Analysis of a Water-Cooled Unit under Different Loads

被引:0
|
作者
Shen, Daoming [1 ]
Xia, Jinhong [1 ]
Gui, Chao [1 ]
Xue, Songtao [2 ]
机构
[1] Xinxiang Univ, Xinxiang 453000, Peoples R China
[2] Tohoku Inst Technol, Dept Architecture, Sendai 9828577, Japan
来源
基金
中国国家自然科学基金;
关键词
Ambient temperature; cold source temperature; refrigerating capacity; Energy ef fi ciency ratio (COP); fan speed load; SCROLL COMPRESSOR; PERFORMANCES;
D O I
10.32604/fdmp.2023.024925
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In order to ensure the safe operation of the compressors used in water chillers, in the present study some interlock protections have been added to the related design. These include a low pressure protection, a high pressure protection, an exhaust temperature protection and a differential pressure protection. Some tests have been conducted by tuning the saturation suction and exhaust temperatures of the compressor through adjustment of the cold source outlet temperature and the ambient temperature. The results show that the ambient temperature increases with decreasing device load and increasing fan speed under the same saturated suction temperature; the device refrigerating capacity steps up with augmenting load and dropping saturation exhaust temperature, while it is not greatly affected by the fan speed. Moreover, the Energy efficiency ratio (COP) decreases with the rise of the saturation exhaust temperature. This parameter is not affected much by the device load and fan speed at high saturation exhaust temperature, while it improves on increasing the device load and decreasing the fan speed at low saturation exhaust temperature.