Characterization of internal discharge shock waves of gas-insulated switchgears using shadowgraphy

被引:0
|
作者
Jia, Chenglong [1 ]
Chu, Penghao [2 ]
Zhao, Wenbin [1 ]
Tang, Zhong [1 ,3 ]
机构
[1] Shanghai Univ Elect Power, Coll Elect Engn, Shanghai, Peoples R China
[2] State Grid Xinxiang Power Co, Xinxiang, Peoples R China
[3] Shanghai Univ Elect Power, Coll Elect Engn, Shanghai 200090, Peoples R China
关键词
aerodynamics; cameras; discharges (electric); gas-insulated switchgear; wave propagation; PULSED DISCHARGE;
D O I
10.1049/gtd2.13050
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The gas-insulated switchgear (GIS) is a vital component of a power system, and understanding the shock wave characteristics of its internal discharge is crucial to ensure the safe and stable operation of the entire system. In this study, a high-speed shadowing technique is employed to obtain the shadowgraphs of a typical flow-field evolution of sulfur hexafluoride (SF6) gas following the breakdown of a pin-plate gap inside a GIS. Experimental data were used to derive parameters, including the Mach number, propagation speed, distance of the discharge shock wave, and the temperature, pressure, density, and velocity of the SF6 gas after wave generation. With a 0.2-mm discharge gap and 0.4-MPa pressure, the discharge generates a spherical shock wave, centred at the contact between the discharge channel and electrodes, that propagates in all directions. The shock wave gradually weakens after 20 mu s, propagating at near-sonic speed, and its Mach number decreases from 2.92 to 1.15; similarly, its post-wave parameters sharply decrease during the first 20 mu s. Additionally, a significant reflection occurs when the shock wave propagates to the metal wall. The authors' findings provide a valuable reference for detecting and diagnosing the internal discharge in GISs. This study focuses on understanding the characteristics of internal discharge shock waves in gas-insulated switchgears (GISs). Using state-of-the-art experimental techniques, such as high-speed shadowgraphy, the authors have investigated the phenomenon of shock waves induced by gas discharge in GISs, and extensively assessed various thermodynamic parameters of interest.image
引用
收藏
页码:5378 / 5385
页数:8
相关论文
共 50 条
  • [1] Anomaly Detection for Partial Discharge in Gas-Insulated Switchgears Using Autoencoder
    Thi, Ngoc-Diem Tran
    Do, The-Duong
    Jung, Jae-Ryong
    Jo, Hyangeun
    Kim, Yong-Hwa
    IEEE ACCESS, 2020, 8 : 152248 - 152257
  • [2] Outdoor Insulation and Gas-Insulated Switchgears
    Fofana, Issouf
    Brettschneider, Stephan
    ENERGIES, 2022, 15 (21)
  • [3] Identification of Partial Discharge Defects in Gas-Insulated Switchgears by Using a Deep Learning Method
    Gu, Feng-Chang
    IEEE ACCESS, 2020, 8 : 163894 - 163902
  • [4] Metal particle contamination in gas-insulated switchgears/gas-insulated transmission lines
    Wang, Jian
    Hu, Qi
    Chang, Yanan
    Wang, Jingrui
    Liang, Ruixue
    Tu, Youping
    Li, Chuanyang
    Li, Qingmin
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2021, 7 (05) : 1011 - 1025
  • [5] Disturbance Elimination for Partial Discharge Detection in the Spacer of Gas-Insulated Switchgears
    Wang, Guoming
    Kil, Gyung-Suk
    Ji, Hong-Keun
    Lee, Jong-Hyuk
    ENERGIES, 2017, 10 (11):
  • [6] Investigating the characteristics of internal discharge shock waves in gas-insulated switchgear under varied gap configurations
    Jia, Chenglong
    Haochu, Peng
    Zhao, Wenbin
    Tang, Zhong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2024, 18 (04) : 653 - 664
  • [7] MAGNETIC FIELD EMISSION OF GAS-INSULATED SWITCHGEARS
    Mach, Martin
    Summer, Raimund
    PROCEEDINGS OF THE 6TH INTERNATIONAL SCIENTIFIC CONFERENCE ELECTRIC POWER ENGINEERING 2005, 2005, : 326 - 333
  • [8] DEVELOPMENT OF PARTIAL DISCHARGE DETECTION METHOD USING AN AUTOREGRESSIVE MODEL IN GAS-INSULATED SWITCHGEARS (GIS)
    INUJIMA, H
    MASUI, T
    MAEKAWA, H
    ELECTRICAL ENGINEERING IN JAPAN, 1995, 115 (01) : 1 - 9
  • [9] Development of partial discharge detection method using an autoregressive model in gas-insulated switchgears (GIS)
    Inujima, Hiroshi, 1600, Scripta Technica Inc, New York, NY, United States (115):
  • [10] Discharge Characteristics and Detectability of Metal Particles on the Spacer Surface in Gas-Insulated Switchgears
    Li, Xing
    Liu, Weidong
    Xu, Yuan
    Ding, Dengwei
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (01) : 187 - 196