Voltage Support and Imbalance Mitigation during Voltage Sags by Renewable Energy Fed Grid Connected Inverters

被引:0
|
作者
Lone, Azad Hamza [1 ]
Gedam, Amol Ishwarrao [1 ]
Sekhar, K. Ramachandra [1 ]
机构
[1] Indian Inst Technol Ropar, Dept Elect Engn, Ropar, India
关键词
Low Voltage Ride Through(LVRT); Point of Common Coupling(PCC); Renewable Energy Sources; Symmetrical Component Analysis; Phase Locked Loop(PLL); and Low Pass Filter(LPF); GENERATION INVERTERS; CONVERTERS;
D O I
10.1109/GLOBCONHT56829.2023.10087647
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this study, symmetrical component-based current injection is used to analyse a single-stage grid-connected inverter with low voltage ride-through (LVRT) capability. During voltage sags, the renewable source-fed voltage source inverter (VSI) may disconnect from the main grid at the point of common coupling. This condition arises due to the Under-voltage/overcurrent protection in the renewable inverters. This sudden disconnecting of the inverters may cause voltage collapse, frequency instability, and synchronous angle instability in utility networks with significant penetration of power from renewable inverters, which can result in blackouts. Utility grid rules require lowvoltage ride-through capabilities in grid-connected inverters to mitigate this effect. In order to support voltage and reduce voltage imbalance at the point of common coupling, a symmetrical component-based real and reactive power injection approach has been developed in this study. This technique is implemented by considering the constraint of not exceeding the inverter's rated current capability. The proposed technique effectively boosted the positive sequence voltage component to a reference value by using a PI controller. The negative sequence reactive power was drawn using the remaining reactive power capacity in order to suppress the voltage's negative sequence component. Results are presented in the paper for various voltage sag conditions. The proposed techniques are validated by simulating the model in a Matlab simulink environment.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Voltage recovery influence on three-phase grid-connected inverters under voltage sags
    Rolan, Alejandro
    Gimenez, Pablo
    Yague, Sauro J.
    Bogarra, Santiago
    Saura, Jaume
    Bakkar, Mostafa
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2019, 13 (03) : 435 - 443
  • [2] A Modified Modulation Scheme for Capacitor Voltage Control of Renewable Energy-Fed Grid-Connected Z-Source Inverters
    Hakeem, Ahmed A.
    Elserougi, Ahmed
    El Zawawi, Amr
    Ahmed, Shehab
    Massoud, A. M.
    38TH ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2012), 2012, : 886 - 893
  • [3] Active voltage support control strategy for a renewable generation farm during unbalanced voltage sags
    Bao Z.
    Ji L.
    Chang X.
    Jiang E.
    Shi J.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (16): : 161 - 169
  • [4] Control Strategy for Distribution Generation Inverters to Maximize the Voltage Support in the Lowest Phase During Voltage Sags
    Camacho, Antonio
    Castilla, Miguel
    Miret, Jaume
    Garcia de Vicuna, Luis
    Garnica L, Miguel Andres
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2018, 65 (03) : 2346 - 2355
  • [5] Mitigation of DC and Harmonic Currents Generated by Voltage Measurement Errors and Grid Voltage Distortions in Transformerless Grid-Connected Inverters
    Quoc Nam Trinh
    Wang, Peng
    Tang, Yi
    Choo, Fook Hoong
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2018, 33 (02) : 801 - 813
  • [6] Mitigation of Voltage Sags by Grid-Connected Distributed Generation System in Series and Shunt Configurations
    Wang Song-cen
    Yu Kun-shan
    Tang Guang-fu
    2008 JOINT INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON) AND IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2008, : 649 - +
  • [7] Control Scheme With Voltage Support Capability for Distributed Generation Inverters Under Voltage Sags
    Miret, Jaume
    Camacho, Antonio
    Castilla, Miguel
    Garcia de Vicuna, Luis
    Matas, Jose
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2013, 28 (11) : 5252 - 5262
  • [8] Mitigation of Voltage sags using Grey Wolf Optimization in the grids connected Energy Resources
    Nandini, R.
    Sekhar, Velappagari
    Ramesh, K.
    BIOSCIENCE BIOTECHNOLOGY RESEARCH COMMUNICATIONS, 2019, 12 (02): : 124 - 128
  • [9] Performance Assessment of Renewable Energy-Fed Three-Phase Grid-Connected Voltage Source Converters and Boost Inverters during DC Side Faults
    Elserougi, A.
    Abdel-Khalik, A. S.
    Massoud, A. M.
    Ahmed, S.
    39TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2013), 2013, : 1154 - 1158
  • [10] Grid Voltage Modulated Direct Power Control for Grid Connected Voltage Source Inverters
    Gui, Yonghao
    Kim, Chunghun
    Chung, Chung Choo
    2017 AMERICAN CONTROL CONFERENCE (ACC), 2017, : 2078 - 2084