Assessment of PM2.5 penetration based on airflow paths in Korean classrooms

被引:2
|
作者
Kim, Sihyeon [1 ]
Kang, Kyungmo [2 ]
Park, Dongjun [1 ]
Kim, Taeyeon [1 ]
机构
[1] Yonsei Univ, Dept Architecture & Architectural Engn, 50 Yonsei Ro, Seoul, South Korea
[2] Daejin Univ, Div Architectural Engn, 1007 Hoguk Ro, Pocheon Si, South Korea
基金
新加坡国家研究基金会;
关键词
Airflow pattern; Contribution analysis; Indoor air quality (IAQ); School with double-loaded corridor; PARTICLE DEPOSITION RATE; PARTICULATE MATTER; ELEMENTARY-SCHOOLS; INDOOR; QUALITY; ASSOCIATIONS; VENTILATION; INFILTRATION; PERFORMANCE; POLLUTANTS;
D O I
10.1016/j.buildenv.2023.111103
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
PM2.5 in classrooms adversely affect the health of young children, underscoring the importance of maintaining indoor air quality. In many Korean schools, the airtightness between a corridor and classrooms is not adequately tight. This lack of airtightness implies that corridors, often having high PM2.5 concentrations, significantly contribute to the degradation of classroom air quality. While some studies have acknowledged corridors as a key source of PM2.5 infiltration, few have quantitatively assessed the amount and frequency of PM2.5 entering classrooms through these pathways. This study examined the pattern and quantity of PM2.5 penetrating from the outdoor and corridor into classrooms in a typical Korean school. In south-facing classrooms, much of the infiltrating air originated directly from external walls, with a minimal amount coming from the corridor. However, given the corridor's relatively high PM2.5 concentration and significant penetration, approximately 25% of the total PM2.5 infiltration was attributed to the corridor. In contrast, east- and west-facing classrooms, influenced by Korea's prevalent westerly winds, experienced a pronounced increase in air entering the room, particularly from the corridor. Although the PM2.5 concentration in the corridor was lower than that in the south-facing classroom, the heightened airflow indicated that the corridor was responsible for 79% and 58% of PM2.5 infiltration in eastand west-facing classrooms, respectively. The results indicate that corridors' contribution to classroom PM2.5 levels is substantial; therefore, enhancing the airtightness between corridor and outdoor is crucial to reducing corridor PM2.5 levels. Alternatively, improving the airtightness between classrooms and corridor can effectively mitigate PM2.5 penetration.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] ASSESSMENT OF AIRBORNE PARTICULATE MATTER (PM2.5) IN UNIVERSITY CLASSROOMS OF VARRYING OCCUPANCY
    Aziz, K.
    Ali, Z.
    Nasir, Z. A.
    Colbeck, I.
    [J]. JOURNAL OF ANIMAL AND PLANT SCIENCES, 2015, 25 (03): : 649 - 655
  • [2] A key study on spatial source distribution of PM2.5 based on the airflow trajectory model
    Wang, Chengli
    Jiang, Hong
    Pan, Delu
    Lu, Xuehe
    Wang, Yixin
    Zhang, Shiqiao
    Xu, Jianhui
    [J]. INTERNATIONAL JOURNAL OF REMOTE SENSING, 2016, 37 (24) : 5864 - 5883
  • [3] PM2.5 Concentration Estimation Based on Image Quality Assessment
    Yang, Benqian
    Chen, Qiang
    [J]. PROCEEDINGS 2017 4TH IAPR ASIAN CONFERENCE ON PATTERN RECOGNITION (ACPR), 2017, : 676 - 681
  • [4] Characteristics of PM2.5 emitted from cement kiln and the risk assessment of PAHs in PM2.5
    Wei, Lin
    Tang, Hai-Long
    Guo, Ying-Ying
    Zou, Zheng-Yu
    Liu, Yang-Sheng
    [J]. Zhongguo Huanjing Kexue/China Environmental Science, 2014, 34 (05): : 1113 - 1118
  • [5] Constructing PM2.5 Map based on Mobile PM2.5 Sensor and Cloud platform
    Lin, Yung-Sheng
    Chang, Yu-Hsiang
    Chang, Yue-Shan
    [J]. 2016 IEEE INTERNATIONAL CONFERENCE ON COMPUTER AND INFORMATION TECHNOLOGY (CIT), 2016, : 702 - 707
  • [6] Indoor PM2.5 concentrations and students' behavior in primary school classrooms
    Zhou Yuhe
    Yang Guangfei
    Li Xianneng
    [J]. JOURNAL OF CLEANER PRODUCTION, 2021, 318
  • [7] The effect of horizontal elements and building orientation on PM2.5 concentration in classrooms
    Tikul, Nachawit
    Hokpunna, Apiruk
    Chawana, Panphat
    [J]. FRONTIERS OF ARCHITECTURAL RESEARCH, 2023, 12 (04) : 775 - 787
  • [8] Assessment of PM2.5 monitoring using MicroPEM: A validation study in a city with elevated PM2.5 levels
    Du, Yanjun
    Wang, Qin
    Sun, Qinghua
    Zhang, Ting
    Li, Tiantian
    Yan, Beizhan
    [J]. ECOTOXICOLOGY AND ENVIRONMENTAL SAFETY, 2019, 171 : 518 - 522
  • [9] Health impact assessment of PM2.5 in Japan
    Yorifuji, T.
    Tsuda, T.
    Yamamoto, E.
    [J]. EPIDEMIOLOGY, 2006, 17 (06) : S274 - S274
  • [10] Evaluation of particle penetration factors based on indoor PM2.5 removal by an air cleaner
    Peng, Chaohua
    Ni, Peiyong
    Xi, Guannan
    Tian, Weiguang
    Fan, Lujian
    Zhou, Dacheng
    Zhang, Qi
    Tang, Yu
    [J]. ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2020, 27 (08) : 8395 - 8405