Improved Instantaneous Reactive Power (PQ) Theory Based Control of DVR for Compensating Extreme Sag and Swell

被引:13
|
作者
Al-Gahtani, Saad F. [1 ]
Salem, Elbarbary Z. M. [1 ,2 ]
Irshad, Shaik M. [1 ]
Azazi, Haitham Zaki [3 ]
机构
[1] King Khalid Univ, Coll Engn, Elect Engn Dept, Abha 61411, Saudi Arabia
[2] Kafrelsheikh Univ, Fac Engn, Dept Elect Engn, Kafrelsheikh 33516, Egypt
[3] Menoufia Univ, Fac Engn, Elect Engn Dept, Shibin Al Kawm 32511, Egypt
关键词
Power quality; Voltage control; Reactive power; Power system dynamics; Harmonic analysis; Transformers; Phase locked loops; Instantaneous reactive power (PQ) theory; dynamic voltage restorer (DVR); balanced and unbalanced load; voltage sag; voltage swell; load change; DYNAMIC VOLTAGE RESTORER; ENHANCEMENT; SYSTEM;
D O I
10.1109/ACCESS.2022.3185662
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In today's power system, power quality is a critical topic having several impacts on customers and utilities. In the current electric power system, the integration of renewable energy sources, smart grid technologies, and significant usage of power electronics equipment has generated a slew of issues. The sensitive equipment might be damaged by harmonics, voltage sag, and swell. These devices are vulnerable to Interference with other elements of the system resulting in input voltage changes. As a result, in the contemporary period, Power quality is becoming more important as the number of sensitive and costly electronic devices grows. To overcome the challenges of non-standard voltage, the Dynamic Voltage restorer (DVR) device has been extensively utilized to keep the load voltage stable. To have a dynamic and fast response of the DVR a modified instantaneous reactive power (PQ) theory is proposed to control DVR under extreme transient voltage circumstances. The proposed technique is based on the extraction of the positive sequence component of grid voltage and the negative sequence component of load current for generating a voltage reference signal. The power system network with the proposed PQ control scheme is investigated and assessed under various scenarios to compensate for severe balanced, unbalanced (voltage sags and swells), and load change. MATLAB/Simulink is used to verify the mathematical models of the conventional PQ and proposed PQ control system for DVR. The complete system is implemented experimentally using a dSPACE 1104 based laboratory system to validate the presented control scheme. The simulation and experimental results are correlated, demonstrating the efficacy of the suggested modified PQ control technique.
引用
收藏
页码:75186 / 75204
页数:19
相关论文
共 50 条
  • [1] An improved control for simultaneous sag/swell mitigation and reactive power support in a grid-connected wind farm with DVR
    Priyavarthini, S.
    Nagamani, C.
    Ilango, G. Saravana
    Rani, M. A. Asha
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 101 : 38 - 49
  • [2] DVR Control Based on Instantaneous Power
    Martin Garcia-Vite, Pedro
    Ramirez, Juan M.
    Posada Contreras, Johnny
    [J]. 2009 6TH INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING, COMPUTING SCIENCE AND AUTOMATION CONTROL (CCE 2009), 2009, : 180 - +
  • [3] Single Phase Detection of Voltage Sag Based on Instantaneous Reactive Power Theory
    Zhang Huizhi
    Li Yongli
    Li Botong
    Zhang Shuo
    Tan Zhen
    [J]. MATERIALS SCIENCE AND INFORMATION TECHNOLOGY, PTS 1-8, 2012, 433-440 : 7261 - 7266
  • [4] Improved single phase instantaneous p-q theory for DVR compensating nonlinear load
    Katole, D. N.
    Daigavane, M. B.
    Gawande, S. P.
    Daigavane, P. M.
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES), 2018,
  • [5] Research on Shunt Active Power Filter based on the Improved Instantaneous Reactive Power Theory
    Zhu, Liancheng
    Yan, Jinchong
    Chang, Liang
    Li, Fuyun
    Yang, Yujie
    Su, Xiaoying
    Wu, Zhitao
    Cui, Di
    [J]. 2015 SIXTH INTERNATIONAL CONFERENCE ON INTELLIGENT CONTROL AND INFORMATION PROCESSING (ICICIP), 2015, : 459 - 464
  • [6] Control strategy for unsymmetrical operation of HVDC-VSC based on the improved instantaneous reactive power theory
    Zhang, GB
    Xu, Z
    Wang, GZ
    [J]. SEVENTH INTERNATIONAL CONFERENCE ON AC-DC POWER TRANMISSION, 2001, (485): : 262 - 267
  • [7] Research on improved harmonic detection method based on instantaneous reactive power theory
    Chen, Lei
    Ji, Tiancheng
    Qi, Yingchuan
    Zhao, Hongtao
    Ma, Yanyan
    [J]. 2019 5TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING (ICAESEE 2019), 2020, 446
  • [8] Improved detection method of current component based on instantaneous reactive power theory
    Ma Wenchuan
    Zhang Shuo
    Wang Shuwen
    Song Yuzhu
    Zhang Dongmei
    Han Gang
    [J]. 2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [9] Improved method of detecting harmonic currents based on instantaneous reactive power theory
    Cheng, Li
    Fan, Mu-Hong
    Wang, Zhen-Yu
    Yin, Xing
    Liu, Xing-Qiao
    Zhu, Jun
    [J]. Gaodianya Jishu/High Voltage Engineering, 2007, 33 (04): : 46 - 49
  • [10] Digital Control of Active Power Line Conditioner Based on Instantaneous Reactive Power Theory
    Thirumoorthi, P.
    Surendar, V.
    Yadaiah, N.
    [J]. PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON CONTROL AUTOMATION, COMMUNICATION AND ENERGY CONSERVATION INCACEC 2009 VOLUME II, 2009, : 909 - +