Mathematical Models of the Phase Voltages of High-, Medium- and Low-Voltage Busbars in a Substation during a Phase-to-Ground Fault on High-Voltage Busbars

被引:0
|
作者
Toader, Dumitru [1 ]
Vintan, Maria [2 ]
机构
[1] Politehn Univ, Dept Fundamental Phys Engineers, Timisoara 300006, Romania
[2] Lucian Blaga Univ, Dept Comp Sci & Elect Engn, Sibiu 550024, Romania
关键词
mathematical models; three-phase systems; phase-to-ground fault; phase voltages; protection setting; SHORT-CIRCUIT CURRENT; SENSITIVITY; SAGS;
D O I
10.3390/math11133032
中图分类号
O1 [数学];
学科分类号
0701 ; 070101 ;
摘要
The electrical energy supply of industrial equipment is provided by electrical power stations with high- (HT), medium- (MV) and low-voltage (LV) busbars. Consumers are connected to either MV or LV busbars. In this paper, a real power station was considered, through which the gasoline extraction from the well gas installation is powered. Electric consumers (electric motors) supplied by a MV busbar have active power of 13.54 MW, and those fed by a LV busbar have active power of 6.4 MW. Since electrical consumers operate in explosive environments, the design and operating conditions are more severe than in the case of electrical installations operating in non-explosive environments. The case of a single phase-to-ground fault occurring on the HV transmission lines feeding the power station has been analysed. First, the mathematical models for the calculation of the phase voltages, the dissymmetry and asymmetry coefficients, the reduction coefficient of the plus sequence component, and the effective values of the phase voltages were established. The influence of the source impedance (the equivalent impedance of the HV transmission lines) and of the neutral point configuration of the HV/MV medium-voltage transformer on the calculated quantities was analysed. Then, the results obtained using the established mathematical models were compared with those obtained experimentally by provoking a single-phase-to-ground fault near the HV busbars of the real power station. This study has shown that the de-symmetrisation of the phase voltages of the MV and LV busbars is lower when using the Y/& UDelta; connection for the HV/MV transformer. As a result, it is recommended the Y/& UDelta; connection be used for this transformer, instead of the Y-0/& UDelta; connection.
引用
收藏
页数:30
相关论文
共 50 条
  • [1] Industrial applications of high-, medium- and low-voltage arc modelling
    Chevrier, P
    Barrault, M
    Fievet, C
    Maftoul, J
    Fremillon, JM
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1997, 30 (09) : 1346 - 1355
  • [2] DESIGN OF MEDIUM VOLTAGE, HIGH FAULT CURRENT BUSBARS FOR SWITCHBOARDS AND RISING MAINS.
    Univ of Auckland, Auckland, NZ, Univ of Auckland, Auckland, NZ
    [J]. New Zealand Journal of Technology, 1986, 2 (01): : 43 - 56
  • [3] HIGH-VOLTAGE MEDIUM(LOW)-VOLTAGE SUBSTATION EARTHING SYSTEMS
    NAHMAN, J
    JELOVAC, D
    [J]. IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1987, 134 (01) : 75 - 80
  • [4] Examination of Low-Voltage High-Current Busbars with Computerized Model.
    Bela, Torok
    [J]. Elektrotechnika Budapest, 1982, 75 (12): : 451 - 456
  • [5] Ground-Fault Recognition in Low-Voltage Ships Based on Variation Analysis of Phase-to-Ground Voltage and Neutral-Point Voltage
    Ryu, Ki-Tak
    Lee, Yun-Hyung
    [J]. IEEE ACCESS, 2024, 12 : 123166 - 123176
  • [6] A Combined High-, Medium-, and Low-Voltage Test System for Stability Studies with DERs
    Escobar, Francisco
    Garcia, Jorge
    Viquez, Juan M.
    Valverde, Gustavo
    Aristidou, Petros
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2020, 189
  • [7] FAULT INDUCED VOLTAGES ON METALLIC FENCING LOCATED IN THE VICINITY OF A HIGH-VOLTAGE SUBSTATION
    ROGERS, EJ
    HALL, RH
    WHITE, JF
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (03): : 746 - 750
  • [8] Application Of Wavelet Transform For Phase-To-Ground Fault Protection In Medium Voltage Electrical Networks
    Syvokobylenko, V.F.
    Lysenko, V.A.
    [J]. Technical Electrodynamics, 2021, 2021 (04): : 55 - 62
  • [9] A grid operation model: Resource demand for an adequate incident management in high-, medium-, and low-voltage grids
    Guarisco, Michael
    Friedrich, Catharina
    Balderer, Christian
    Laumanns, Marco
    Zdrallek, Markus
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2009, 31 (09) : 504 - 511
  • [10] URBAN EXPOSURE TO ELF MAGNETIC FIELD DUE TO HIGH-, MEDIUM- AND LOW-VOLTAGE ELECTRICITY SUPPLY NETWORKS
    Bottura, V.
    Borlino, M. Cappio
    Carta, N.
    Cerise, L.
    Imperial, E.
    [J]. RADIATION PROTECTION DOSIMETRY, 2009, 137 (3-4) : 214 - 217