Novel approach to typical air-conditioning behavior pattern extraction based on large-scale VRF system online monitoring data

被引:14
|
作者
Wu, Yi [1 ]
Zhou, Xin [2 ]
Qian, Mingyang [1 ]
Jin, Yuan [1 ]
Sun, Hongsan [1 ]
Yan, Da [1 ]
机构
[1] Tsinghua Univ, Sch Architecture, Bldg Energy Res Ctr, Beijing 100084, Peoples R China
[2] Southeast Univ, Sch Architecture, Nanjing 210096, Jiangsu, Peoples R China
来源
基金
中国国家自然科学基金;
关键词
Occupant air-conditioning (AC) behavior; Bayesian calibration; Big data; Data mining; OCCUPANT BEHAVIOR; BAYESIAN CALIBRATION; MODEL; PERFORMANCE; PROBABILITY; SIMULATIONS; STATE;
D O I
10.1016/j.jobe.2023.106243
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The diversity of occupant air-conditioning (AC) behavior in buildings leads to significant discrepancies in building energy consumption. Thus, establishing models that reflect diverse realistic occupant AC behavior is crucial for the building performance simulations (BPS). Owing to the lack of large-scale samples, it is difficult to extract typical AC behavior patterns from existing studies. With advances in IT methods for data collection, large-scale on-site air-conditioning (AC) operation data of variable refrigerant flow (VRF) systems have become available. Therefore, based on the Big Data of 1200 indoor units (IDUs) of VRF systems, a novel method was proposed herein to establish realistic AC behavior models and extract typical patterns. The overall framework included three steps: data collection and preprocessing, large-scale occupant AC behavior model establishment, and typical behavior pattern extraction and evaluation. First, data preprocessing approaches were implemented to address data issues. Subsequently, based on Big Data, Bayesian parameter calibration was proposed to construct large-scale occupant AC behavior models. Afterwards, using the large-scale calibrated AC behavior models, the cooling demands of the population were simulated, and k-means clustering analysis was adopted to categorize the AC behavior into five groups representing different cooling demand levels and a typical model reflecting the group feature was selected. In the model validation, a hypothesis-based test was applied to confirm the validity of extracted typical patterns in reflecting the real distribution of district cooling demands. In the results, this study identified two occupancy patterns, i.e. "Daily occupied mode" (DOM) and "Night occupied mode" (NOM), and based on two occupancy types, five typical AC behavior patterns were extracted separately. From the typical patterns, it could be noticed that 90% of occupants had relatively low cooling demand less than 40 kWh/m2 during the cooling season. Moreover, comparing to the performance of fixed AC schedule model in district cooling demand evaluation, the extracted typical AC behavior patterns improved the accuracy up to 30.4% when calculating the bias between average modelled cooling demand and measured data. Additionally, the typical AC behavior models put forward in this study can be further integrated in BPS tools, which is promising for the simulation of cooling demand at building or district scale, and realizing AC technology evaluation in future engineering projects.
引用
收藏
页数:15
相关论文
共 37 条
  • [1] Fault diagnosis of VRF air-conditioning system based on improved Gaussian mixture model with PCA approach
    Guo, Yabin
    Chen, Huanxin
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 118 : 1 - 11
  • [2] An adaptive approach for online monitoring of large-scale data streams
    Cao, Shuchen
    Zhang, Ruizhi
    IISE TRANSACTIONS, 2023, 57 (02) : 119 - 130
  • [3] Energy Consumption and Analysis of Air-conditioning System of Large-scale Public Buildings in Xi'an
    Pan, Wenyan
    Yang, Liu
    Zhang, Zhuhui
    ARCHITECTURE AND BUILDING MATERIALS, PTS 1 AND 2, 2011, 99-100 : 388 - +
  • [4] Correlation analysis of occupancy and air-conditioning behavior of different offices based on a large-scale survey in HSCW zone of China
    Liu, Xiangyu
    Li, Tao
    Ma, Jiangqiaoyu
    Wu, Pinguo
    Li, Yang
    Chen, Min
    Li, Guannan
    Mao, Qianjun
    Energy, 2024, 311
  • [5] Energy Consumption Comparison of Large-scale Air-conditioning System With Different Temperature of Chilled-Water
    Jiang, Xiaojiang
    Xiao, Jianren
    Li, Xingyou
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 2100 - 2104
  • [6] Research on the missing value methods for large-scale online air quality monitoring data
    Zhang, Bo
    Song, Guo-Jun
    Zhongguo Huanjing Kexue/China Environmental Science, 2022, 42 (05): : 2078 - 2087
  • [7] Application of the Water Loop Variable Refrigerant Flow Air-Conditioning System in Large-Scale Buildings in Cold Climate
    Sun, Tingting
    Ni, Long
    Yao, Yang
    Ma, Zuiliang
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 475 - 482
  • [8] A Data-Centric Storage Approach for Monitoring System of Large-Scale Smart Grid
    Wang, Yan
    Deng, Qingxu
    Liu, Wei
    Song, Baoyan
    2012 INTERNATIONAL CONFERENCE ON WIRELESS COMMUNICATIONS, NETWORKING AND MOBILE COMPUTING (WICOM), 2012,
  • [9] Detecting and monitoring game bots based on large-scale user-behavior log data analysis in multiplayer online games
    Choi, YeonJun
    Chang, SungJune
    Kim, YongJun
    Lee, HunJoo
    Son, WookHo
    Jin, SeongIl
    JOURNAL OF SUPERCOMPUTING, 2016, 72 (09): : 3572 - 3587
  • [10] Detecting and monitoring game bots based on large-scale user-behavior log data analysis in multiplayer online games
    YeonJun Choi
    SungJune Chang
    YongJun Kim
    HunJoo Lee
    WookHo Son
    SeongIl Jin
    The Journal of Supercomputing, 2016, 72 : 3572 - 3587