CFD simulation study of flow equalisation plate model in single-phase immersion liquid cooling for servers

被引:5
|
作者
Ni, Daoxu [1 ]
Yu, Fan [1 ]
机构
[1] Univ Sci & Technol Beijing, Sch Energy & Environm Engn, Beijing 100083, Peoples R China
关键词
Flow equalisation plate; Temperature imbalance; Servers; FC-40; Immersion liquid cooling; Flow distribution; NATURAL-CONVECTION; DATA CENTERS; HEAT; AIR;
D O I
10.1016/j.tsep.2023.102268
中图分类号
O414.1 [热力学];
学科分类号
摘要
Immersion liquid cooling is progressively being adopted for server cooling applications within data centers. Uneven coolant distribution in liquid-cooled cabinets may cause large temperature difference between servers under some extreme conditions, prompted this study on a flow equalization plate structure. Firstly, the servers, the cabinet and the flow equalisation plate were modelled using Ansys Icepak software, and then the effects of holes radii, inlet layout configurations, and the number of holes on the flow distribution of the FC-40 coolant and the temperature control across servers was investigated. The results indicate that the smaller radii is beneficial in balancing the flowrate within the holes of the flow equalization plate by increasing the flow resistance, yielding a maximum temperature difference and a maximum temperature standard deviation of 2.1 degrees C and 0.8 degrees C at r = 7.5 mm. However, excessively small radii can lead to higher internal pressures and flow resistance. With larger hole radii, temperature control is significantly influenced by the inlet flowrate. As the flowrate increases, Delta T and Tsd also increase, reaching up to 3.8 degrees C and 1.3 degrees C at r = 12.5 mm, respectively. Larger hole radii result in smaller coolant flowrate, leading to lower convective heat transfer coefficient and higher server temperature. Locating inlets on one side creates large low-velocity vortex areas, disrupting server cooling, while center placement enhances thermal performance. When the number of holes is 18, the hole spacing increases, which leads to an increase in the flowrate in the holes and an increase in the convective heat transfer coefficient, which improves the thermal performance factor epsilon to 1.04.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] CFD Simulation of Single-Phase Flow in Plate Heat Exchangers
    O'Halloran, Steven
    Jokar, Amir
    ASHRAE: TRANSACTIONS 2011, VOL 117, PT 1, 2011, 117 : 147 - 155
  • [2] CFD SIMULATION-BASED COMPARATIVE STUDY OF FORCED CONVECTION SINGLE-PHASE LIQUID IMMERSION COOLING FOR A HIGH-POWERED SERVER
    Murthy, Prajwal
    Gupta, Gautam
    Herring, Joseph
    Lamotte-Dawaghreh, Jacob
    Sivaraju, Krishna Bhavana
    Bansode, Pratik
    Modi, Himanshu
    Agonafer, Dereje
    Mynampati, Poornima
    Sweeney, Mike
    PROCEEDINGS OF ASME 2022 INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, INTERPACK2022, 2022,
  • [3] Efficient jet-assisted single-phase immersion liquid cooling for high heat-flux servers
    Liu, Chendong
    Huang, Yongping
    Zhang, Chengbin
    APPLIED THERMAL ENGINEERING, 2025, 259
  • [4] Performance evaluation and optimization of data center servers using single-phase immersion cooling
    Wang, Huijuan
    Yuan, Xuejun
    Zhang, Kun
    Lang, Xujin
    Chen, Hua
    Yu, Huimin
    Li, Shengtao
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2024, 221
  • [5] Experimental study of the performance of liquid cooling tank used for single-phase immersion cooling data center
    Li, Xueqiang
    Guo, Shentong
    Sun, Haiwang
    Yin, Shen
    Liu, Shengchun
    Wang, Zhiming
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 63
  • [6] Performance Enhancement of Single-Phase Immersion Liquid-Cooled Data Center Servers
    Ge, Junlei
    Xia, Feifan
    Zhang, Chengbin
    Huang, Yongping
    JOURNAL OF THERMAL SCIENCE, 2024, 33 (05) : 1757 - 1772
  • [7] Advanced Single-phase Passive Immersion Cooling Solution with Natural Convection for Outdoor Edge Servers
    Guo, Liwen
    Wu, Jiahong
    Hsieh, I-Min
    Huang, Cheng-Hua
    Li, Bo
    Jao, Chiming
    Lin, Vinson
    Yuan, Robert
    Tan, Xianguang
    Fan, Xiaojin
    Wu, Zhenghui
    Sheng, Yong
    He, Yongzhan
    Zhang, Jiajun
    Zhang, Jun
    Chen, Carrie
    Xia, Yuyang
    Lv, Wenqing
    Wu, Min
    Du, Chris
    He, Candy
    Zhang, Jonas
    Ahuja, Nishi
    Qiao, Qing
    PROCEEDINGS OF THE TWENTIETH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM 2021), 2021, : 417 - 422
  • [8] Performance Enhancement of Single-Phase Immersion Liquid-Cooled Data Center Servers
    GE Junlei
    XIA Feifan
    ZHANG Chengbin
    HUANG Yongping
    JournalofThermalScience, 2024, 33 (05) : 1757 - 1772
  • [9] Comprehensive experimental study of battery thermal management using single-phase liquid immersion cooling
    Chandrasekaran, M.
    Jithin, K., V
    Soundarya, T.
    Rajesh, P. K.
    JOURNAL OF ENERGY STORAGE, 2025, 111
  • [10] Optimization and comprehensive evaluation of liquid cooling tank for single-phase immersion cooling data center
    Liu, Shengchun
    Xu, Zhiming
    Wang, Zhiming
    Li, Xueqiang
    Sun, Haiwang
    Zhang, Xinyu
    Zhang, Haoran
    APPLIED THERMAL ENGINEERING, 2024, 245