Sensitivity analysis of avoidable and unavoidable exergy destructions in a parallel double-effect LiBr-water absorption cooling system

被引:7
|
作者
Zendehnam, Arman [1 ]
Pourfayaz, Fathollah [1 ]
机构
[1] Univ Tehran, Fac New Sci & Technol, Dept Renewable Energies & Environm, Tehran, Iran
关键词
advanced exergy analysis; avoidable/unavoidable exergy destruction; double effect absorption refrigeration; endogenous/exogenous exergy destruction; LiBr-water; sensitivity analysis; REFRIGERATION SYSTEM; RANKINE-CYCLE; ENERGY; OPTIMIZATION; CHILLER; PERFORMANCE; RECOVERY; DRIVEN; POWER;
D O I
10.1002/ese3.1344
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A parametric study has been carried out based on advanced exergy assessment for a parallel double-effect LiBr-water absorption chiller. The advanced exergy method provides the real potential of the equipment for improvement in the system by recognizing the avoidable irreversibilities. The sensitivity analysis of various parts of the exergy destruction (endogenous avoidable, endogenous unavoidable, exogenous avoidable, and exogenous unavoidable) in system components and the overall performance (coefficient of performance, exergy efficiency, and modified exergy efficiency) of the system has been done to identify the actual potential of different components of the system to improve the overall performance of the system relative to operational parameters. Operational parameters include the heat source temperature, heat sink temperature, and the difference between the absorption and condensation temperature. The results showed that by modifying and improving the performance of components, 18.5% of the total exergy destruction of the system could be reduced. The modified exergy efficiency reduces sharply (nearly 40%) with the rising heat sink temperature. The endogenous exergy destruction increases in all system components except the condenser and evaporator by the heat source temperature increase. With the increase in the heat sink temperature, the avoidable part of the total exergy destruction in the system increases due to the significant rise in the avoidable exogenous exergy destruction in the components, and the unavoidable endogenous exergy destruction decreases (more than 200%) in the absorber. Increasing the condensation temperature reduces the unavoidable endogenous exergy destruction in the components except for the low-temperature heat exchanger.
引用
收藏
页码:527 / 546
页数:20
相关论文
共 50 条
  • [1] DAILY EXERGY ASSESSMENT OF LIBR-WATER ABSORPTION CHILLER USED FOR SOLAR COOLING
    Onan, Cenk
    Ozkan, Derya B.
    ES2010: PROCEEDINGS OF ASME 4TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, VOL 1, 2010, : 869 - 878
  • [2] Irreversibility analysis of double effect LiBr-water vapor absorption chiller
    Imran, K. Muhammad
    Journal of Engineering Science and Technology Review, 2013, 6 (05) : 115 - 122
  • [3] Simulation of solar cooling system based on variable effect LiBr-water absorption chiller
    Xu, Z. Y.
    Wang, R. Z.
    RENEWABLE ENERGY, 2017, 113 : 907 - 914
  • [4] Performance comparison of solar-driven single and double-effect LiBr-water vapor absorption system based cold storage
    De, Ramen Kanti
    Ganguly, Aritra
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2020, 17
  • [5] Dynamic simulation of a double-effect parallel-flow LiBr/water absorption chiller
    Lin, P.
    Wang, R. Z.
    Wu, J. Y.
    CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 604 - 608
  • [6] Simulation of a double-effect LiBr/H2O absorption cooling system
    Wardono, Bagas
    Nelson, Ron M.
    ASHRAE Journal, 1996, 38 (10) : 32 - 38
  • [7] Exergy and Exergoenvironmental Analysis of a CCHP System Based on a Parallel Flow Double-Effect Absorption Chiller
    Mousafarash, Ali
    INTERNATIONAL JOURNAL OF CHEMICAL ENGINEERING, 2016, 2016
  • [8] Thermodynamic analysis and optimisation of double effect absorption type combined power and cooling cycle using LiBr-water as working fluid
    Patil, Rahul S.
    Bhagwat, Sunil S.
    INTERNATIONAL JOURNAL OF EXERGY, 2021, 34 (02) : 159 - 178
  • [9] ENERGY AND EXERGY ANALYSIS OF A DOUBLE EFFECT PARALLEL FLOW LIBR/H2O ABSORPTION REFRIGERATION SYSTEM
    Arora, Akhilesh
    Dixit, Manoj
    Kaushik, S. C.
    JOURNAL OF THERMAL ENGINEERING, 2016, 2 (01): : 541 - 549
  • [10] Exergy analysis of a parallel double-effect organosilicon monomer distillation scheme
    Sun, Jinsheng
    Wang, Fan
    Ma, Tingting
    Gao, Hong
    Liu, Yanzhen
    Cai, Fang
    ENERGY, 2012, 47 (01) : 498 - 504