Experimental Study On Bird Streamer Flashover for V-Type Insulators of DC Transmission Line in High Altitude Area

被引:0
|
作者
Wang, Shenghui [1 ]
Lei, Shengfeng [1 ]
Zhou, Jun [2 ]
Ding, Yujian [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewable, Beijing 102206, Peoples R China
[2] China Elect Power Res Inst, Beijing 100192, Peoples R China
关键词
Birds; Flashover; Viscosity; Insulators; Conductivity; Discharges (electric); Power transmission lines; High altitude; DC; Bird streamer flashover; Protection range; Breakdown potential gradient; PREVENTIVE MEASURES; POWER OUTAGES;
D O I
10.1109/TPWRD.2022.3199262
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In order to obtain the bird streamer flashover characteristics in high altitude areas, the discharge of DC V-type string insulators was studied in high-altitude test base at 4300 m in Tibet. The study results show that medium viscosity bird streamer is easy to form a continuous channel and cause flashover. The flashover probability of positive polarity transmission lines is slightly higher than that of negative. The conductivity of bird excrement almost has no effect on the flashover probability in the range of 1.9 similar to 20.9 mS/cm. To increase the vertical air gap distance can reduce bird streamer flashover probability. Based on the experiment results, the recommended vertical air gap distance values of +/- 400 kV DC transmission line were proposed. Considering the influence of wind and bird streamer falling angle, the protection radius was set 3.5 m at 3500 similar to 5000 m altitude area. Bird streamer flashover is a mixed discharge of air gap breakdown and the surface discharge along the bird streamer channel, at the altitude of 4300 m area, the minimum breakdown potential gradient is about 2.1 kV/cm, and the discharge between bird streamer and shielding ring can be approximately equivalent to rod-rod gap discharge.
引用
收藏
页码:812 / 820
页数:9
相关论文
共 14 条
  • [1] Simulated Experimental Research on the Bird Streamer Flashover of DC Transmission Line in High Altitude Area
    Zhou J.
    Wang S.
    Ding Y.
    Wang X.
    Yao X.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (04): : 1345 - 1352
  • [2] Study of DC Flashover Performance of Ice-covered Insulators at High Altitude
    Jiang, Xingliang
    Zhao, Shihua
    Hu, Jianlin
    Zhang, Zhijin
    Shu, Lichun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (02) : 391 - 400
  • [3] DC pollution flashover performance of ultra high voltage parallel double insulators in high altitude area
    Song, Lei
    Zhang, Fuzeng
    Liang, Xidong
    Liao, Yifan
    Li, Ruihai
    Gaodianya Jishu/High Voltage Engineering, 2013, 39 (06): : 1382 - 1389
  • [4] Influence of angles of V-strings on DC flashover characteristics of polluted insulators in high altitude areas
    Zhang Fuzeng
    Wang Xin
    Long Biao
    Wang Liming
    Guan Zhicheng
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 449 - 452
  • [5] Study on pollution flashover characteristic of insulators on 500kV AC transmission lines in high-altitude area
    Huang, Ruiping
    Zhou, Jun
    Xu, Yueneng
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 3306 - 3309
  • [6] Flashover Possibility Analysis of Overhead Power Transmission and Distribution Line Insulators with the Excitation of High Altitude Electromagnetic Pulse
    Zhang H.
    Zou J.
    Tian B.
    Wu M.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (02): : 435 - 443
  • [7] Analysis and Protection Studies of Bird Droppings Falling on the Electric Field Distribution Near the 330-kV Transmission Line V-Type Composite Insulators
    Wang, Wenzhuo
    Ma, Zhenxiang
    Fan, Yudi
    Ma, Jianqiao
    Liu, Kang
    Wang, Yihu
    Xu, Hao
    IEEE ACCESS, 2024, 12 : 97938 - 97950
  • [8] Study on Process of DC Pollution Flashover of Porcelain Insulators of Parallel Double-Strings Form at High Altitude
    Peng, Gongmao
    Zhao, Feng
    Guan, Zhicheng
    Wang, Liming
    CEIDP: 2009 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2009, : 526 - +
  • [9] Lightning Flashover Performance Test and Flashover Criterion Study of Insulators in a 110 kV True Type Tower at High Altitude Areas
    Zhang Y.
    Han Y.
    Yang J.
    Ruan Y.
    Liu G.
    Cai H.
    Li L.
    Dianwang Jishu/Power System Technology, 2019, 43 (01): : 340 - 348
  • [10] Air-gaps Flashover Characteristics and Insulation Coordination of Inverse V-type Insulator String Tower for UHV AC Transmission Line
    Hu W.
    Huo F.
    Xu T.
    Nan J.
    Ye Q.
    Ma Y.
    Gaodianya Jishu/High Voltage Engineering, 2017, 43 (12): : 4117 - 4122