A new climate chamber for air-source and ground-source heat pump testing based on the Hardware-in-the Loop approach: Design and cross validation

被引:3
|
作者
Dongellini, Matteo [1 ]
Ballerini, Vincenzo [1 ]
Morini, Gian Luca [1 ]
Naldi, Claudia [1 ]
Pulvirenti, Beatrice [1 ]
di Schio, Eugenia Rossi [1 ]
Valdiserri, Paolo [1 ]
机构
[1] Alma Mater Studiorum Univ Bologna, Dept Ind Engn, Viale Risorgimento 2, I-40136 Bologna, Italy
来源
关键词
Climate chamber; Hardware-in-the-Loop; Heat pumps; Dynamic tests; Control strategy; CFD; SYSTEMS; PERFORMANCE;
D O I
10.1016/j.jobe.2022.105661
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The present paper describes a new test bench, designed for experimental tests on small-and medium-sized air-source and ground-source heat pumps, built at the University of Bologna (Italy). The test rig is based on the "Hardware-in-the-Loop" approach and is mainly composed of a test room (i.e. the climate chamber), in which the tested heat pump is placed, a borehole heat exchanger field for tests on ground-source units, the hydraulic loop and the building emulator. The test rig allows to test commercial and prototypal heat pumps under dynamic operating conditions, in order to reproduce the real behavior of a heat-pump based heating system and assess the heat pump effective energy performance. According to the Hardware-in-the-Loop approach, the hydraulic circuit of the facility is designed to reproduce exactly the time-dependent variations of the weather data during a series of representative days in a chosen site and the building thermal load given to the heat pump, calculated by a dynamic simulation software (i.e., the building emulator). In this paper, main components of the experimental facility are presented and the outcomes of a series of numerical simulations carried out with different software, such as Trnsys, Matlab-Simulink and STAR-CCM+, to define the system operative range and the effective behavior of the test bench under dynamic conditions are reported. Numerical models have been validated with experimental data, obtained from a trial test carried out on an air-source heat pump according to current technical standards. Comparison between numerical data and experimental results point out an excellent agreement and, for this reason, numerical models can be used to assess the optimal position of the tested heat pump within the chamber or to define the test bench operating conditions. The cross-validation methodology between experimental data and numerical results from different software, applied in this paper to a test bench for heat pumps, can be employed for the sizing of other test facilities.
引用
收藏
页数:17
相关论文
共 24 条
  • [1] A performance comparison between an air-source and a ground-source reversible heat pump
    de Swardt, CA
    Meyer, JP
    STROJNISKI VESTNIK-JOURNAL OF MECHANICAL ENGINEERING, 2001, 47 (08): : 519 - 526
  • [2] A performance comparison between an air-source and a ground-source reversible heat pump
    De Swardt, CA
    Meyer, JP
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2001, 25 (10) : 899 - 910
  • [3] A performance comparison between an air-source and a ground-source reversible heat pump
    de Swardt, CA
    Meyer, JP
    THERMAL SCIENCES 2000, 2000, : 561 - 568
  • [4] Energy Use and Greenhouse Gas Emissions of Air-Source Heat Pump and Innovative Ground-Source Air Heat Pump in a Cold Climate
    Mattinen, Maija K.
    Nissinen, Ari
    Hyysalo, Sampsa
    Juntunen, Jouni K.
    JOURNAL OF INDUSTRIAL ECOLOGY, 2015, 19 (01) : 61 - 70
  • [5] Techno-economic analysis on ground-source and air-source heat pump systems
    Chen, GM
    Li, YC
    Huang, YY
    Zhang, L
    CRYOGENICS AND REFRIGERATION - PROCEEDINGS OF ICCR'2003, 2003, : 691 - 694
  • [6] Power-hardware-in-the-loop validation of air-source heat pump for fast frequency response applications
    Song, Ruihao
    Mohapatra, Anurag
    Hamacher, Thomas
    Peric, Vedran S.
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 235
  • [7] A techno-economic comparison of a direct expansion ground-source and an air-source heat pump system in Canadian cold climates
    Hakkaki-Fard, Ali
    Eslami-Nejad, Parham
    Aidoun, Zine
    Ouzzane, Mohamed
    ENERGY, 2015, 87 : 49 - 59
  • [8] Modeling approach to design of a ground-source heat pump bridge deck heating system
    Chiasson, A
    Spitler, JD
    ADVANCES AND ISSUES IN SNOW-REMOVAL AND ICE-CONTROL TECHNOLOGY: MAINTENANCE, 2001, (1741): : 207 - 215
  • [9] Performance analysis of heat pump based on a new solar air-source heat pump heating system
    Liang, Caihua
    Zhang, Xiaosong
    Zhu, Xia
    Li, Xiuwei
    Journal of Southeast University (English Edition), 2010, 26 (02) : 227 - 231
  • [10] A 12-Step Method for Closed-Loop Ground-Source Heat-Pump Design
    Kavanaugh, Steve
    ASHRAE TRANSACTIONS 2008, VOL 114, PT 2, 2008, 114 : 328 - 337