Extended Characterization of an Optical Sag Sensor for High-Temperature Low-Sag Lines

被引:3
|
作者
Singh, Himanshi [1 ,2 ]
Fusiek, Grzegorz [1 ]
Niewczas, Pawel [1 ]
机构
[1] Univ Strathclyde, Dept Elect & Elect Engn, Glasgow G1 1XQ, Scotland
[2] Natl Phys Lab, London TW11 0LW, England
基金
英国工程与自然科学研究理事会;
关键词
Sensor phenomena; fiber Bragg gratings (FBGs); high-temperature low-sag (HTLS) conductors; optical sag sensor; power grids;
D O I
10.1109/LSENS.2023.3300810
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This letter reports on the extended characterization of an optical sag sensor to verify its suitability for monitoring sag and temperature in high-temperature low-sag (HTLS) overhead lines. The sensor utilizes fiber Bragg grating (FBG) technology and can be integrated with the photonic voltage and current sensors that were previously developed by the authors. The response of the sag sensor was evaluated experimentally in the laboratory for temperatures from -20 to 180 degrees C and for forces up to 3 kN. The sensitivities of the sag sensor to force and to temperature estimated from the experiments were around 0.116 nm/kN and 30 pm/degrees C, respectively. The change in the sag sensor sensitivity to force was approximately 25% within the considered temperature range and the change in the sag sensor sensitivity to temperature was 2% within the considered force range. It was demonstrated that the proposed sensor can provide force and temperature measurements within the considered ranges and should be suitable for HTLS lines.
引用
收藏
页数:4
相关论文
共 50 条
  • [1] Evaluating Aeolian Vibration Performance of High-Temperature Low-Sag OHL Conductors
    Kopsidas, K.
    Al Aqil, M. A.
    Haldar, A.
    Kavanagh, T.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1775 - 1784
  • [2] Aspects to take into account in the application of mechanical calculation to high-temperature low-sag conductors
    Albizu, I.
    Mazon, A. J.
    Valverde, V.
    Buigues, G.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2010, 4 (05) : 631 - 640
  • [3] Experimental Study of Dynamic Line Rating Applied to High-Temperature Low-Sag Conductors
    Vejo, Luis
    Castro, Pablo
    Manana, Mario
    Laso, Alberto
    Lecuna, Ramon
    Bustamante, Sergio
    Sainz, Eugenio
    ENERGIES, 2025, 18 (04)
  • [4] Possibilities of Increasing the Ampacity of Overhead Lines Using High-Temperature Low-Sag Conductors in the Electric Power System of the Slovak Republic
    Margita, Frantisek
    Bena, Lubomir
    Malska, Wieslawa
    Pijarski, Pawel
    APPLIED SCIENCES-BASEL, 2024, 14 (17):
  • [5] Environmental impact of high voltage overhead powerlines with low-sag wires
    Szuba, Marek
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (5A): : 143 - 146
  • [6] Temperature and force characterization of an optical sag sensor for overhead line monitoring
    Fusiek, Grzegorz
    Singh, Himanshi
    Niewczas, Pawel
    2023 IEEE INTERNATIONAL INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE, I2MTC, 2023,
  • [7] High-temperature sag model for overhead conductors
    Chen, SL
    Black, WZ
    Fancher, ML
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) : 183 - 188
  • [8] The sag and fatigue properties of STACIR/AW as a high temperature, low sag conductor
    Lee, Sung-Doo
    Shin, Koo-Yong
    Song, Hyuk-Jin
    Lee, Dong-Il
    Min, Byung-Uk
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 3107 - +
  • [9] HIGH TEMPERATURE LOW SAG CONDUCTORS AS METHOD FOR THE IMPROVEMENT OF ELECTRICAL TRANSMISSION LINES
    Berjozkina, Svetlana
    Sauhats, Antans
    Bargels, Vladimirs
    Vanzovichs, Edvins
    ELECTRICAL AND CONTROL TECHNOLOGIES, 2012, : 200 - 205
  • [10] HIGH-VOLTAGE TRANSMISSION LINES IN TECHNOLOGY OF THE HIGH TEMPERATURE LOW SAG CONDUCTORS
    Baum, Krystyna
    RYNEK ENERGII, 2011, (03): : 94 - 98