Experimental Verification of Mist Cooling Effect in Front of Air-Conditioning Condenser Unit, Open Space, and Bus Stop

被引:3
|
作者
Kyogoku, Sae [1 ]
Takebayashi, Hideki [1 ]
机构
[1] Kobe Univ, Urban Environm Engn Lab, Kobe 6578501, Japan
关键词
mist cooling; air-conditioning condenser unit; open space; bus stop;
D O I
10.3390/atmos14010177
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Mist spraying is a technique for locally lowering air temperature by spraying fine mist into the air and using the latent heat of evaporation immediately after spraying. This study focuses on the conditions under which mist spraying contributes to the increase in sensible heat release from the human body, using the ratio of air temperature decrease and humidity increase in the space where mist is sprayed. From the measurement results in front of the air-conditioning condenser unit, humidity increased by about 10 g/kg(DA), while air temperature decreased by about 10 degrees C. From the measurement results in an open space in a park, air temperature decreased by about 0.5 to 1 degrees C within 2 m of the mist spray and humidity increased by about 0.5 to 1 g/kg(DA) at the height of the mist spray, regardless of the distance from the mist spray. From the measurement results at semi-open bus stops, air temperature decreased slightly to 1 degrees C and humidity increased slightly to 1 g/kg(DA) under low-wind conditions. Unfortunately, the measured results of air temperature decrease in relation to humidity increase, which the human body perceives as cooler, were not available.
引用
收藏
页数:15
相关论文
共 7 条
  • [1] Experimental Study for the Effect of Pre-Cooling the Condenser Inlet Air of Split Type Air Conditioning Unit
    Faisal, Safaa H.
    Hammadi, Salman H.
    Mutlag, Saif S.
    ENGINEERING JOURNAL-THAILAND, 2018, 22 (05): : 67 - 85
  • [2] A comparative experimental study on the performance of the air-conditioning system through effective condenser cooling and preheating the refrigerant
    Mohamed Ibrahim, Mohamed Musthafa
    ENVIRONMENTAL PROGRESS & SUSTAINABLE ENERGY, 2021, 40 (01)
  • [3] Effect of a double-row liquid-vapor separation condenser on an air-conditioning unit performance
    Zhong, Tianming
    Ding, Lixing
    Chen, Shu
    Chen, Ying
    Yang, Qingcheng
    Luo, Yuhe
    APPLIED THERMAL ENGINEERING, 2018, 142 : 476 - 482
  • [4] A study on the thermal energy storage of different phase change materials incorporated with the condenser of air-conditioning unit and their effect on the unit performance
    Said, M. A.
    Hassan, Hamdy
    ENERGY AND BUILDINGS, 2019, 202
  • [5] Experimental investigation of the effect of condenser subcooling in R134a and R1234yf air-conditioning systems with and without internal heat exchanger
    Pottker, Gustavo
    Hrnjak, Pega
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 50 : 104 - 113
  • [6] Experimental Investigation of the Cooling Effect Generated by a Heat Sink Integrated Thermoelectric-Based U-Shaped Air-Conditioning System
    Patel, Yesha
    Siddique, Abu Raihan Mohammad
    Mohaghegh, Mohammad Reza
    Tasnim, Syeda Humaira
    Mahmud, Shohel
    APPLIED SCIENCES-BASEL, 2021, 11 (21):
  • [7] Experimental investigation on the effect of geometrical configuration of suction and discharge tube across the sub-units of propane-based vapor compression air-conditioning unit
    Kutar, Swayam Prakash
    Srivastava, Anmesh Kumar
    Chandra, Prakash
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2025,