A New Technique for Connecting a Dual Excitation Synchronous Generator to the Power Grid

被引:0
|
作者
De Fazio, Roberto [1 ]
Alerksousi, Ayman [2 ]
Spongano, Lorenzo [1 ]
Al-Naami, Bassam [3 ]
Al-Odienat, Abdullah [4 ]
Visconti, Paolo [1 ]
机构
[1] Univ Salento, Dept Innovat Engn, I-73100 Lecce, Italy
[2] Damascus Univ, Dept Elect Power Engn, POB 30621, Damascus, Syria
[3] Hashemite Univ, Fac Engn, Dept Biomed Engn, Zarqa 13133, Jordan
[4] Mutah Univ, Dept Elect Engn, Al Karak 61710, Jordan
关键词
dual excitation synchronous generator; DESG mathematical model; DESG characteristics; DESG two-axis flux linkage equations; STABILITY;
D O I
10.3390/en16247936
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Due to an increasing demand for electric power and changes in the typology of loads, stability has become a major concern in power systems. As the system stability is directly related to the response of the connected generator, recent research has focused on enhancing generators' stability and improving their response to load variations. This study focuses on adding another excitation winding on to the q-axis, perpendicular to the conventional excitation winding on the d-axis, to control both active and reactive power. This paper studies and compares the performance of the dual excitation synchronous generator (DESG) to conventional synchronous generators. The mathematical equations are derived, and a mathematical model is then developed. The experimental tests have been conducted using a laboratory model consisting of a two-phase synchronous generator driven by a DC motor with different loads. The obtained results and radial diagrams for the different loading types are presented and evaluated. Therefore, a new approach has been designed to connect the DESG directly to the power grid without any electronic components using a special coupling that works in one direction. Two perpendicular excitation coils, d and q, were formed from the existing coils, and the tests were carried out on all loads, ensuring that the revolving angle (i.e., the stability angle phi) was fixed. The results show that the proposed method offers significant cost savings, potentially amounting to 15-20% of the unit price. The experimental results confirm that the DESG significantly improves the generator stability by maintaining a constant rotor angle delta, which requires using an automatic angle regulator (AAR) in addition to the conventional automatic voltage regulator (AVR).
引用
收藏
页数:24
相关论文
共 50 条
  • [1] Electric Parameters Identification of Synchronous Generator Connecting to the Grid
    Frolov, Mikhail Yu.
    Fishov, Alexander G.
    2016 11TH INTERNATIONAL FORUM ON STRATEGIC TECHNOLOGY (IFOST), PTS 1 AND 2, 2016,
  • [2] PERFORMANCE OF DUAL-EXCITATION SYNCHRONOUS GENERATOR AT LEADING POWER-FACTORS
    AGGARWAL, RK
    FISHWICK, E
    HOGG, BW
    PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1975, 122 (08): : 813 - 818
  • [3] Synchronous Control of Connecting AC-Excited Doubly-Fed Wind Power Generator to the Grid
    Mi Zeng-qiang
    Wang Xin
    Shen Yan
    2008 IEEE INTERNATIONAL CONFERENCE ON INDUSTRIAL TECHNOLOGY, VOLS 1-5, 2008, : 827 - 831
  • [4] Research on power tracking excitation control system of dual-excited synchronous generator
    Xu G.
    Wang Z.
    Li W.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2022, 42 (06): : 192 - 198
  • [5] Employing Virtual Synchronous Generator with a New Control Technique for Grid Frequency Stabilization
    Saeedian, Meysam
    Eskandari, Bahman
    Rouzbehi, Kumars
    Taheri, Shamsodin
    Pouresmaeil, Edris
    2020 22ND EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'20 ECCE EUROPE), 2020,
  • [6] Power Tracking Excitation Control and Its Parameter Optimization of Dual-Excited Synchronous Generator
    Xu, Guorui
    Li, Zijing
    Wang, Zhenzhen
    Li, Weili
    Zhan, Yang
    Zhao, Haisen
    Liu, Wenmao
    Luo, Yingli
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2022, 58 (06) : 7099 - 7109
  • [7] Study on Power Tracking Excitation Control and Parameters Sensitivity of Dual-Excited Synchronous Generator
    Xu, Guorui
    Wang, Zhenzhen
    Li, Weili
    Zhan, Yang
    Zhao, Haisen
    Luo, Yingli
    2021 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2021, : 4240 - 4245
  • [8] Reducing the Excitation Circuit Power of a Traction Synchronous Generator
    Loginova E.Y.
    Pudovikov O.E.
    Russian Electrical Engineering, 2023, 94 (09) : 633 - 640
  • [9] Connecting an Embedded Generator to an Existing Facility in Singapore Power Grid
    Xuan, Tan Xiao
    Logenthiran, T.
    Yathunanthan, K.
    Amirthan, P.
    PROCEEDINGS OF THE 2016 IEEE REGION 10 CONFERENCE (TENCON), 2016, : 1190 - 1193
  • [10] Analytical technique for synchronous generator loss-of-excitation protection
    Noroozi, Naser
    Yaghobi, Hamid
    Alinejad-Beromi, Yoosef
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (09) : 2222 - 2231