Predictive control for the operation of cascade pumping stations in water supply canal systems considering energy consumption and costs

被引:19
|
作者
Kong, Lingzhong [1 ,2 ]
Li, Yueqiang [2 ]
Tang, Hongwu [3 ]
Yuan, Saiyu [3 ]
Yang, Qian [1 ]
Ji, Qingfeng [1 ]
Li, Zhipeng [2 ]
Chen, Ruibin [1 ]
机构
[1] Yangzhou Univ, Coll Hydraul Sci & Engn, Yangzhou 225009, Peoples R China
[2] Hohai Univ, Coll Water Conservancy & Hydropower Engn, Nanjing 210098, Peoples R China
[3] Hohai Univ, State Key Lab Hydrol Water Resources & Hydraul Eng, Nanjing 210098, Peoples R China
基金
中国国家自然科学基金;
关键词
Predictive control; Energy efficiency; Pump operation; Water -supply canal systems; Time-of-use; ALGORITHM;
D O I
10.1016/j.apenergy.2023.121103
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Water supply canal systems (WSCSs) have a significant environmental and energetic impact due to the large amount of energy consumed in water pumping and water losses. The safe and efficient operation of these systems is crucial. This study presents a closed-loop predictive control method for the operation of pumping stations in WSCSs, considering operation safety and energy consumption. In the proposed method, a linear prediction model derived from the hydrodynamic model is used for state prediction; data assimilation is used to correct the prediction model based on the feedback water level information; on the basis of the prediction results, the optimization control model for energy or cost saving is rolling established and solved to obtain the optimal pump control strategy. The method was tested on a virtual simulation model of a WSCS with two pumping stations under uncertain disturbances and compared to an open-loop optimal control method. The results demonstrated that the proposed method's cost- and energy-driven optimization strategies could reduce the system's operating energy and cost by 5.1 % and 5.5 %, respectively while ensuring the safe operation of the system. Compared with the result of 1.4 % energy reduction and 0.2 % cost reduction under the open-loop optimal control, the proposed method can retain a better optimization effect under uncertain disturbance and has good robustness. Furthermore, the method can be modified according to the needs of the WSCSs for pump control.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] REMOTE MONITORING AND CONTROL OF PUMPING STATIONS IN THE WATER SUPPLY SYSTEMS
    Prvulovic, Slavica
    Tolmac, Dragisa
    Josimovic, Ljubisa
    Tolmac, Jasna
    [J]. FACTA UNIVERSITATIS-SERIES MECHANICAL ENGINEERING, 2013, 11 (01) : 113 - 121
  • [2] Optimization of Pumping Energy and Maintenance Costs in Water Supply Systems
    Pham Duc Dai
    Li, Pu
    [J]. MODELLING, COMPUTATION AND OPTIMIZATION IN INFORMATION SYSTEMS AND MANAGEMENT SCIENCES - MCO 2015, PT 1, 2015, 359 : 93 - 104
  • [3] REDUCING ENERGY CONSUMPTION BY UPGRADING PUMPING STATIONS IN WATER DISTRIBUTION SYSTEMS
    Perju, Sorin
    Hasegan, Liviu Valer
    [J]. ENVIRONMENTAL ENGINEERING AND MANAGEMENT JOURNAL, 2013, 12 (04): : 735 - 740
  • [4] Energy Efficient Control by the Group of Oil Pumping Stations Operation
    Kaniuk, G., I
    Yu, Mezeria A.
    Kniazeva, V. N.
    Fursova, T. N.
    Blyznychenko, E. N.
    [J]. PROBLEMELE ENERGETICII REGIONALE, 2021, (04): : 13 - 22
  • [5] Virtual Training on Pumping Stations for Drinking Water Supply Systems
    Romo, Juan E.
    Tipantasi, Gissela R.
    Andaluz, Victor H.
    Sanchez, Jorge S.
    [J]. AUGMENTED REALITY, VIRTUAL REALITY, AND COMPUTER GRAPHICS (AVR 2019), PT II, 2019, 11614 : 410 - 429
  • [6] Vibrational protection of the pumping stations in water-supply systems
    Aver'yanov G.S.
    Bel'kov V.N.
    Bur'yan Y.A.
    Korchagin A.B.
    Balashov V.S.
    [J]. Aver'yanov, G. S. (omankor@mail.ru), 1600, Allerton Press Incorporation (34): : 199 - 204
  • [7] Diagnostics and Control of Pumping Stations in Water Supply Systems: Hybrid Model for Fault Operating Modes
    Milosevic, Marko
    Radic, Milan
    Rasic-Amon, Milica
    Litricin, Dragan
    Stajic, Zoran
    [J]. PROCESSES, 2022, 10 (08)
  • [8] Optimal control of water supply pumping systems
    Ormsbee, Lindell E.
    Lansey, Kevin E.
    [J]. Journal of Water Resources Planning and Management, 1994, 120 (02) : 237 - 252
  • [9] METHODOLOGY FOR OPTIMAL OPERATION OF PUMPING STATIONS IN WATER DISTRIBUTION-SYSTEMS
    BRION, LM
    MAYS, LW
    [J]. JOURNAL OF HYDRAULIC ENGINEERING-ASCE, 1991, 117 (11): : 1551 - 1569
  • [10] DECREASING ENERGY CONSUMPTION OF WATER-SUPPLY PUMPING SYSTEMS IN THE ASPECT OF POLISH BALANCED ENERGY POLICY
    Spernol, Elzbieta