Analysis of the GGD Vibroacoustic Detector of Power Transformer Core Damage

被引:0
|
作者
Krupinski, Robert [1 ]
Kornatowski, Eugeniusz [1 ]
机构
[1] West Pomeranian Univ Technol, Dept Signal Proc & Multimedia Engn, PL-71126 Szczecin, Poland
关键词
Vibrations; Detectors; Transformer cores; Windings; Power transformer insulation; Maximum likelihood estimation; Vibration measurement; Acoustics; Gaussian processes; Estimation; Vibroacoustic method; transformer core damage; generalized Gaussian distribution; estimation; GENERALIZED GAUSSIAN DISTRIBUTIONS; APPROXIMATED FAST ESTIMATOR; SHAPE PARAMETER; CLASSIFICATION; GENERATION; NOISE; MODEL; FRA;
D O I
10.1109/ACCESS.2024.3382114
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Vibroacoustic diagnostics (VM-Vibroacoustic Method) is one of the methods for diagnosing the active part of power transformers. One of the recently published objective method for the detection of transformer unit core damage was based on the analysis of the statistical properties of the vibration signal registered on the surface of the tank of an unloaded transformer in the steady state of vibrations. The GGD vibroacoustic detector of power transformer core damage is based on the relative changes in vibration power as a function of frequency and the generalized Gaussian distribution (GGD). The article shows how to configure the detector in order to reduce the variance at the detector output and speed up the detection.
引用
收藏
页码:45752 / 45761
页数:10
相关论文
共 50 条
  • [1] The Use of Generalized Gaussian Distribution in Vibroacoustic Detection of Power Transformer Core Damage
    Krupinski, Robert
    Kornatowski, Eugeniusz
    [J]. ENERGIES, 2020, 13 (10)
  • [2] The wavelet analysis of the vibroacoustic signal of the power transformer
    Borucki, Sebastian
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11B): : 182 - 185
  • [3] The influence of the power transformer load on vibroacoustic signal analysis results
    Borucki, Sebastian
    Cichon, Andrzej
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (07): : 45 - 47
  • [4] Mechanical-condition Assessment of Power Transformer Using Vibroacoustic Analysis
    Kornatowski, Eugeniusz
    [J]. ADVANCED MATERIALS IN MICROWAVES AND OPTICS, 2012, 500 : 40 - 44
  • [5] The Wavelet Analysis of the Vibroacoustic Signal Measurement in a Transient State Operation of Power Transformer
    Borucki, S.
    Cichon, A.
    Boczar, T.
    Zmarzly, D.
    [J]. ACTA PHYSICA POLONICA A, 2012, 122 (05) : 800 - 803
  • [6] The Vibroacoustic Characteristics Analysis of Transformer Core Faults Based on Multi-Physical Field Coupling
    Yao, Degui
    Li, Longfei
    Zhang, Songyang
    Zhang, Dianhai
    Chen, Dezhi
    [J]. SYMMETRY-BASEL, 2022, 14 (03):
  • [7] High Voltage Power Transformer Diagnostics using Vibroacoustic Method
    Zmarzly, Dariusz
    Boczar, Tomasz
    Fracz, Pawel
    Borucki, Sebastian
    [J]. 2014 IEEE INTERNATIONAL POWER MODULATOR AND HIGH VOLTAGE CONFERENCE (IPMHVC), 2014, : 561 - 564
  • [8] Analysis of Reactive Power of Transformer Core with Subsynchronous Components
    Sun J.
    Li L.
    Yu J.
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2022, 37 (20): : 5104 - 5116
  • [9] Evaluation of the Technical Condition of the Active Part of the High Power Transformer Based on Measurements and Analysis of Vibroacoustic Signals
    Borucki, Sebastian
    Cichon, Andrzej
    Majchrzak, Henryk
    Zmarzly, Dariusz
    [J]. ARCHIVES OF ACOUSTICS, 2017, 42 (02) : 313 - 320
  • [10] CHARACTERISTICS ANALYSIS OF SUPERCONDUCTING POWER TRANSFORMER WITHOUT IRON CORE
    YAMAGUCHI, H
    SATO, Y
    KATAOKA, T
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 1994, 114 (08) : 80 - 92