Characteristics of outdoor pollutants intrusion and ventilation control in sentry buildings with normal openings

被引:4
|
作者
Liang, Linfeng [1 ]
Yin, Haiguo [1 ,2 ,3 ]
Zhang, Da [1 ]
Han, Yuekun [1 ]
Li, Yanyan [1 ]
Zhang, Jingying [1 ]
Zhang, Yongshou [2 ,3 ]
Ma, Zhenjun [4 ]
Li, Angui [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, Xian 710055, Shaanxi, Peoples R China
[2] Qinghai Bldg & Mat Res Co Ltd, Xining 810008, Qinghai, Peoples R China
[3] Qinghai Prov Key Lab Plateau Green Bldg & Ecocomm, Xining 810008, Qinghai, Peoples R China
[4] Univ Wollongong, Sustainable Bldg Res Ctr, Wollongong, NSW 2522, Australia
关键词
sentry buildings; pollutants intrusion; indoor air quality; wind field; double attached ventilation; computational fluid dynamics (CFD); AIR CURTAIN; STRATUM VENTILATION; NATURAL VENTILATION; CFD SIMULATION; WIND-TUNNEL; PARTICLE DISPERSION; CROSS-VENTILATION; FLOW; INDOOR; PERFORMANCE;
D O I
10.1007/s12273-022-0946-4
中图分类号
O414.1 [热力学];
学科分类号
摘要
Sentry buildings have windows that are often open to facilitate communication between personnel. It also provides the possibility for the intrusion of pollutants such as vehicle exhaust emissions. To prevent the intrusion of outdoor pollutants and create an excellent indoor environment, internal circulation with double-attached ventilation (IC-DAV) and external circulation with double-attached ventilation (EC-DAV) are proposed for such buildings, and the isolation effect of two attached ventilation modes on pollutants is compared with that of natural ventilation. A computational fluid dynamics (CFD) method was used to simulate the transportation process and indoor distribution of outdoor pollutants intruding into sentry buildings from the regular openings under different outdoor wind directions, wind velocities, and states of the doors and ventilation modes. The results indicate that the leeward airflow of the three wind directions caused the largest pollutants to invade the room. The amount of pollutants intrusion increased with increasing wind velocity. When the leeward airflow and the windward airflow blow through the building, opening the door increased the amount of pollutants intruding into the room by 3.34 times and 8.85 times, respectively, compared with closing the door. However, the IC-DAV can isolate 81.7% of the pollutants while the EC-DAV can isolate 99.92% of the pollutants as compared with natural ventilation. Applying double attached ventilation mode in buildings can effectively prevent the intrusion of outdoor pollutants into the room, reduce the harm of outdoor pollutants to the health of indoor personnel, and provide a new idea for buildings to improve the indoor air quality.
引用
收藏
页码:393 / 411
页数:19
相关论文
共 5 条
  • [1] Characteristics of outdoor pollutants intrusion and ventilation control in sentry buildings with normal openings
    Linfeng Liang
    Haiguo Yin
    Da Zhang
    Yuekun Han
    Yanyan Li
    Jingying Zhang
    Yongshou Zhang
    Zhenjun Ma
    Angui Li
    [J]. Building Simulation, 2023, 16 : 393 - 411
  • [2] Modelling the influence of outdoor pollutants on the indoor air quality in buildings with airflow rate control
    Kraenzmer, M
    [J]. 17TH AIVC CONFERENCE - OPTIMUM VENTILATION AND AIR FLOW CONTROL IN BUILDING, PROCEEDINGS, VOLS 1 AND 2, 1996, : 135 - 143
  • [3] Fault-tolerant control for outdoor ventilation air flow rate in buildings based on neural network
    Wang, SW
    Chen, YM
    [J]. BUILDING AND ENVIRONMENT, 2002, 37 (07) : 691 - 704
  • [4] Monte Carlo simulation to control indoor pollutants from indoor and outdoor sources for residential buildings in Tianjin, China
    Dai, Xilei
    Liu, Junjie
    Zhang, Xin
    [J]. BUILDING AND ENVIRONMENT, 2019, 165
  • [5] Examination of buoyancy driven ventilation design using the characteristics of opening ratio of natural ventilation opening: Study on the performance evaluation of natural ventilation control in office buildings (Part 3)
    Shimonosono, Kei
    Kohri, Kimiko
    Ishino, Hisaya
    [J]. Journal of Environmental Engineering (Japan), 2021, 86 (784): : 608 - 618