Surface charge accumulation on insulating plates in SF6 and the effect on DC and AC breakdown voltage of electrode arrangements

被引:0
|
作者
Winter, A [1 ]
Kindersberger, J [1 ]
机构
[1] Tech Univ Munich, Inst High Voltage Engn & Elect Power Transmiss, Munich, Germany
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Surface charge accumulation on insulating materials, which are located next to electrodes in electrical devices may lead to a change of the electrical field. In some cases the breakdown voltage of electrode arrangements could be exceeded. For the investigations an insulating plate made from PTFE was used. The test set-up allows to charge the specimen, to measure the charge density distribution and to verify the effect of charge on the breakdown voltage of an electrode arrangement. The test set-up was installed into a test vessel to study the effects under SF6. As a result the formation of a bipolar electrical charge double layer with charge densities of up to -18 nC/cm(2) on the upper surface of the specimen and up to + 15 nC/cm(2) on the opposite surface Was determined. The formation of a-bipolar electrical charge double layer could be simulated by numerical field calculation. Placing the charged specimen next to a rod-electrode arrangement causes a reduction of the AC and DC breakdown voltage up to more then 20%.
引用
收藏
页码:757 / 761
页数:5
相关论文
共 50 条
  • [1] Effect of Surface Charge Accumulation on Flashover Voltage of GIS Insulator in SF6 under DC and AC Voltages
    Qi, Bo
    Gao, Chunjia
    Li, Chengrong
    Zhao, Linjie
    Sun, Xiaqing
    2015 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2015, : 848 - 851
  • [2] EFFECT OF ELECTRODE SHAPE ON PARTICLE-INITIATED BREAKDOWN IN SF6 GAS UNDER DC VOLTAGE
    HARA, M
    LEE, HH
    EGASHIRA, T
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (01): : 156 - 170
  • [3] SF6 Breakdown in Cylindrical Field with dc Voltage.
    Ermel, Michael
    Elektrotechnische Zeitschrift Ausgabe A, 1975, 96 (11): : 505 - 510
  • [4] MECHANISM AND EFFECT OF DC CHARGE ACCUMULATION ON SF6 GAS INSULATED SPACERS
    FUJINAMI, H
    TAKUMA, T
    YASHIMA, M
    KAWAMOTO, T
    IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) : 1765 - 1772
  • [5] Characteristics of Charge Accumulation on Coated Electrode in SF6 Gas
    Kainaga, S.
    Miyamoto, T.
    Yoshimura, M.
    Tsurimoto, T.
    2012 15TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2012), 2012,
  • [6] Coating effect on AC and impulse breakdown stress of SF6
    Matsuo, T
    Hirotsu, K
    Hata, R
    1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, : 259 - 262
  • [7] Surface Charge Accumulation on Epoxy Insulator with Complex Surface Profile under DC Voltage in SF6/N2 Mixture
    Zhao, Huicun
    Gao, Yu
    Song, Xiaobo
    Zhang, Chi
    Yuan, Xiaochen
    Wang, Huan
    PROCEEDINGS OF THE 2020 3RD IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD 2020), 2020, : 471 - 474
  • [8] EFFECT OF SURFACE-ROUGHNESS ON BREAKDOWN IN SF6
    PEDERSEN, A
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (05): : 1749 - 1754
  • [9] The influence of surface charge on lightning impulse breakdown of spacers in SF6
    Tenbohlen, S
    Schröder, G
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2000, 7 (02) : 241 - 246
  • [10] The influence of surface roughness and coating on the impulse breakdown voltage in SF6
    Lederle, C
    Kindersberger, J
    2004 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2004, : 522 - 525