Important safety considerations for arrangement of flammable storage tanks: Thermal radiation effects with meteorological conditions

被引:0
|
作者
Lee, Sung-Kyu [1 ]
Lim, Jae-Yong [1 ,2 ]
机构
[1] Seoul Natl Univ Sci & Technol, Dept Safety Engn, Seoul, South Korea
[2] Seoul Natl Univ Sci & Technol, Dept Safety Engn, Seoul 01811, South Korea
基金
新加坡国家研究基金会;
关键词
domino effect; flammable liquid storage tanks; layout optimization; meteorological conditions; separation distance; thermal radiation; DOMINO EFFECT ANALYSIS; LAYOUT OPTIMIZATION; FIRE; UNCERTAINTY;
D O I
10.1002/prs.12510
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
We examine the effects of thermal radiation on the meteorological conditions and layout of flammable liquid storage tanks. Currently, the separation distances between the tanks are dictated by regulations to prevent the domino effect of fire accidents. Although thermal radiation leads to the domino effect, it is questionable whether thermal radiation is considered in the current Korean regulations. In this study, three cases-one based on a regulation and two others associated with meteorological conditions-are considered, for which the radiation effects and tank layouts are calculated. A software program and an optimization algorithm, namely ALOHA and sequential least-squares programming, respectively, are employed for hazard analysis and optimization, respectively. The results indicate that the current regulation is appropriate under normal meteorological conditions but may not ensure prevention of the domino effect under the worst conditions.
引用
收藏
页码:752 / 762
页数:11
相关论文
共 50 条