Experimental study and numerical analysis of thermal hazard for fire accident in converter transformers

被引:5
|
作者
Zhang, Shaohua [1 ]
Zhao, Jinlong [1 ]
Zhang, Qingyuan [1 ]
Zhang, Jianping [2 ]
Jiang, Huiling [3 ]
机构
[1] China Univ Min & Technol Beijing, Sch Emergency Management & Safety Engn, Beijing, Peoples R China
[2] Ulster Univ, Belfast Sch Architecture & Built Environm, Fire SERT, Belfast BT37 0QB, North Ireland
[3] Univ Sci & Technol Beijing, Sch Civil & Resources Engn, Beijing, Peoples R China
关键词
Converter transformer; Fire hazard; CFD; Fire characteristics; Thermal hazard; POOL FIRE;
D O I
10.1016/j.tsep.2023.102108
中图分类号
O414.1 [热力学];
学科分类号
摘要
Converter transformers are widely used in high voltage direct current (HVDC) transmission systems. Due to its large storage capacity and relatively high failure probability of the insulation, pool fires are a common type of accidents for this type of transformers, which could pose a significant threat to the safety of personnels and the integrity of nearby transformers. During normal operation, the temperature of the transformer oil can vary between 80 and 90 degrees C. It is known that the oil temperature can have a significant impact on its burning characteristics. However, most of previous simulations of transformer fires utilized the material properties of transform oil obtained at ambient temperature to determine the heat release rate (HRR). In this study, experimental data (D = 0.2-1.0 m) at an initial oil temperature of 85 degrees C were employed to determine the correlation between HRR and burner diameter, which was subsequently used to validate the numerical model. 14 typical fire scenarios were examined to understand the accident development process of transformer pool fires. The results showed that a merged flame was observed at the inner side for the case when the fire occurred both on the oil tank upper surface and in the oil storage pit. The radiation impact on (and thus the risk of failure of) key transformer components was found to vary considerably across the different fire scenarios. The radiative heat flux at the outlet of the enclosure where the fire is located was found to exceed 5 kW/m2 and the recommended safety distance for firefighting can reach 6.6 m. It was also found that the maximum heat radiative flux received by the high voltage bushing of an adjacent transformer can reach 46.2 kW/m2 in the worst-case scenario, with a probability of escalation to the adjacent transformer approximately 3.50x10- 4. Three distinctive areas (safety area, risk area, and dangerous area) were identified to determine firefighting positions and strategies for transformer substation fires. The present results could not only enhance the understanding of the accidental development of converter transformer fires but also provide valuable guidance in firefighting in various fire accident scenarios.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] Experimental study and numerical simulation for a storehouse fire accident
    Yang, Peizhong
    Tan, Xun
    Xin, Wang
    BUILDING AND ENVIRONMENT, 2011, 46 (07) : 1445 - 1459
  • [2] Experimental and numerical investigation of fire hazard of vertical greenery systems
    Karunaratne, Tharindu
    Han, Shousou
    Lau, Denvid
    Chow, Cheuk Lun
    JOURNAL OF BUILDING ENGINEERING, 2024, 95
  • [3] Experimental Study of Induction Cooker Fire Hazard
    Wong, Arthur K. K.
    Fong, N. K.
    2012 INTERNATIONAL CONFERENCE ON PERFORMANCE-BASED FIRE AND FIRE PROTECTION ENGINEERING, 2013, 52 : 13 - 22
  • [4] Thermal Analysis of a 9975 Package in a Facility Fire Accident
    Gupta, Narendra K.
    PROCEEDINGS OF THE ASME PRESSURE VESSELS AND PIPING CONFERENCE (PVP-2011), VOL 7, 2012, : 347 - 353
  • [5] Review of Numerical Calculation Methods for Electro-thermal Coupling of Converter Transformers
    Li, Qingquan
    Zhu, Ran
    Li, Shuqi
    Ren, Fuqiang
    Kang, Zhaoyang
    Liu, Hongshun
    Li, Ze
    Sun, Youliang
    Gaodianya Jishu/High Voltage Engineering, 2024, 50 (10): : 4734 - 4748
  • [6] Thermal hazard analysis of ALA nightclub fire debris
    Yeh, Chi-Tang
    Shih, Shun-Jen
    Chi, Jen-Hao
    Shu, Chi-Min
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2014, 117 (03) : 1065 - 1071
  • [7] Thermal hazard analysis of ALA nightclub fire debris
    Chi-Tang Yeh
    Shun-Jen Shih
    Jen-Hao Chi
    Chi-Min Shu
    Journal of Thermal Analysis and Calorimetry, 2014, 117 : 1065 - 1071
  • [8] The Need for Experimental and Numerical Analyses of Thermal Ageing in Power Transformers
    Fernandez, Inmaculada
    ENERGIES, 2022, 15 (17)
  • [9] Experimental study on fire hazard of xylon floors in building
    Shu, ZJ
    Xue, G
    Ma, Z
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL V, PTS A AND B, 2005, 5 : 1057 - 1059
  • [10] Experimental and numerical thermo-mechanical analysis of the influence of thermoplastic slabs installation on the assessment of their fire hazard
    Vincent, Chloe
    Corn, Stephane
    Longuet, Claire
    Aprin, Laurent
    Rambaud, Guillaume
    Ferry, Laurent
    FIRE SAFETY JOURNAL, 2019, 108