 (06) : 1402 - 1411
  • [10] COLLABORATIVE ARC FLASH MANAGEMENT SOLUTIONS IN MEDIUM VOLTAGE SWITCHGEAR
    Krause, Kenneth N.
    Hutchinson, Scott A.
    Burns, David
    Arvola, Juha
    2012 RECORD OF CONFERENCE PAPERS INDUSTRY APPLICATIONS SOCIETY 59TH ANNUAL IEEE PETROLEUM AND CHEMICAL INDUSTRY TECHNICAL CONFERENCE (PCIC), 2012,