Comparative study on the thermal characteristics of natural draft wet cooling tower with internal and external auxiliary fans

被引:6
|
作者
Chen, Xuehong [1 ]
Sun, Fengzhong [2 ]
Xia, Lijiang [1 ]
Song, Xu [1 ]
Zhang, Xiaoyu [2 ]
机构
[1] Ludong Univ, Low Carbon Energy Inst, Yantai 264000, Peoples R China
[2] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
关键词
Natural draft wet cooling tower; Internal auxiliary fan; External auxiliary fan; Thermal performance; Environmental crosswind; Air deflector; Numerical calculation; NUMERICAL-SIMULATION; PERFORMANCE; VENTILATION; WALLS;
D O I
10.1016/j.ijheatmasstransfer.2022.123648
中图分类号
O414.1 [热力学];
学科分类号
摘要
Auxiliary ventilation is an innovative approach for strengthening the thermal performance of natural draft wet cooling towers, which can be implemented with internal and external fans. In this study, a threedimensional numerical model for cooling tower with these fans is established, with consideration of the existence or absence of air deflectors. To comparatively study the thermal performance of the above cooling towers, some critical parameters such as the air mass flow rate and circulating water temperature drop are computed, and the airflow and water temperature field are also investigated. Results manifest that external fans can enhance the air mass flow rate greater than internal fans under various crosswind velocities, while they are more effective in increasing the water temperature drop under a lower and a higher crosswind velocity, with a maximum increment of 8.5% and 10.0%, respectively. The addition of air deflectors narrows the high-velocity area, thus improving the uniformity of air distribution. The positive effect of air deflectors enhances with the increase of crosswind velocity, which decreases the water temperature drop of cooling tower with internal fans and that with external fans by 10.3% and 5.6% at most, respectively. This study can promote the engineering applications of auxiliary fans.(c) 2022 Elsevier Ltd. All rights reserved.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Comparative study on the cooling characteristics of high level water collecting natural draft wet cooling tower and the usual cooling tower
    Zhao, Yuanbin
    Sun, Fengzhong
    Long, Guoqing
    Huang, Xiaofeng
    Huang, Wenqiang
    Lyv, Dongqiang
    ENERGY CONVERSION AND MANAGEMENT, 2016, 116 : 150 - 164
  • [2] Thermal optimization of a natural draft wet cooling tower
    Williamson, N.
    Behnia, M.
    Armfield, S. W.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (14) : 1349 - 1361
  • [3] Numerical study of natural draft wet cooling tower
    Zheng Shuihua
    Jin Tai
    Fan Jianren
    MEMS, NANO AND SMART SYSTEMS, PTS 1-6, 2012, 403-408 : 3191 - 3194
  • [4] Numerical simulation for thermal performance of natural draft wet cooling tower
    Zhou, Lan-Xin
    Jiang, Bo
    Chen, Su-Min
    Shuili Xuebao/Journal of Hydraulic Engineering, 2009, 40 (02): : 208 - 213
  • [5] Evaluation of thermal performance for natural and forced draft wet cooling tower
    Al-Dulaimi, M. J.
    Kareem, F. A.
    Hamad, F. A.
    JOURNAL OF MECHANICAL ENGINEERING AND SCIENCES, 2019, 13 (04) : 6007 - 6021
  • [6] Thermal characteristics of dry cooling tower reconstructed from obsolete natural draft wet cooling tower and the relevant thermal system coupling optimization
    Ge, Wenjing
    Zhao, Yuanbin
    Song, Shiwei
    Li, Wendong
    Gao, Shasha
    Chen, TieFeng
    APPLIED THERMAL ENGINEERING, 2020, 174
  • [7] The discussion on cooling optimization of natural draft wet cooling tower
    Ma, L. B.
    Ren, J. X.
    Li, F. Q.
    Zhang, L. J.
    Li, M. Q.
    2018 FIRST INTERNATIONAL CONFERENCE ON ENVIRONMENT PREVENTION AND POLLUTION CONTROL TECHNOLOGY (EPPCT 2018), 2018, 199
  • [8] Three-dimensional numerical study on thermal performance in a natural draft wet cooling tower
    Zheng, Shuihua
    Jin, Tai
    Fan, Jianren
    ADVANCES IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 614-615 : 169 - +
  • [9] Evaluating vaporization heat, thermal performance, and efficiency of a natural draft wet cooling tower
    Song, Baohong
    Song, Yu
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2022, 236 (06) : 1183 - 1191
  • [10] The influence and analysis of natural crosswind on cooling characteristics of the high level water collecting natural draft wet cooling tower
    Ma, Libin
    Ren, Jianxing
    2017 3RD INTERNATIONAL CONFERENCE ON ENVIRONMENTAL SCIENCE AND MATERIAL APPLICATION (ESMA2017), VOLS 1-4, 2018, 108