A time-varying state-space model for real-time temperature predictions in rack-based cooling data centers

被引:11
|
作者
Tong, Xiaoxi [1 ,2 ]
Wang, Jiaqiang [1 ,2 ]
Liu, Weiwei [1 ]
Samah, Hodo-Abalo [1 ,5 ]
Zhang, Quan [3 ]
Zhang, Linfeng [4 ]
机构
[1] Cent South Univ, Sch Energy Sci & Engn, Changsha 410083, Hunan, Peoples R China
[2] Anhui Jianzhu Univ, Anhui Prov Key Lab Intelligent Bldg & Bldg Energy, Hefei 230022, Anhui, Peoples R China
[3] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
[4] Southeast Univ, Sch Transportat, Nanjing 211189, Jiangsu, Peoples R China
[5] Univ Kara, Lab Mat Renewable Energies & Environm, Kara, Togo
基金
中国国家自然科学基金;
关键词
Rack -based cooling data center; Temperature prediction; Time -varying state -space model; Parameter identification; WORKLOAD MANAGEMENT; SYSTEM;
D O I
10.1016/j.applthermaleng.2023.120737
中图分类号
O414.1 [热力学];
学科分类号
摘要
Fast-growing data centers (DCs) require efficient cooling systems (such as rack-based cooling architectures) and control strategies to reduce operating costs and guarantee desired indoor conditions. Thus, this study proposed a novel real-time temperature prediction model for rack-based cooling DCs, in order to facilitate advanced control regarding cooling management and workload assignment. Specifically, a data-driven technology was introduced to estimate time-invariant model parameters, in order to avoid the time-consuming physics-based parameters extracting process. The mass conservation relationships were employed to update time-varying flow parameters in real-time to capture the nonlinear behaviors in DCs. Moreover, the proposed control-oriented thermal modeling method can model hot air recirculation and cold air bypass occurring simultaneously for the first time. The performance of the developed time-varying state-space model was validated by CFD simulation data. Additionally, the timeliness of modeling and temperature prediction was also investigated. The results show that the developed model achieves sufficient accuracy with a mean absolute error (MAE) equal to 0.28 degrees C, even for long prediction horizons and dynamic IT workloads. Also, the developed model has outstanding timeliness for advanced control techniques, in terms of less than 30 min for parameter identification and less than 10 s for temperature prediction.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Real-time temperature predictions via state-space model and parameters identification within rack-based cooling data centers
    Liu, Weiwei
    Tong, Xiaoxi
    Wang, Jiaqiang
    Yue, Chang
    Zhang, Quan
    JOURNAL OF BUILDING ENGINEERING, 2022, 58
  • [2] Real-time temperature distribution reconstruction via linear parameter-varying state-space model and Kalman filter in rack-based cooling data centers
    Wang, Jiaqiang
    Tong, Xiaoxi
    Yue, Chang
    Liu, Weiwei
    Zhang, Quan
    Zeng, Liping
    Huang, Gongsheng
    BUILDING AND ENVIRONMENT, 2023, 242
  • [3] Model-based control strategy with linear parameter-varying state-space model for rack-based cooling data centers
    Deng, Weiqi
    Wang, Jiaqiang
    Yue, Chang
    Guo, Yang
    Zhang, Quan
    ENERGY AND BUILDINGS, 2024, 319
  • [4] Estimating time-varying proximity with a state-space model
    Liu, Shaowen
    Caporin, Massimiliano
    Paterlini, Sandra
    JOURNAL OF STATISTICAL COMPUTATION AND SIMULATION, 2023, 93 (14) : 2534 - 2562
  • [5] A gray-box model for real-time transient temperature predictions in data centers
    Asgari, Sahar
    MirhoseiniNejad, SeyedMorteza
    Moazamigoodarzi, Hosein
    Gupta, Rohit
    Zheng, Rong
    Puri, Ishwar K.
    APPLIED THERMAL ENGINEERING, 2021, 185
  • [6] DECOMPOSITION OF TIME-VARYING LC ELEMENTS AND STATE-SPACE FORMULATION
    MURATA, T
    ELECTRONICS LETTERS, 1969, 5 (07) : 142 - &
  • [7] Modelling time-varying growth in state-space stock assessments
    Correa, Giancarlo M.
    Monnahan, Cole C.
    Sullivan, Jane Y.
    Thorson, James T.
    Punt, Andre E.
    ICES JOURNAL OF MARINE SCIENCE, 2023, 80 (07) : 2036 - 2049
  • [8] Time-varying biorthogonal filter banks: A state-space approach
    Lemma, AN
    Deprettere, EF
    IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-FUNDAMENTAL THEORY AND APPLICATIONS, 1998, 45 (03): : 280 - 289
  • [9] TIME-VARYING 2-DIMENSIONAL STATE-SPACE STRUCTURES
    MCLERNON, DC
    IEE PROCEEDINGS-CIRCUITS DEVICES AND SYSTEMS, 1995, 142 (02): : 120 - 124
  • [10] OPTIMAL FIR FILTERS FOR TIME-VARYING STATE-SPACE MODELS
    KWON, WH
    LEE, KS
    KWON, OK
    IEEE TRANSACTIONS ON AEROSPACE AND ELECTRONIC SYSTEMS, 1990, 26 (06) : 1011 - 1021