Dynamic Energy Analysis of Different Heat Pump Heating Systems Exploiting Renewable Energy Sources

被引:6
|
作者
Kitsopoulou, Angeliki [1 ]
Zacharis, Antonis [1 ]
Ziozas, Nikolaos [1 ]
Bellos, Evangelos [1 ]
Iliadis, Petros [1 ]
Lampropoulos, Ioannis [1 ]
Chatzigeorgiou, Eleni [1 ]
Angelakoglou, Komninos [1 ]
Nikolopoulos, Nikolaos [1 ]
机构
[1] Ctr Res & Technol Hellas CERTH, Chem Proc & Energy Resources Inst CPERI, Egialeias 52, Maroussi 15125, Greece
关键词
solar-driven heat pump; dual-source heat pump; geothermal field; dynamic analysis; Modelica; PERFORMANCE ANALYSIS; HOT-WATER; SOLAR; SIMULATION; BUILDINGS; CONSUMPTION; STORAGE;
D O I
10.3390/su151411054
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Renewable energy source-fed heat pumps (HPs) may perform up to very high-efficiency standards, offering a promising tool in the wider residential heat decarbonization effort. In this context, this paper investigates different heating configurations utilizing various renewable thermal sources in conjunction with an HP-based system in order to determine the optimal configuration in terms of efficiency, using an existing, fully functioning residential building in Zaragoza, Spain, as our case study, comprising 40 dwellings. Four different HP configurations are investigated:, (i) an air-source system, (ii) a ground-source system, (iii) a dual-source system with solar thermal collectors, and (iv) a triple-source system based on solar, geothermal, and ambient sources. For the purpose of such investigation, detailed dynamic energy simulations are conducted through the use of the INTEMA.building tool (developed in Modelica), applying a multi-objective optimization process that aims at minimizing both the annual electricity consumption and the net present cost. It is demonstrated that the renewable thermally driven HPs are more efficient than the conventional, air-source ones, with the seasonal coefficient of performance increasing by 9.98% (ground source), 4.57% (dual source), and 17.40% (triple source), compared to the air-source heat pump system. Finally, it is revealed (via integrated techno-economic analyses) that the most effective and economical design is the dual source system, while the most expensive is the ground-source configuration. These findings can guide the ongoing design efforts on green residential heat solutions at both research and commercial implementation level.
引用
收藏
页数:36
相关论文
共 50 条
  • [1] Energy and economic analysis of different heat pump systems for space heating
    Busato, Filippo
    Lazzarin, Renato M.
    Noro, Marco
    [J]. INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2012, 7 (02) : 104 - 112
  • [2] Renewable energy sources: analysis of two different alternatives of the heat pumps
    Stefanco, M.
    Kosicanova, D.
    [J]. ADVANCES AND TRENDS IN ENGINEERING SCIENCES AND TECHNOLOGIES, 2016, : 413 - 418
  • [3] Dynamic Decision Making in Energy Systems with Storage and Renewable Energy Sources
    Meisel, Stephan
    Powell, Warren B.
    [J]. ADVANCES IN ENERGY SYSTEM OPTIMIZATION, 2017, : 87 - 101
  • [5] An energy consumption analysis of surface water heat pump systems in heating season
    Liu, TT
    Peng, JG
    Zhang, GQ
    Chen, X
    [J]. BUILT ENVIRONMENT AND PUBLIC HEALTH, PROCEEDINGS, 2004, : 518 - 524
  • [6] Comparisons between energy carriers' productions for exploiting renewable energy sources
    Trop, P.
    Goricanec, D.
    [J]. ENERGY, 2016, 108 : 155 - 161
  • [7] Evaluation of hybrid heating systems with a combination of fossil and renewable energy sources
    Borodinecs, Anatolijs
    Bogdanovics, Raimonds
    Prozuments, Aleksejs
    Tihana, Jelena
    Gaujena, Baiba
    [J]. SBE 19 - EMERGING CONCEPTS FOR SUSTAINABLE BUILT ENVIRONMENT, 2019, 297
  • [8] Optimisation of heating system with renewable energy sources
    Nikulshin, V
    von Zedtwitz, V
    [J]. Proceedings of ECOS 2005, Vols 1-3: SHAPING OUR FUTURE ENERGY SYSTEMS, 2005, : 1549 - 1556
  • [9] Comparative Thermo-Energetic Analysis of the District Heating Systems that Harness Renewable Energy Sources
    Soimosan, Teodora-Melania
    Felseghi, Raluca-Andreea
    [J]. 10TH INTERNATIONAL CONFERENCE INTERDISCIPLINARITY IN ENGINEERING, INTER-ENG 2016, 2017, 181 : 754 - 761
  • [10] Criteria for use of groundwater as renewable energy source in geothermal heat pump systems for building heating/cooling purposes
    Milenic, Dejan
    Vasiljevic, Petar
    Vranjes, Ana
    [J]. ENERGY AND BUILDINGS, 2010, 42 (05) : 649 - 657