Effect mechanism of wind shields on the thermal performance for mechanical draft wet cooling towers

被引:6
|
作者
Chen, Xuehong [1 ]
Sun, Fengzhong [2 ]
Yang, Shasha [3 ]
Xia, Lijiang [1 ]
Zhang, Xiaoyu [2 ]
机构
[1] Ludong Univ, Low Carbon Energy Inst, Yantai 264000, Peoples R China
[2] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
[3] Moon Environm Technol Co Ltd, Yantai 264000, Peoples R China
关键词
Mechanical draft wet cooling tower; Thermal performance; Ventilation performance; Environmental crosswind; Wind shields; Numerical calculation; NUMERICAL-SIMULATION; FLOW; CROSSWIND; OPTIMIZATION; AIR; VENTILATION; DEFLECTORS; IMPROVE;
D O I
10.1016/j.applthermaleng.2022.119452
中图分类号
O414.1 [热力学];
学科分类号
摘要
Environmental crosswind is demonstrated to be disadvantageous for the thermal characteristics of mechanical draft cooling towers. To mitigate the adverse effect of crosswind, this study proposes an innovative structural retrofit by adding wind shields with simple structure for both single and double air inlet cooling towers. Nu-merical investigations are conducted to clarify the effect mechanism of wind shields on tower thermal perfor-mance under different crosswinds, through assessing the ventilation rate, the water temperature drop, the air flow field and water temperature field, etc. Results demonstrate that wind shields can eliminate transverse vortices to improve the distribution homogeneity of airflow velocity and water temperature, of which the effects are greatly affected by crosswind velocity and angle. Based on this mechanism, the thermal performance of these cooling towers is prominently strengthened by wind shields when crosswind angle exceeds 45 degrees. The positive effect of wind shields is the most noticeable under a crosswind angle of 90 degrees and a crosswind velocity of 10 m/s, which recovers 17.2 % and 9.4 % of the water temperature drop, and 33.1 % and 19.5 % of the ventilation rate, respectively for the single and double air inlet cooling tower. Present findings can promote applications of wind shields in practical engineering.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Crosswinds effect on the performance of natural draft wet cooling towers
    Al-Waked, Rafat
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2010, 49 (01) : 218 - 224
  • [2] A novel approach for performance assessment of mechanical draft wet cooling towers
    Naik, B. Kiran
    Muthukumar, P.
    APPLIED THERMAL ENGINEERING, 2017, 121 : 14 - 26
  • [3] EFFECT OF MECHANICAL DRAFT COOLING TOWERS ON PLANT PERFORMANCE
    KU, FS
    STUBBINS, RL
    MECHANICAL ENGINEERING, 1973, 95 (04) : 58 - 58
  • [4] Influence mechanism of the louver on the thermal performance of the mechanical draft wet cooling tower
    Deng, Weipeng
    Sun, Fengzhong
    Wang, Runchen
    He, Keting
    APPLIED THERMAL ENGINEERING, 2023, 230
  • [5] PERFORMANCE CHARACTERISTICS OF MECHANICAL DRAFT COOLING TOWERS IN THERMAL POWER PLANT
    Delalic-Gurda, Berina
    Kadric, Dzana
    Delalic, Nijaz
    THERMAL SCIENCE, 2020, 24 (02): : 1423 - 1433
  • [6] CALCULATIONS ON THERMAL PERFORMANCE CAPABILITY OF MECHANICAL DRAFT COOLING-TOWERS
    FUJITA, T
    TEZUKA, S
    BULLETIN OF THE JSME-JAPAN SOCIETY OF MECHANICAL ENGINEERS, 1984, 27 (225): : 490 - 497
  • [7] Experimental investigation on thermal performance of natural draft wet cooling towers employing an innovative wind-creator setup
    Alavi, Seyed Rashid
    Rahmati, Mehdi
    ENERGY CONVERSION AND MANAGEMENT, 2016, 122 : 504 - 514
  • [8] Effect of forced ventilation on the thermal performance of wet cooling towers
    Zhang, Deying
    Wang, Nini
    Li, Jinpeng
    Li, Jinheng
    He, Suoying
    Gao, Ming
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 35
  • [9] PERFORMANCE CURVES FOR MECHANICAL DRAFT COOLING-TOWERS
    HALLETT, GF
    JOURNAL OF ENGINEERING FOR POWER-TRANSACTIONS OF THE ASME, 1975, 97 (04): : 503 - 508
  • [10] PERFORMANCE CURVES FOR MECHANICAL DRAFT COOLING TOWERS.
    Hallett, G.F.
    Journal of Engineering for Power, Transactions ASME, 1975, 97 Ser A (04): : 503 - 508