Improved design shear method of the bolted cold-formed steel clip-angle for serviceability

被引:2
|
作者
Mallepogu, Nagaraju [1 ]
Madhavan, Mahendrakumar [1 ]
机构
[1] Indian Inst Technol Hyderabad, Dept Civil Engn, Sangareddy 502284, Telangana, India
关键词
Three bolted clip-angle; CFS beam-to-column connection; Service limit-state design; Welded clip-angle; Reliability studies; CONNECTIONS;
D O I
10.1016/j.tws.2023.110994
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents an experimental investigation on the three-bolted clip-angle (CA) connector under direct shear load. A total of 48 clip-angle connection tests were carried out with 27 different clip-angle configurations by varying the thickness, width and depth of the clip-angle. The present experimental results and the data from literature indicates that the existing design methods for the service limit state design of the clip-angle are inefficient. The present investigation proposes a novel and efficient design method for the service limit state after calibration against test data, for the low-grade steel clip-angle (fy = 271 MPa to 307 MPa) from the present research work and for the higher grade steel (fy = 375 MPa to 550 MPa) from the literature data. Hence the proposed design method has wider steel grade application from fy = 271 MPa to 550 MPa. Parametric studies were performed to evaluate the influence of the geometric variables on the service shear strength of the three bolted clip-angle. The proposed design method was also applied to the welded clip-angle configuration in the literature and corresponding design equations were developed. In addition, a comparative study between the present three-bolted and most recent welded clip-angle connection was conducted which indicated that the three-bolted clip-angle configuration has higher stiffness than that of the welded configuration. Reliability studies were performed and relevant design factors were determined according to the LRFD, LSD and ASD methods.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Improved Design Shear Method for the Bolted Cold-Formed Steel Clip-Angle Connector
    Mallepogu, Nagaraju
    Madhavan, Mahendrakumar
    JOURNAL OF STRUCTURAL ENGINEERING, 2023, 149 (05)
  • [2] A unified design model to assess the shear behaviour and ultimate strength of a cold-formed steel welded and bolted clip-angle connection
    Mallepogu, Nagaraju
    Madhavan, Mahendrakumar Mathialagu
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2025, 228
  • [3] Improved shear design method of cold-formed steel clip angles
    Zhang, Wenying
    Liu, Yang
    Xu, XiangZhi
    Yu, Cheng
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2022, 188
  • [4] Serviceability limit state for cold-formed steel bolted connections
    LaBoube, RA
    Yu, WW
    Carril, JL
    CONNECTIONS IN STEEL STRUCTURES III: BEHAVIOUR, STRENGTH AND DESIGN, 1996, : 403 - 411
  • [5] Shear capacity of the cold-formed steel beam to column welded moment connection using clip-angle and flange-cleat
    Mallepogu, Nagaraju
    Madhavan, Mahendrakumar
    THIN-WALLED STRUCTURES, 2023, 187
  • [6] Experimental analysis of the cold-formed steel beam-to-column connection using the welded clip-angle
    Mallepogu, Nagaraju
    Madhavan, Mahendrakumar
    THIN-WALLED STRUCTURES, 2022, 179
  • [7] Testing and design of cold-formed steel clip angles in tension: Pull-over and serviceability
    Zhang, Wenying
    Mandavian, Mahsa
    Yousof, Mohamad
    Yu, Cheng
    THIN-WALLED STRUCTURES, 2018, 124 : 13 - 19
  • [8] Improved shear design rules of cold-formed steel beams
    Keerthan, Poologanathan
    Mahendran, Mahen
    ENGINEERING STRUCTURES, 2015, 99 : 603 - 615
  • [9] THE DESIGN OF BOLTED JOINTS IN COLD-FORMED STEEL SECTIONS
    BRYAN, ER
    THIN-WALLED STRUCTURES, 1993, 16 (1-4) : 239 - 262
  • [10] Design of Cold-Formed Steel Clip Angles in Compression
    Yu, Cheng
    Yousof, Mohamad
    Mahdavian, Mahsa
    Zhang, Wenying
    JOURNAL OF STRUCTURAL ENGINEERING, 2017, 143 (06)