Performance characterization of M-cycle indirect evaporative cooler and heat recovery ventilator for commercial buildings-Experiments and model

被引:4
|
作者
Chakraborty, Subhrajit [1 ]
Vernon, David [1 ]
Jha, Apoorva [2 ]
Narayanan, Vinod [1 ,2 ]
机构
[1] Univ Calif Davis, Western Cooling Efficiency Ctr, 215 Sage St,Suite 100, Davis, CA 95616 USA
[2] Univ Calif Davis, Dept Mech & Aerosp Engn, 2132 Bainer Hall,One Shields Ave, Davis, CA 95616 USA
关键词
HRV; IEC; ERV; Heat and mass transfer; Evaporative cooling; M-cycle; MAISOTSENKO CYCLE; NUMERICAL-ANALYSIS; EXCHANGERS; FLOW;
D O I
10.1016/j.enbuild.2022.112762
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Evaporative cooling systems in buildings can dramatically reduce greenhouse gas emissions due to their low energy consumption, lack of ecologically harmful refrigerants and their diverse applications. Indirect evaporative cooling (IEC) uses water in the secondary air stream to cool the primary air without adding humidity to the indoor environment. The Maisotsenko Cycle (M-Cycle) design of an IEC has the potential to approach dew-point on the primary air by pre-cooling the secondary air stream before extracting heat in cross-flow with the primary air. Separately, a variety of technologies exist for energy recovery in com-mercial buildings to pre-condition ventilation air. In this study a M-cycle heat and mass exchanger was used as a heat recovery ventilator (HRV) to recover energy from the exhaust air stream during winter and as an IEC during summer to cool the ventilation air. Experiments were performed by operating the full-size IEC/HRV system with a maximum air flow rate of 2210 m3/hr in conjunction with indoor and outdoor environmental chambers simulating respective environments. The experimental results showed HRV heating sensible effectiveness between 67 % and 63 % and IEC cooling total effectiveness between 81 % and 71 % with increasing air flow rates. A detailed numerical model was developed to predict the perfor-mance of the IEC/HRV over a large range of operating conditions. The IEC model simulates heat and mass transfer from water evaporation in the secondary air and potentially from condensation in the primary air during summer season operation. The HRV model simulates heat transfer and potentially mass trans-fer from secondary air condensation during winter season operation. The detailed physics-based model was compared with experimental data, and it predicted the performance with high accuracy for both summer and winter operating conditions. The average absolute errors for supply air temperature between the experimental results and model predictions were 0.2 degrees C in HRV winter mode and 1.0 degrees C in IEC summer mode. The validated IEC model was used to further explore the possibility of combined ventilation and passive space cooling without a supplemental air-conditioner. The analysis shows that utilizing IEC for summer operation offers high cooling COP and even the potential for passive space cool-ing, which is not possible with conventional energy recovery ventilators (ERV).(c) 2022 The Authors. Published by Elsevier B.V. This is an open access article under the CC BY license (http:// creativecommons.org/licenses/by/4.0/).
引用
收藏
页数:18
相关论文
共 12 条
  • [1] Enhancing the performance of an M-cycle based tubular indirect evaporative cooler by mesh screens
    Rahmati, Bahram
    Jadidi, Amir Mohammad
    Valipour, Mohammad Sadegh
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2024, 156
  • [2] Optimization of the performance of M-Cycle indirect evaporative cooling via thermodynamic approach
    Jia, Chenxia
    Sun, Daxi
    Hu, Xingfu
    Jing, Chengjun
    JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING, 2023, 22 (06) : 3612 - 3626
  • [3] Numerical study of a M-cycle cross-flow heat exchanger for indirect evaporative cooling
    Zhan, Changhong
    Zhao, Xudong
    Smith, Stefan
    Riffat, S. B.
    BUILDING AND ENVIRONMENT, 2011, 46 (03) : 657 - 668
  • [4] THE ENERGY AND EXERGY ANALYSIS ON THE PERFORMANCE OF COUNTER-FLOW HEAT AND MASS EXCHANGER FOR M-CYCLE INDIRECT EVAPORATIVE COOLING
    Wang, Lei
    Zhan, Chonghong
    Zhang, Jianli
    Zhao, Xudong
    THERMAL SCIENCE, 2019, 23 (02): : 613 - 623
  • [5] Full optimal geometric exploration of M-cycle indirect evaporative dewpoint cooler using a substantial experiment-oriented AI algorithm
    Dizaji, Hamed Sadighi
    Pourhedayat, Samira
    Moria, Hazim
    Aldawi, Fayez
    Anqi, Ali E.
    Alsenani, Theyab R.
    APPLIED THERMAL ENGINEERING, 2025, 261
  • [6] Comparative study of the performance of the M-cycle counter-flow and cross-flow heat exchangers for indirect evaporative cooling - Paving the path toward sustainable cooling of buildings
    Zhan, Changhong
    Duan, Zhiyin
    Zhao, Xudong
    Smith, Stefan
    Jin, Hong
    Riffat, Saffa
    ENERGY, 2011, 36 (12) : 6790 - 6805
  • [7] Optimization of the counter-flow heat and mass exchanger for M-Cycle indirect evaporative cooling assisted with entropy analysis
    Wang, Lei
    Zhan, Changhong
    Zhang, Jianli
    Zhao, Xudong
    ENERGY, 2019, 171 : 1206 - 1216
  • [8] Modeling and multi-objective optimization of an M-cycle cross-flow indirect evaporative cooler using the GMDH type neural network
    Sohani, Ali
    Sayyaadi, Hoseyn
    Hoseinpoori, Sina
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 69 : 186 - 204
  • [9] Improving the performance of indirect evaporative cooler for energy recovery from the perspective of nozzle configuration: A CFD model analysis
    Ma, Xiaochen
    Shi, Wenchao
    Yang, Hongxing
    JOURNAL OF BUILDING ENGINEERING, 2023, 76
  • [10] Numerical study on performance of a hybrid indirect evaporative cooling heat recovery heat pump ventilator as applied in different climatic regions of China
    Wang, Jue
    Lu, Jun
    Li, Wuyan
    Zeng, Cheng
    Shi, Fenghao
    ENERGY, 2022, 239