Experimental study on performance of different local radiant cooling schemes

被引:10
|
作者
Zhang, Dongkai [1 ]
Li, Cui [2 ]
Li, Zhengrong [2 ]
机构
[1] Hefei Univ Technol, Coll Architecture & Art, Hefei 230009, Anhui, Peoples R China
[2] Tongji Univ, Sch Mech Engn, Shanghai 200092, Peoples R China
关键词
Local radiant cooling; Layout scheme; Thermal comfort; Room thermal characteristics; THERMAL COMFORT; ENERGY-CONSUMPTION; HEATING-SYSTEM; HUMAN RESPONSE; TEMPERATURE; ENVIRONMENT; RADIATION; BEHAVIOR; DESIGN; OFFICE;
D O I
10.1016/j.ijrefrig.2023.04.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
Energy consumption from building cooling is critical for the development of nearly-zero energy building. The indoor zone control of local cooling strategy has been proposed to address this problem. In this study, the application performance of different layout scheme of local radiant cooling was experimentally investigated to explore the optimum design strategy. A series of field experiments were conducted under eight layout schemes of the local radiant cooling considered height, horizontal installation zone, and area of the radiant terminal. The obtained results indicate that in the personnel activity zone (below 2.0 m), local radiant cooling can satisfy the thermal comfort requirements of the occupant. The installation zone has an obvious influence on the room thermal characteristics, whereas the influence from the area was limited. The thermal stability and uniformity of the indoor environment can be improved by modifying the layout of the low and outer zone for the radiant terminal. Increasing the area of the radiant panel is inefficient for the improvement of room thermal characteristics and indoor thermal comfort. The main ranges of the cooling capacity are 115-125 W/m2 for different layout forms of the local radiant terminal and the cooling capacity can be increased by 7%. The layout scheme for the radiant terminal with the outer and low zone can effectively improve the stability of the terminal cooling capacity. Results suggested that the layout scheme of both outer and low zone for the local radiant terminal is crucial to improve the thermal comfort and cooling efficient.
引用
收藏
页码:241 / 252
页数:12
相关论文
共 50 条
  • [1] AN EXPERIMENTAL STUDY ON THE PERFORMANCE OF RADIANT FLOOR COOLING MODULES
    Chien, K. C.
    Chuah, Y. K.
    Chang, W. T.
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2013, 21 (02)
  • [2] THE EXPERIMENTAL STUDY ON THERMAL PERFORMANCE OF COOLING RADIANT CEILING UNIT
    Gao, S. L.
    Yu, G. Q.
    Lv, W.
    7TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, PROCEEDINGS OF ISHVAC 2011, VOLS I-IV, 2011, : 799 - 804
  • [3] Experimental Study of Heat Performance on Ceiling Radiant Cooling Panel
    Yuan, Yong-Li
    Zhou, Xiang
    Zhang, Xu
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 2176 - 2183
  • [4] EXPERIMENTAL STUDY ON THERMAL PERFORMANCE OF THE RADIANT FLOOR COOLING SYSTEM IN BEIJING
    Wu, Pin
    Chen, Chao
    Lin, Jie
    Li, Qingqing
    Li, Zhuo
    Zhang, Ye
    Quan, Zhenhua
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 2139 - 2146
  • [5] Performance Comparisons of Different Radiant Cooling Panel Positions
    Gao, Zhihong
    Liu, Xiaohua
    Jiang, Yi
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 2083 - 2090
  • [6] An experimental study of thermal performance of the radiant ceiling cooling in office building in Thailand
    Aryal, Ashmin
    Chaiwiwatworakul, Pipat
    Chirarattananon, Surapong
    ENERGY AND BUILDINGS, 2023, 283
  • [7] Cooling Performance Prediction for Hydraulic Thermoelectric Radiant Cooling Panels with Experimental Validation
    Kim, Minseong
    Kang, Yong-Kwon
    Joung, Jaewon
    Jeong, Jae-Weon
    SUSTAINABILITY, 2022, 14 (23)
  • [8] Experimental Study on Performance of Lightweight Radiant Floor Cooling Combined with Underfloor Ventilation System
    Xia, Xue-ying
    Zhang, Xu
    LOW-CARBON CITY AND NEW-TYPE URBANIZATION, 2015, : 307 - 315
  • [9] Experimental Study on Cooling Characteristics of Concrete Ceiling Radiant Cooling Panel
    Su, Lin
    Li, Nianping
    Zhang, Xuhan
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 2168 - 2175
  • [10] The performance of radiant cooling test system under different covers
    Byun, Ki-Hong
    Smith, Theodore F.
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 427 - +