The influence of NH3-H2O-LiBr ternary working fluid on the performance and solution circulation in ammonia absorption refrigeration system

被引:6
|
作者
Xu, Mengkai [1 ]
Li, Shuhong [1 ]
Jin, Zhenghao [1 ]
Jiang, Weixue [2 ]
Du, Kai [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Key Lab Energy Thermal Convers & Control, Minist Educ, 2 SiPaiLou, Nanjing 210096, Jiangsu, Peoples R China
[2] Yangzhou Univ, Coll Elect Energy & Power Engn, Yangzhou, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
Ammonia absorption refrigeration system; Lithium bromide; Ternary working fluid; COP; Solution circulation; VAPOR-LIQUID-EQUILIBRIA; WASTE HEAT; WATER; CYCLE; ABSORBER; NH3+H2O+LIBR; NH3-LINO3; MIXTURE;
D O I
10.1016/j.applthermaleng.2023.121297
中图分类号
O414.1 [热力学];
学科分类号
摘要
The ammonia absorption refrigeration system(AARS) has been widely applied in the recovery of industrial waste heat. Using NH3-H2O-LiBr ternary working fluid is an effective way to promote the performance of AARS. While previous studies mainly focused on the vapor-liquid equilibrium of the NH3-H2O-LiBr solution and the performance variation of the ternary system under specific working conditions, this paper aims to experimentally investigate the influence of LiBr on performance and solution circulation under various operation conditions. Experiment results indicated that 15%(w/w) was the optimum LiBr concentration across all working conditions. The COP of the ternary system was 7.55% higher than the binary system at most and the heat source temperature of the ternary system can be reduced by 25 degrees C to reach the same COP of the binary system. The COP was promoted because the rectifier cooling duty decreased by 53% at most, resulting in a reduction of its proportion in the heating capacity from 28.6% to 17.0%. Although the circulation ratio increased by 52% when the LiBr concentration increased from 5% to 15%, the absorber cooling duty experienced an average increase of 6.19%. The effectiveness of the solution heat exchanger was improved from 66.8% to 76.3% when the LiBr concentration increased from 5% to 20%. As the rise of the circulation ratio leads to higher pump power, the viscosities of the NH3-H2O, H2O-LiBr, and NH3-H2O-LiBr solutions were measured. The results demonstrated that solution temperature and NH3 concentration had more influence on solution viscosity than LiBr concentration. The viscosity increased by 6.2%, 17.1%, and 7.1% when the LiBr concentration increased by 11.26%, NH3 concentration increased by 9.5%, and solution temperature dropped by 2 degrees C, respectively.
引用
收藏
页数:16
相关论文
共 50 条
  • [1] Mathematical model and experiment investigation on electrodialysis separation process of LiBr from NH3-H2O-LiBr ternary solution in ammonia absorption refrigeration system
    Xu, Mengkai
    Li, Shuhong
    Jin, Zhenghao
    Jiang, Weixue
    Li, Yanjun
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 158 : 9 - 24
  • [2] Mechanism of action of LiBr on characteristics of NH3-H2O-LiBr ternary solution
    School of Power and Energy Engineering, Xi'an Jiaotong University, Xi'an 710049, China
    [J]. Hsi An Chiao Tung Ta Hsueh, 2008, 7 (848-851):
  • [3] Analysis of NH3-H2O-LiBr absorption refrigeration system based on membrane separator
    Yue, Xiaoyang
    Li, Shuhong
    Xu, Mengkai
    Li, Yanjun
    Du, Kai
    Yang, Liu
    [J]. Huagong Jinzhan/Chemical Industry and Engineering Progress, 2019, 38 (02): : 813 - 818
  • [4] Analysis of NH3-H2O-LiBr absorption refrigeration integrated with an electrodialysis device
    Liang, Yuanyuan
    Li, Shuhong
    Yue, Xiaoyang
    Zhang, Xiaosong
    [J]. APPLIED THERMAL ENGINEERING, 2017, 115 : 134 - 140
  • [5] Experiment Research on the Performance of Ammonia Absorption Refrigeration System With Ternary Working Fluid
    三元工质氨吸收式制冷性能实验研究
    [J]. Li, Shu-Hong (equart@seu.edu.cn), 1600, Science Press (42): : 2243 - 2249
  • [6] Experimental study of ternary NH3-H2O-LiBr absorption cycle combined with membrane separation technique
    Yue Xiao-yang
    Li Shu-hong
    Xu Meng-kai
    Li Yan-jun
    Du Kai
    Yang Liu
    [J]. SUSTAINABLE CITIES AND SOCIETY, 2018, 40 : 728 - 734
  • [7] SIMULATION RESEARCH ON ABSORPTION REFRIGERATION SYSTEM BASED ON NH3-H2O-LiBr VAPOR-LIQUID EQUILIBRIUM CALCULATION MODEL
    Wang, Shan
    Li, Shuhong
    Xu, Mengkai
    Jin, Zhenghao
    Xu, Chengcheng
    [J]. THERMAL SCIENCE, 2022, 26 (02): : 1825 - 1840
  • [8] Experimental study on enhancement of ultrasonic and TiO2nanoparticles on NH3-H2O-LiBr solution bubbling absorption
    Wang, Minqi
    Zhou, Runfa
    Jin, Zhenghao
    Li, Shuhong
    Feng, Lijie
    [J]. Dongnan Daxue Xuebao (Ziran Kexue Ban)/Journal of Southeast University (Natural Science Edition), 2022, 52 (04): : 658 - 665
  • [9] Experimental investigation of the effect of LiBr on the high-pressure part of a ternary working fluid ammonia absorption refrigeration system
    Xu, Mengkai
    Li, Shuhong
    Jin, Zhenghao
    Jiang, Weixue
    Du, Kai
    [J]. APPLIED THERMAL ENGINEERING, 2021, 186
  • [10] NH3/H2O-LIBR AS WORKING FLUID FOR THE COMPRESSION ABSORPTION CYCLE
    AHLBY, L
    HODGETT, D
    RADERMACHER, R
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1993, 16 (04): : 265 - 273