Performance analysis and optimisation of the chiller-air handling units system with a wide range of ambient temperature

被引:9
|
作者
Zulkafli, Nur I. [1 ]
Sukri, Mohamad F. [1 ]
Tahir, Musthafah Mohd [1 ]
Muhajir, Asjufri [1 ]
Hanak, Dawid P. [2 ,3 ]
机构
[1] Univ Teknikal Malaysia Melaka, Fac Mech Engn, Ctr Adv Res Energy, Durian Tunggal 76100, Melaka, Malaysia
[2] Canfield Univ, Sch Water Energy & Environm, Energy & Sustainabil, Canfield MK43 0AL, Bedfordshire, England
[3] Teesside Univ, Net Zero Ind Innovat Ctr, Middlesbrough TS1 3BA, England
来源
关键词
Chiller; Air handling unit; Cooling tower; HVAC; Linear programming model; Coefficient of performance; Power consumption; ENERGY;
D O I
10.1016/j.clet.2023.100643
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The integrated optimisation modelling for the chiller-air handling units system is developed for increasing the efficiency and energy utilisation of system. A building management system in the chillers network controls the cooling load to ensure the specified desired set temperature of the cooling air within the building can be satisfied. Unfortunately, the desired set point temperature of the cooling air is a fixed value and does not vary with the dynamic change of cooling demand with different ambient temperatures. Therefore, the power consumption of the chillers and the building cooling requirement with a wide range of different ambient temperatures is properly modelled by optimising the performance of chillers, air handling units, cooling towers, and water pumps. The linear programming model for the system is established to model a real representation of the chiller-air handling unit system. The result shows that the optimal coefficient of performance is greater by about 7%-10% than the current chiller system. The optimal power consumption of the chiller system reduces to 3%. Overall, the optimal decision solutions could be used as the potential improvement strategy to control the desired set point values in the building management system for efficient chiller-AHU system.
引用
收藏
页数:16
相关论文
共 50 条
  • [1] Performance analysis and improvement of air-to-water chiller for application in wide ambient temperature range
    Ding, GL
    Fu, L
    APPLIED THERMAL ENGINEERING, 2005, 25 (01) : 135 - 145
  • [2] A comparative thermodynamic analysis of air handling units at variable reference temperature
    Martinaitis, Vytautas
    Streckiene, Giedre
    Bagdanavicius, Audrius
    Bielskus, Juozas
    APPLIED THERMAL ENGINEERING, 2018, 143 : 385 - 395
  • [3] Evaluation of supply air temperature control performance with different control strategies at air handling units
    Wang, Zufen
    Hashem, Marwan R.
    Song, Li
    Wang, Gang
    BUILDING AND ENVIRONMENT, 2023, 243
  • [4] Air management modeling of condensing units in a confined space and its impact on the chiller system performance
    Shi, Yu-Ling
    Yang, Liang
    Zhang, Chun-Lu
    ENERGY AND BUILDINGS, 2011, 43 (10) : 2673 - 2677
  • [5] Performance test of medium-temperature chiller with induction air-conditioning system
    Hong, Yuhua
    Wang, Gaoyuan
    Wang, Zhiyi
    INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2022, 17 : 373 - 379
  • [6] Analysis, design, and optimisation of an LCC/S compensated WPT system featured with wide operation range
    Qi, Jiajin
    IET POWER ELECTRONICS, 2020, 13 (09) : 1819 - 1827
  • [7] Analysis of the anti-icing system used in air handling units with a counterflow heat exchanger
    Jaszczur, Marek
    Kleszcz, Slawosz
    Borowski, Marek
    ENERGY AND FUELS 2018, 2019, 108
  • [8] Ambient air temperature sensitivity analysis for indirect air cooled system with compound refrigeration cycle
    Yang, Shan-Rang (yangshanrang@126.com), 1600, Zhejiang University (48):
  • [9] EFFECT OF RANDOM FLUCTUATIONS IN AMBIENT AIR-TEMPERATURE ON SOLAR-SYSTEM PERFORMANCE
    HOLLANDS, KGT
    DANDREA, LJ
    MORRISON, ID
    SOLAR ENERGY, 1989, 42 (04) : 335 - 338
  • [10] Performance Analysis of Double Skin Air Handling Unit With Active Purification System