Performance analysis of a novel multi-heat sinks heat pump based on two-stage ejector-compression cycle

被引:5
|
作者
Shifang, Huang [1 ]
Zhou, Lu [1 ]
Liu, Jian [1 ,2 ]
Lin, Zhang [3 ]
Zhou, Qiang [4 ]
Zhang, Xiaosong [1 ,2 ]
机构
[1] Southeast Univ, Dept Energy & Environm, Nanjing, Peoples R China
[2] Minist Educ, Engn Res Ctr Bldg Equipment Energy & Environm, Nanjing, Peoples R China
[3] City Univ Hong Kong, Div Bldg Sci & Technol, Hong Kong, Peoples R China
[4] State Grid Jiangsu Integrated Energy Serv Co LTD, Nanjing, Peoples R China
关键词
Multi-heat sinks; Ejector; COPh; Energy-saving; Heat pump; Two-stage compression cycle; SYSTEM;
D O I
10.1016/j.tsep.2022.101544
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study proposes a multi-heat sinks heat pump based on a two-stage ejector-compression cycle. The system produces two kinds of heat sink, e.g., the hot water of high temperature ranging from 60 to 90 degrees C, which shows high applied potential in hot water production or wall radiator heating, and of low temperature ranging from 30 to 40 degrees C, which can be applied in space heating. A validated theoretical model was constructed to compare and analyze the performance between the two-stage compression two heat sinks heat pump cycle (TSC) and ejector two-stage compression multi-heat sinks heat pump cycle (ETSC) under various operated conditions. The sensitive analysis of four operative parameters, evaporation temperature (T1), condensation temperature (T4, T7), and load ratio (LR), on system performance has been conducted, which provides the direction of system performance optimization. The results show that the heating coefficient of performance (COPh), volumetric heating capacity (qv) and entrainment ratio (mu) are more sensitive to the variation of T1. The exergy loss per kilowatt heating capacity is more sensitive to T4 variation. Besides, more air source energy is absorbed in the evaporator by the ejector, and then ETSC performance outperforms the TSC, especially under the high demand of high-temperature heat sink conditions. Lastly, the ecofriendly refrigerants R290 and R1234yf show good potential as the alter-native for the R134a in the ETSC. The results hope to promote the further improvement and application of two stage compression cycle.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Exergy analysis for quasi two-stage compression heat pump system coupled with ejector
    Xu Shuxue
    Ma Guoyuan
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2011, 35 (04) : 700 - 705
  • [2] A novel dual-temperature ejector-compression heat pump cycle-exergetic and economic analyses
    Liu, Jian
    Lin, Zhang
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 126 : 155 - 167
  • [3] The Performance Analysis of Two-Stage Compression Refrigeration Heat Pump Cycle with heating and cooling simultaneously
    Liu, X.
    Jiang, Q. Q.
    Liu, K.
    Qi, L.
    Xing, X. Y.
    [J]. SUSTAINABLE DEVELOPMENT OF URBAN ENVIRONMENT AND BUILDING MATERIAL, PTS 1-4, 2012, 374-377 : 655 - 662
  • [4] Performance analysis of a two-stage vapor compression heat pump based on intercooling effect
    Jin, Xu
    Zhang, Jiapeng
    Liu, Zhongyan
    Hong, Wenpeng
    Sha, Shuai
    Qiu, Zheng
    Wu, Zhe
    Su, Wei
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2023, 51
  • [5] AN ALTERNATE SOURCE OF COOLING - THE EJECTOR-COMPRESSION HEAT-PUMP
    HAMNER, RM
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1980, 22 (07): : 62 - 66
  • [6] Separated condensation and cascaded evaporation - A novel method to improve ejector-compression heat pump cycle using zeotropic mixtures
    Liu, Jian
    Shi, b Jihao
    Zhang, Tao
    Cheng, Jianhong
    Zhang, Xiaosong
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2024, 304
  • [7] Theoretical analysis on a new direct expansion solar assisted ejector-compression heat pump cycle for water heater
    Chen, Jiaheng
    Yu, Jianlin
    [J]. SOLAR ENERGY, 2017, 142 : 299 - 307
  • [8] Performance analysis of a dual temperature heat pump based on ejector-vapor compression cycle
    Liu, Jian
    Lu, Yalin
    Tian, Xue
    Niu, Jianlei
    Lin, Zhang
    [J]. ENERGY AND BUILDINGS, 2021, 248
  • [9] Two-stage high temperature hybrid heat pump with parallel heat sinks
    Ellingsen, Oyvind Mortveit
    Kvalsvik, Karoline Husevag
    Bantle, Michael
    [J]. 13TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS: NATURAL REFRIGERANT SOLUTIONS FOR WARM CLIMATE COUNTRIES, 2018, : 773 - 781
  • [10] 4E analyses of novel dual-heat source/sink ejector-compression heat pump system
    Liu, Jian
    Tian, Xue
    Lin, Zhang
    [J]. BUILDING AND ENVIRONMENT, 2021, 196